Plan Review Details - Permit 13061104
Plan Review Stops For Permit 13061104
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-01-07 Cont ID  
Sent By jwitmer Date 2014-01-07 Time 07:21 Rev Time 0.00
Received By jwitmer Date 2014-01-07 Time 07:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-11-26 Cont ID  
Sent By jwitmer Date 2013-11-26 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2013-11-26 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-17 Cont ID  
Sent By JWITMER Date 2013-08-17 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2013-08-17 Time 10:17 Sent To  
Notes
2013-08-17 11:01:27BUILDING PLAN REVIEW
 PERMIT: 13061104
 ADD: 5800 S DIXIE
 CONT: MIKE MOORE
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: AUGUST 17/2013
 ACTION: DENIED
  
 FROM 1ST REVIEW, QUESTION WAS ASKED IF THIS BUILDING IS
 FIRE SPRINKLERED, NOT PROVIDED, ASSUMED FOR THIS PLAN
 REVIEW, NON-SPRINKLERED.
  
 1) SHEET A1.1: THE CONTRACTOR WILL NEED TO UPDATE THE
 EXISSTING PERMIT APPLICATION AND APPLY FOR A SECOND
 PERMIT APPLICATION. THE PLANS INDICATE THE SPLITING OF
 A SINGLE TENANT SPACE INTO TWO INDIVUAL TENANT SPECES
 BY CREATING A TENANT SEPERATION WALL. THE CURRENT
 PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK ONLY
 LIST A DEMISSING WALL. THE PLANS REFLECT ALSO THE
 CREATION OF TWO RESTROOMS, ONE IN EACH TENANT SPACE.
 NOTE THE VALLUE FOR THE NEW TENANT SEPERATION WALL, 2
 NEW RESTROOM WALLS, AND THE OUTFITTING OF RESTROOMS IS
 ONLY $1,500.00.
  
 1A) ON THE EXISTING PERMIT APPLICATION UPDATE THE
 DESCRIPTION OF WORK, ADD A SUITE NUMBER TO THE
 APPLICATION AND INCREASE THE VALUE OF WORK TO BE
 COMPLETED UNDER THIS PERMIT.
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 1B) SUBMIT A SECOND PERMIT PERMIT APPLICATION UPDATE
 THE DESCRIPTION OF WORK, ADD A SUITE NUMBER TO THE
 APPLICATION AND INCREASE THE VALUE OF WORK TO BE
 COMPLETED UNDER THIS PERMIT.
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 1C) NOTE INDICATES THE CHOICE OF TWO 1 HOUR UL RATINGS
 FOR THE 1 HOUR TENANT SEPERATION WALL. PLEASE SUBMIT
 ONE UL DESIGN AND PRODUCE THE DESIGN ON THE PLANS,
 INSPECTORS DO NOT CARRY A UL BOOK IN THEIR CAR.
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 PLEASE NOTE SOME OF THE UL LISTINGS INDICATE TO TAKE
 THE WALL TO THE CEILING LINE. PLEASE REVIEW2010 FBC-B
 709.4 CONTINUITY.
 FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY
 ATTACHED THERETO. IF THE PARTITIONS ARE NOT CONTINUOUS
 TO THE SHEATHING, DECK OR SLAB, AND WHERE CONSTRUCTED
 OF COMBUSTIBLE CONSTRUCTION, THE SPACE BETWEEN THE
 CEILING AND THE SHEATHING, DECK OR SLAB ABOVE SHALL BE
 FIREBLOCKED OR DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS
 717.2 AND 717.3 AT THE PARTITION LINE. THE SUPPORTING
 CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED
 FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT
 FOR WALLS SEPARATING TENANT SPACES IN COVERED MALL
 BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS
 SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN
 BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION.
  
 1D) THE PLANS DO NOT INDICATE WHICH WAY THE ROOF
 FRAMING MEMBERS ARE DESIGNED, IF THE ROOF FRAMING
 MEMBERS PENETRATE THE NEW 1 HOUR FIRE RATED WALL OR
 THERE IS ANY OTHER PENETRATIONS OF THE 1 HOUR RATED
 WALL COMPLIANCE WITH 2010 FBC-B 709.7 PENETRATIONS.
 PENETRATIONS OF FIRE PARTITIONS SHALL COMPLY WITH
 SECTION 713.
 713.3.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS
 SHALL COMPLY WITH SECTION 713.3.1.1 OR 713.3.1.2.
 713.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 713.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 1E) 2010 FBC-B 713.6
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 1F) PLEASE REVIEW PLUMBING COMMENTS ABOUT THE
 ACCESSIBLE RESTROOM THAT IS DESIGNED WITH THE OUTSIDE
 DIMENSION OF 7'-2", THE MINIMUM INTERIOR DIMENSION IS
 7'-1". 2010 FL ACC CODE FIGURE 604.8.1.6.
  
 SUGGEST A MEETING BEFORE PLANS ARE RESUBMITTED TO
 REVIEW AND MAKE SURE A PERMIT WILL BE ABLE ISSUED UNDER
 THE NEXT REVIEW!!!!
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2013-07-11 Time 14:22 Sent To  
Notes
2013-07-11 14:34:14BUILDING PLAN REVIEW
 PERMIT: 13061104
 ADD: 5800 S DIXIE
 CONT: MIKE MOORE
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 11/2013
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD FOR THE PLANS WILL NEED TO
 PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER
 FOR TAKING RESPONSIBILITY FOR THE PLAN. 2010 WPB
 ADMINISTRATIVE CODE 107.1.
  
 2) PLANS FAIL TO SHOW EXISTING CONDITIONS AND THE
 PROPOSED NEW WORK THAT WILL COMPLETED UNDER THIS
 PERMIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 3) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 4) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 MINIMUM BUILDING TYPE
 FIRE SPRINKLERED
 OCCUPANCY TYPE: USAGE, SHOW WHAT USAGE THE ROOMS WILL
 BE USED FOR
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 FIRE RATING OF WALLS
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-01-16 Cont ID  
Sent By albarran Date 2014-01-16 Time 15:39 Rev Time 0.00
Received By albarran Date 2014-01-16 Time 14:38 Sent To I
Notes
2014-01-16 15:40:16NOTICE:
 AS INDICATED ON NEC 422.52, ELECTRIC DRINKING FOUNTAINS
 SHALL BE ON A GFI PROTECTED CIRCUIT.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-12-09 Cont ID  
Sent By albarran Date 2013-12-09 Time 17:04 Rev Time 0.00
Received By albarran Date 2013-12-09 Time 17:00 Sent To P
Notes
2013-12-09 17:08:33ELECTRICAL REVIEW DENIED FOR THE SECOND TIME. AS
 PREVIOUSLY STATED ON THE FIRST REVIEW, IF A BATHROOM IS
 REQUIRED, YOU SHALL INCLUDE ON THE DRAWINGS THE MINIMUM
 ELECTRICAL REQUIREMENTS FOR THE BATHROOMS. AS PART OF
 THE ELECTRICAL SUBMITTAL, A PANEL SCHEDULE SCHEDULE
 REFLECTING THE BATHROOM CKT. AS WELL AS THE EMERGENCY
 LIGHTING SHALL BE PROVIDED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-09 Cont ID  
Sent By dharvey Date 2013-09-09 Time 14:10 Rev Time 0.00
Received By dharvey Date 2013-09-09 Time 14:10 Sent To  
Notes
2013-09-09 14:14:05FIRST REVIEW - 9-9-13
  
 ELECTRIC DENIED. PLEASE REFER TO BUILDING AND PLUMBING
 COMMENTS. IF BATHROOMS ARE REQUIRED, ELECTRIC MUST BE
 SHOWN. IF WATER COOLER IS REQUIRED, ELECTRIC MUST BE
 SHOWN.
  
 PLEASE SHOW PANEL LOATIONS AND INDICATE CIRCUITS FOR
 EMERGENCY FIXTURE AND BATHROOM AND COOLER IF REQUIRED
 BY OTHER CODES.
  
 END OF REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2014-01-08 Cont ID  
Sent By lphilmor Date 2014-01-08 Time 10:35 Rev Time 0.00
Received By lphilmor Date 2014-01-08 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-12-12 Cont ID  
Sent By lphilmor Date 2013-12-12 Time 13:39 Rev Time 0.00
Received By lphilmor Date 2013-12-12 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-08-17 Cont ID  
Sent By WJOLIN Date 2013-08-17 Time 19:07 Rev Time 0.00
Received By wjolin Date 2013-08-17 Time 18:54 Sent To  
Notes
2013-08-17 19:07:415800 SOUTH DIXIE HIGHWAY
 PERMIT #13061104
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 101, SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PER NFPA 101, SECTION 8.3.5.1, PENETRATIONS THROUGH A
 FIRE-RATED WALL ASSEMBLY SHALL BE PROTECTED BY A
 FIRESTOP SYSTEM OR DEVICE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-07-03 Cont ID  
Sent By wjolin Date 2013-07-03 Time 13:07 Rev Time 0.00
Received By wjolin Date 2013-07-03 Time 12:24 Sent To  
Notes
2013-07-03 13:06:495800 SOUTH DIXIE HIGHWAY
 PERMIT #13061104
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED ON THE PLANS.
  
 PLANS DO NOT INDICATE WHICH WALL(S) IS BEING
 CONSTRUCTED.
  
 PLANS DO NOT INDICATE IF THIS IS A FIRE RATED TENANT
 SEPARATION WALL.
  
 NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO PERFORM A
 THOROUGH AND COMPLETE PLAN REVIEW. GENERALLY, A LIFE
 SAFETY PLAN SHOWING ALL EXIT DOORS, OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
 IS NEEDED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-01-16 Cont ID  
Sent By skennedy Date 2014-01-16 Time 16:43 Rev Time 0.00
Received By skennedy Date 2013-12-31 Time 14:21 Sent To  
Notes
2014-01-16 15:40:55SENT TO SAK 1 OF 2
2013-12-31 14:22:13INCOMING SENT TO B-14 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-12-13 Cont ID  
Sent By shill Date 2013-12-13 Time 18:26 Rev Time 0.00
Received By shill Date 2013-11-22 Time 17:20 Sent To  
Notes
2013-11-22 17:21:33B08 - TRAVELING WITH 13110723

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-09 Cont ID  
Sent By dharvey Date 2013-09-09 Time 14:14 Rev Time 0.00
Received By dharvey Date 2013-09-09 Time 14:14 Sent To  
Notes
2013-08-12 08:51:40B42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2013-06-28 Time 04:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-01-07 Cont ID  
Sent By jwitmer Date 2014-01-07 Time 08:10 Rev Time 0.00
Received By jwitmer Date 2014-01-07 Time 07:09 Sent To  
Notes
2014-01-07 07:19:35 
 PLUMBING PLAN REVIEW
 PERMIT: 13061104
 ADD: 5800 S DIXIE HWY, SUITE #A
 CONT: MIKE MOORE CONSTRUCTION
 TEL: (561)301-9468
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JAN. 07/2014
  
 ACTION:PLUMBING PROVISO:
  
 1) A HIGH/ LOW DRINKING FOUNTAIN IS REQUIRED. 2010
 FBC-BLUMBING TABLE 403.1 SEE FOOTNOTES (E) & (F):
 FOOTNOTE (E). THE MINIMUM NUMBER OF REQUIRED DRINKING
 FOUNTAINS SHALL COMPLY WITH TABLE 403.1 AND THE FLORIDA
 BUILDING CODE, ACCESSIBILITY.
 FOOTNOTE (F). DRINKING FOUNTAINS ARE NOT REQUIRED FOR
 AN OCCUPANT LOAD OF 15 OR FEWER. NOTE THE OCCUPANT LOAD
 FOR THIS SPACE MIN. BUSINESS IS 29/ MERCANTILE 95.
  
 2) 2010 FBC-ACCESSIBILITY CODE: 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-12-12 Cont ID  
Sent By lwagner Date 2013-12-12 Time 09:32 Rev Time 0.00
Received By skennedy Date 2013-12-12 Time 09:19 Sent To FIRE
Notes
2013-12-12 09:29:43FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 REVIEW COMMENT #2 HAS NOT BEEN ADDRESSED:
 2. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER 15
 OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN .
 PLUMBING TABLE 403.1 (E) (F)
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 NOTE: UNLESS A PLUMBING ISOMETRIC IS PROVIDED, A
 PLUMBING APPLICATION, DRAWINGS, FEES, AND PERMIT WIILL
 BE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-15 Cont ID  
Sent By lwagner Date 2013-08-15 Time 12:35 Rev Time 0.00
Received By lwagner Date 2013-08-15 Time 12:16 Sent To  
Notes
2013-08-15 12:33:11FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. THE NEW RESTROOM IN THE 3508 S.F. RETAIL SPACE WOULD
 NOT MEET (IN THE SHOWN CONFIGURATION) THE 2010
 ACCESSIBILITY CODE. THE RESTROOM WILL BE REQUIRED TO BE
 A MINIMUM OF 7'-1" WIDE TO ACHIEVE THE REQUIRED 60"
 CLEAR SPACE FOR THE WATER CLOSET. (OTHER CONFIGURATIONS
 ARE ALSO POSSIBLE).
 FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE
 AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM)
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
 PLEASE ALSO SEE FIGURE 604.8.1.6.
  
 2. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER 15
 OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN .
 PLUMBING TABLE 403.1 (E) (F)
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 3. NO PLUMBING DRAWINGS WERE FOUND WITH THIS PLAN. IF
 THE PLUMBING CONTRACTOR IS GOING TO DO THE DRAWING AT
 THE TIME OF APPLICATION PLEASE MAKE NOTE OF THIS WITH
 THE NEXT SUBMITTAL.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  