Plan Review Details - Permit 13060993
Plan Review Stops For Permit 13060993 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-07-11 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-07-11 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-07-11 |
Time |
09:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-07-05 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-07-05 |
Time |
12:18 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-07-05 |
Time |
11:51 |
Sent To |
G |
|
Notes |
2013-07-05 12:19:13 | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | PROVIDE SPECIFICATION FOR ATS. VERIFY SERVICE RATING OF | | EQUIPMENT. NEC 110.3, 110.8, 230.66 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2013-07-05 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2013-07-05 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2013-07-05 |
Time |
13:39 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-07-07 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2013-07-07 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2013-06-26 |
Time |
07:31 |
Sent To |
|
|
Notes |
2013-06-27 07:31:56 | SENT TO GENERATOR BOX. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2013-07-07 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2013-07-07 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2013-07-07 |
Time |
16:25 |
Sent To |
|
|
Notes |
2013-07-07 16:26:35 | GENERATOR SHALL BE LOCATED A MINIMUM OF ONE (1) FOOT | | FROM THE SIDE PROPERTY LINE. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | PLANNER, AT (561) 822-1448. |
|
|
|