Plan Review Details - Permit 13060989
Plan Review Stops For Permit 13060989
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2013-07-11 Time 12:55 Sent To  
Notes
2013-07-11 13:01:24BUILDING PLAN REVIEW
 PERMIT: 13060989
 ADD: 1801 S FLAGLER DR # 802
 CONT:MARYJULECONSTRUCTION
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: JULY 11/ 2013
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1) PLANS WILL REQUIRE A DETAIL FOR THE CREATION OF A
 NEW DROPPED CEILING AND SOFFITS. THE DETAIL SHALL
 INCLUDE, FRAMING MATERIALS, SIZE, GAUGE, SPACING OF
 FRAMING, SPAN OF CEILING BEING HUNG, IF STIFF BACKS ARE
 REQUIRED? PROVIDE DETAIL OF HOW THE TRAY DROPPED CEILNG
 WILL BE ATTACHED TO THE DECK ABOVE, TYPE OF FASTENER,
 AND LENGTH, ALSO INCLUDE TYPE OF CEILING FINISH AND
 THICKNESS OF MATERIAL. WILL THE DROPPED CEILING ABOVE
 BE CONSIDERED A PLENUM?
 2010 WPB ADMINISTRATIVE CODE 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 2) PLANS SHOW A KITCHEN WALL BEING MOVED, NEW FLOOR
 AREA IS GOING TO BE REVEALED. IF THE FLOOR FINISH OF
 THE KITCHEN IS NOT BEING REMOVED, THIS IS CONSIDERED A
 REPAIR AND NO FLOOR INSULATION IS NEEDED. IF THE
 KITCHEN FLOOR IS REMOVED THEN COMPLIANCE WITH THE
 FOLLOWING SECTIONS WILL NEED TO BE REQUIRED:
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 2B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FBC-B 2010
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-08 Cont ID  
Sent By dharvey Date 2013-07-08 Time 10:15 Rev Time 0.00
Received By dharvey Date 2013-07-08 Time 10:06 Sent To  
Notes
2013-07-08 10:15:19BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-03 Cont ID  
Sent By wjolin Date 2013-07-03 Time 12:08 Rev Time 0.00
Received By wjolin Date 2013-07-03 Time 12:04 Sent To  
Notes
2013-07-03 12:08:541801 SOUTH FLAGLER DRIVE - #802
 PERMIT #13060989
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EXISTING APARTMENT BUILDINGS NOT PROTECTED BY AUTOMATIC
 SPRINKLERS OR A COMPLETE AUTOMATIC SMOKE DETECTION
 SYSTEM SHALL HAVE SINGLE STATION OR MULTI-STATION SMOKE
 ALARMS (HARD-WIRED OR BATTERY POWERED) INSTALLED INSIDE
 EACH BEDROOM AND DIRECTLY OUTSIDE BEDROOM DOORS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2013-06-26 Time 08:26 Sent To  
Notes
2013-06-27 08:27:16B28

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2013-07-11 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-02 Cont ID  
Sent By lwagner Date 2013-07-02 Time 14:01 Rev Time 0.00
Received By lwagner Date 2013-07-02 Time 13:54 Sent To  
Notes
2013-07-02 14:02:00PLUMBING PERMIT REQUIRED.