Plan Review Details - Permit 13060772
Plan Review Stops For Permit 13060772
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-03-21 Cont ID  
Sent By shill Date 2014-03-21 Time 19:22 Rev Time 0.00
Received By shill Date 2014-03-21 Time 19:22 Sent To  
Notes
2014-03-21 19:22:39TRUSS DRAWINGS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-11-04 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2013-11-04 Time 14:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-22 Cont ID  
Sent By jwitmer Date 2013-07-22 Time 14:44 Rev Time 0.00
Received By jwitmer Date 2013-07-22 Time 14:26 Sent To  
Notes
2013-07-22 14:44:50 
 1ST REVIEW
 DATE: JULY 22/2013
 ACTION: DENIED
 PAVILION
  
 1) MISSING SOILS REPORT. 2010 FBC-B 1803.6.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS, ,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4) MISSING ON PLANS 2010 FBC-B 1209.2 ATTIC SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-12 Cont ID  
Sent By dharvey Date 2013-09-12 Time 11:03 Rev Time 0.00
Received By dharvey Date 2013-09-12 Time 10:51 Sent To  
Notes
2013-09-12 11:03:36BY RL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2013-08-20 Cont ID  
Sent By   Date 2013-08-20 Time   Rev Time 1.00
Received By   Date 2013-08-20 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-05 Cont ID  
Sent By scaldero Date 2013-07-05 Time 08:41 Rev Time 0.00
Received By scaldero Date 2013-07-02 Time 08:41 Sent To  
Notes
2013-07-05 08:42:06SHOW LOCATIONS OF FIRE EXTINGUISHERS. (LIFE SAFETY PLAN
 SHEET A191).

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-09-12 Time   Rev Time 0.00
Received By rregueir Date 2013-06-24 Time 15:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-10-24 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2013-10-24 Time 14:20 Sent To  
Notes
2013-11-04 14:21:41IMPACT FEES PAID TOTAL $1,647,080.64 JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-07-22 Cont ID  
Sent By jwitmer Date 2013-07-22 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2013-07-22 Time 14:45 Sent To  
Notes
2013-07-22 14:46:021ST REVIEW
 DATE: JULY 22/2013
 ACTION: DENIED
 PAVILION
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-03 Cont ID  
Sent By lwagner Date 2013-07-03 Time 12:53 Rev Time 0.00
Received By lwagner Date 2013-07-03 Time 10:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-01-17 Cont ID  
Sent By rregueir Date 2014-01-17 Time 16:31 Rev Time 0.00
Received By rregueir Date 2014-01-17 Time 16:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-10-10 Cont ID  
Sent By ajones Date 2013-10-10 Time 11:25 Rev Time 0.00
Received By ajones Date 2013-10-10 Time 11:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-07-23 Cont ID  
Sent By avann Date 2013-07-23 Time 14:17 Rev Time 0.00
Received By ajones Date 2013-07-23 Time 14:16 Sent To  
Notes
2013-07-23 14:20:277/23/13- FAILED
 THE PAVILLION BUILDING WAS NOT PART OF THE SITE PLAN
 APPROVED BY THE CITY COMMISSION. A MINOR PLANNED
 DEVELOPMENT AMENDMENT IS REQUIRED TO ADD THIS BUILDING.
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
  
  
  
2013-07-10 15:04:497/10/13