Plan Review Details - Permit 13060742
Plan Review Stops For Permit 13060742
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-06-21 Cont ID  
Sent By lwagner Date 2013-06-21 Time 13:02 Rev Time 0.00
Received By lwagner Date 2013-06-21 Time 12:50 Sent To  
Notes
2013-06-21 13:03:46G2411.1.1 (310.1.1) CSST.
 CORRUGATED STAINLESS STEEL TUBING (CSST) GAS PIPING
 SYSTEMS SHALL BE BONDED TO THE ELECTRICAL SERVICE
 GROUNDING ELECTRODE SYSTEM AT THE POINT WHERE THE GAS
 SERVICE ENTERS THE BUILDING. THE BONDING JUMPER SHALL
 BE NOT SMALLER THAN 6 AWG COPPER WIRE OR EQUIVALENT.
  
 G2420.4 (409.4) MP REGULATOR VALVES.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-21 Cont ID  
Sent By lwagner Date 2013-06-21 Time 13:02 Rev Time 0.00
Received By lwagner Date 2013-06-20 Time 15:18 Sent To  
Notes
2013-06-20 15:19:12INCOMING SENT TO <$5K PLUMBING BOX. JW