Plan Review Details - Permit 13060734
Plan Review Stops For Permit 13060734
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-26 Cont ID  
Sent By rmcdouga Date 2013-06-26 Time 09:33 Rev Time 0.00
Received By rmcdouga Date 2013-06-26 Time 09:33 Sent To  
Notes
2013-06-26 09:39:48AFTER TALKING WITH THE HOME OWNER, THE CONTRACTOR HAS
 REMOVED THE TWO SMALL FLAT DECKS FROM THE SCOPE OF
 WORK. SEE NOTARIZED LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-20 Cont ID  
Sent By rmcdouga Date 2013-06-20 Time 13:18 Rev Time 0.00
Received By rmcdouga Date 2013-06-20 Time 13:18 Sent To  
Notes
2013-06-20 13:38:102010 FBC
  
 DENIED BUILDING
  
 1) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE CERTAINTEED CORP. FLINTASTIC SA ROOFING SYSTEM (
 NOA 10-0330.02 ) PRODUCT APPROVAL AND IT'S MAXIMUM
 DESIGN PRESSURE WILL BE USED ON THE FLAT DECK. DCA RULE
 9N-3 AND FBC R301.2.1
  
 2) THE STRUCTURE IS LOCATED IN A 170 MPH VULT (132 MPH
 VALT) WIND-SPEED AND EXPOSURE CATEGORY D. FOR A
 STRUCTURE WITH A 15' MRH, THE UPLIFT PRESSURES FOR ROOF
 ZONES 2 &3 ARE - 99.0 PSF AND -116.2 PSF. THESE
 PRESSURES EXCEED THE MAXIMUM DESIGN PRESSURES IN THE
 PRODUCT APPROVAL. SUBMIT TWO COPIES OF SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION
 NUMBER 7 OF NOA 10-0330.02. FBC R 301.2.1 AND CITY
 AMENDMENTS 107.2.1.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]