Plan Review Details - Permit 13060645
Plan Review Stops For Permit 13060645
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date 2013-08-16 Cont ID  
Sent By jgomez Date 2013-08-15 Time 17:18 Rev Time 0.00
Received By jgomez Date 2013-08-15 Time 17:12 Sent To  
Notes
2013-08-15 17:19:58PROVIDE RAS 117 CALCULATIONS WITH ENGINEER'S CURRENT
 SEAL. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-02 Cont ID  
Sent By jgomez Date 2013-08-02 Time 17:58 Rev Time 0.00
Received By jgomez Date 2013-08-02 Time 17:50 Sent To  
Notes
2013-08-02 18:01:08REVISION SECOND BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE ENERGY CALCULATIONS. NEED TO SPECIFY R-30
 INSULATION IN THE CEILING AS REQUIRED BY TABLE 402A OF
 ENERGY CALCULATIONS SUBMITTED.
  
 2- TYPICAL WALL SECTION ON SHEET A-4:
 A) R-30 CEILING INSULATION REQUIRED BY TABLE 402A OF
 THE ENERGY CALCULATIONS SUBMITTED DOESN'T FIT ON 2X8
 WOOD JOISTS. REVISE AS REQUIRED.
  
 B) ORIGINAL COMMENT: "SPECIFY SIZE OF VENTILATION TO
 COMPLY WITH SEC. R806 OF 2010 FBC-RESIDENTIAL. ***NOTE:
 KEEP IN MIND THAT NEED CROSS VENTILATION".
  
 ***THIS COMMENT WAS NOT PROPERLY ADDRESSED. WALL
 SECTION SPECIFIES 4" X 6" VENT TO MATCH EXISTING. THIS
 DOESN'T PROVIDE CROSS VENTILATION AND VENT SPACING IS
 NOT SPECIFIED EITHER. REVISE AS REQUIRED.
  
 3- MASTER BEDROOM EGRESS WINDOW: FLOOR PLAN ON SHEET
 A-2 SPECIFIES 52" X 60" SINGLE HUNG WINDOW, WHILE EAST
 ELEVATION ON SHEET A-3 SPECIFIES 52"X 54" SINGLE HUNG
 WINDOW. THERE IS A DISCREPANCY ON SIZE. REVISE AS
 REQUIRED TO MATCH AND MAKE SURE WINDOW COMPLIES WITH
 EGRESS SEC. R310.
  
 4- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL USED SAYS "CERTIFICATE". THIS
 SEAL IS NO ALLOWED SINCE JANUARY 2006. NEED TO RE-SEAL
 ALL DRAWINGS AND THE RAS 117 CALCULATIONS SUBMITTED.
  
 5- REVISION FEES WERE ADJUSTED ACCORDING TO EACH NEW
 SHEET SUBMITTED. OWES $339.00. THIS INCLUDES THE $30.OO
 ADDED BY ZONING FOR THEIR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-09 Cont ID  
Sent By jgomez Date 2013-07-09 Time 14:51 Rev Time 0.00
Received By jgomez Date 2013-07-09 Time 11:38 Sent To  
Notes
2013-07-09 16:21:15RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED: ITEM # 7(B).
 NEED R-13 MIN TO COMPLY WITH TABLE 402A ON ENERGY
 CALCULATIONS SUBMITTED.
  
 2- SHEET A-3B:
 A) SPECIFY INSULATION ON THE RAISED FLOOR. COORDINATE
 WITH ENERGY CALCULATIONS ITEM #1 ABOVE. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 B) TYPICAL WALL SECTION:
 (1) IT'S NOT CLEAR IF EXTERIOR WALL IS 2X4 OR 2X6. WALL
 SECTION CALLS FOR 2X4 DOUBLE TOP PLATE AND 2X4 BOTTOM
 PLATE, WHILE SPECS FOR WALL CALLS FOR 2X6 WOOD STUDS
 @16"O.C. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
 (2) R-19 INSULATION SPECIFIED ON THE ENERGY
 CALCULATIONS DOESN'T FIT ON A 2X6 WALL. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 (3) R-30 CEILING INSULATION REQUIRED BY THE ENERGY
 CALCULATIONS DOESN'T FIT ON 2X6 WOOD JOISTS. REVISE AS
 REQUIRED. ***NOTE; COORDINATE WITH ITEM #2 (B)(5)
 BELOW. SEC. 107.2.1 CITY AMENDMENTS.
 (4) ROOF SHEATHING SIZE SPECIFIED DOESN'T MATCH ROOF
 SHEATHING SPECIFIED ON THE DIAPHRAGM SCHEDULE ON SAME
 SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 (5) SPECIFY SIZE OF VENTILATION TO COMPLY WITH SEC.
 R806 OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP IN MIND
 THAT NEED CROSS VENTILATION.
 (6) PROVIDE COMPLETE SPECIFICATIONS FOR WOOD PROTECTION
 (FLOOR JOISTS) AS REQUIRED BY SEC. R317.1.
 (7) SPECIFY 7/8" MIN. STUCCO THICKNESS AS REQUIRED BY
 TABLE R702.1(1).
 (8) SPECIFY TWO LAYERS OF APPROVED WATER RESISTANT
 BARRIER AS REQUIRED BY SEC. R703.6.3.
  
 C) SPECIFY DIMENSION "A" ON ROOF ZONES SKETCH SHOWN
 ABOVE THE DIAPHRAGM SCHEDULE. SEE NOTE "A" ON FIGURE
 R301.2(7) AND ROOF SHEATHING NAILING ZONES FIGURE
 R803.2.3.1.
  
 D) ROOF PLAN: SPECIFY MIN. ROOF PITCH OF 1/4 PER FT. AS
 REQUIRED BY SEC. R905.11.1.
  
 3- MASTER BEDROOM EGRESS WAS REDUCED WHEN CLOSING THE
 WINDOW TO ALLOW FOR THE BATHROOM ADDITION. NEED TO
 PROVIDE COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 R310.
  
 4- LOW SLOPE ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 TO MEET THE
 DESIGN PRESSURES OF SEC. R301.2.1.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-08 Cont ID  
Sent By dharvey Date 2013-07-08 Time 12:26 Rev Time 0.00
Received By dharvey Date 2013-07-08 Time 12:15 Sent To  
Notes
2013-07-08 12:26:57BY RL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-08-15 Cont ID  
Sent By jgomez Date 2013-08-15 Time 17:48 Rev Time 0.00
Received By jgomez Date 2013-08-09 Time 08:40 Sent To  
Notes
2013-08-12 08:40:34GAVE TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-02 Cont ID  
Sent By jgomez Date 2013-08-02 Time 18:51 Rev Time 0.00
Received By jgomez Date 2013-07-23 Time 11:58 Sent To  
Notes
2013-07-23 11:58:35TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-09 Cont ID  
Sent By jgomez Date 2013-07-09 Time 16:21 Rev Time 0.00
Received By jgomez Date 2013-06-18 Time 09:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2013-07-09 Cont ID  
Sent By jgomez Date 2013-07-09 Time 11:41 Rev Time 0.00
Received By jgomez Date 2013-07-09 Time 11:41 Sent To  
Notes
2013-07-09 11:42:17NO FEES DUE. MU-2013-12589. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-09 Cont ID  
Sent By avann Date 2013-07-09 Time 13:21 Rev Time 0.00
Received By jgomez Date 2013-07-09 Time 13:21 Sent To  
Notes
2013-06-24 18:47:486/25/13

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By ajones Date 2013-06-27 Time 10:38 Rev Time 0.00
Received By ajones Date 2013-06-27 Time 10:38 Sent To  
Notes
***NONE***