Notes |
2013-06-21 09:57:02 | 1781 PALM BEACH LAKES BOULEVARD - PB MALL BUILDING J-9 | | PERMIT #13060634 | | MASTER #12110064 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED | | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. | | | | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT | | CONNECTION. | | | | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE | | DEPARTMENT CONNECTION. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|
|