Plan Review Details - Permit 13060633
Plan Review Stops For Permit 13060633
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-21 Cont ID  
Sent By wjolin Date 2013-06-21 Time 09:46 Rev Time 0.00
Received By wjolin Date 2013-06-21 Time 09:20 Sent To M
Notes
2013-06-21 09:38:001721 PALM BEACH LAKES BOULEVARD - PB MALL BUILDING J-6
 PERMIT #13060633
 MASTER #12110060
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 SHEET FP-4: TWO SPRINKLERS (LOCATED IN THE SOUTHWEST
 CORNER OF TENANT E415) ARE COVERING AN AREA GREATER
 THAN 130 SQ.FT. (13X11 = 143 SQ.FT.).
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 PROVIDE 4 SIDEWALL SPRINKLERS NEAR THE TOP OF THE SHADE
 CANOPIES.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
2013-06-18 10:42:53SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-25 Cont ID  
Sent By hmoser Date 2013-06-25 Time 14:44 Rev Time 0.00
Received By hmoser Date 2013-06-21 Time 09:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-06-25 Cont ID  
Sent By hmoser Date 2013-06-25 Time 14:43 Rev Time 0.00
Received By hmoser Date 2013-06-25 Time 14:32 Sent To  
Notes
***NONE***