Plan Review Details - Permit 13060623
Plan Review Stops For Permit 13060623
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-05 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 09:24 Rev Time 0.00
Received By jwitmer Date 2013-07-05 Time 08:33 Sent To  
Notes
2013-07-05 09:27:31BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 SHEET A-500 DETAIL # 1, CEILING INSULATION. PLEASE
 UPDATE PLANS TO COMPLY WITH 2010 FBC-B 502.3.5.2
 UNVENTED DROPPED CEILING CAVITIES.
 WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER
 CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER
 BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH
 AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED
 FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND
 ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS
 ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT
 CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER
 THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-05 Cont ID  
Sent By dharvey Date 2013-07-05 Time 14:57 Rev Time 0.00
Received By dharvey Date 2013-07-05 Time 14:44 Sent To  
Notes
2013-07-05 14:58:12BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-22 Cont ID  
Sent By wjolin Date 2013-06-22 Time 17:24 Rev Time 0.00
Received By wjolin Date 2013-06-22 Time 17:04 Sent To  
Notes
2013-06-22 17:24:49313 10TH STREET
 PERMIT #13060623
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS AND DESIGN SHALL CONFORM TO THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET E-1: PLAN INDICATES A CARD READER ON THE EGRESS
 SIDE OF EXIT ACCESS DOOR #12. DOORS SHALL BE ARRANGED
 TO BE OPENED READILY FROM THE EGRESS SIDE WHENEVER THE
 BUILDING IS OCCUPIED. DOORS SHALL NOT REQUIRE THE USE
 OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-12 Cont ID  
Sent By shill Date 2013-07-12 Time 15:54 Rev Time 0.00
Received By shill Date 2013-06-17 Time 11:35 Sent To  
Notes
2013-06-18 11:36:04SENT TO B3 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-12 Cont ID  
Sent By hmoser Date 2013-07-12 Time 14:06 Rev Time 0.00
Received By hmoser Date 2013-07-12 Time 13:26 Sent To  
Notes
2013-07-12 14:06:11PASS PROVISO
 REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-24 Cont ID  
Sent By lwagner Date 2013-06-24 Time 09:56 Rev Time 0.00
Received By lwagner Date 2013-06-24 Time 09:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-07-12 Cont ID  
Sent By aaponte Date 2013-07-12 Time 15:53 Rev Time  
Received By shill Date   Time   Sent To  
Notes
2013-07-12 15:54:09INTERIOR RENOVATION OF EXISTING OFFICE SPACE
 NO ZONING REQUIRED PER AAPONTE
  
2013-06-20 09:28:056/20/13