Plan Review Details - Permit 13060550
Plan Review Stops For Permit 13060550
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-22 Cont ID  
Sent By jwitmer Date 2013-07-22 Time 10:10 Rev Time 0.00
Received By jwitmer Date 2013-07-22 Time 10:09 Sent To  
Notes
2013-07-22 10:10:30SHEET S1-2 UNATTENDED SCALE FOUNDATION ONLY, JW

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-31 Cont ID  
Sent By dharvey Date 2013-07-31 Time 14:19 Rev Time 0.00
Received By dharvey Date 2013-07-30 Time 16:32 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-07-23 Cont ID  
Sent By mgonzale Date 2013-07-23 Time   Rev Time 1.00
Received By mgonzale Date 2013-07-23 Time   Sent To I
Notes
2013-07-23 15:17:46PROVISO
  
 EOR WILL CERTIFY SITE CONSTRUCTION TO CITY OF WPB.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-08-24 Cont ID  
Sent By wjolin Date 2013-08-24 Time 12:01 Rev Time 0.00
Received By wjolin Date 2013-08-20 Time 17:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-07-24 Cont ID  
Sent By wjolin Date 2013-07-24 Time 10:20 Rev Time 0.00
Received By wjolin Date 2013-07-24 Time 10:07 Sent To  
Notes
2013-07-24 10:20:236895 NORTH JOG ROAD - SCALES
 PERMIT #13060550
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE EXISTING ROADWAY BYPASS (FOR THE EXISTING SCALES)
 IS A FIRE DEPARTMENT ACCESS ROAD. INSTALLATION OF A NEW
 UNATTENDED SCALE WILL ENCROACH UPON THE REQUIRED CLEAR
 WIDTH OF 20 FEET NEEDED FOR FIRE DEPARTMENT APPARATUS.
 PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 32 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-27 Cont ID  
Sent By shill Date 2013-08-27 Time 17:51 Rev Time 0.00
Received By shill Date 2013-08-13 Time 09:51 Sent To  
Notes
2013-08-14 09:52:07RESUBMITTAL SENT TO C3 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-31 Cont ID  
Sent By dharvey Date 2013-07-31 Time 14:20 Rev Time 0.00
Received By dharvey Date 2013-06-15 Time 09:24 Sent To  
Notes
2013-07-17 12:04:51C03 - SENT TO PLAN SLOT C03. RB
  
2013-06-15 09:25:13INCOMING SENT TO ZONING BOX . JW

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-17 Cont ID  
Sent By lwagner Date 2013-07-17 Time 13:17 Rev Time 0.00
Received By lwagner Date 2013-07-17 Time 09:34 Sent To  
Notes
2013-07-01 15:43:13 
  

Review Stop Z ZONING
Rev No 2 Status P Date 2013-08-23 Cont ID  
Sent By eschneid Date 2013-08-23 Time 13:12 Rev Time 0.50
Received By eschneid Date 2013-08-23 Time 13:12 Sent To  
Notes
2013-08-23 13:15:03PASSED W/PROVISO:
  
 1) PRIOR TO FINAL INSPECTION (104), INSTALL/PASS
 LANDSCAPE FROM PERMIT 13060870.
  
 2) THE WORK ASSOCIATED WITH THE NEW FIRE DEPARTMENT
 ACCESS DRIVE, TO INCLUDE THE REMOVAL OF ANY TREES,
 REQUIRE SEPARATE PERMITTING.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.
2013-08-16 14:27:018-16-13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-07-15 Cont ID  
Sent By eschneid Date 2013-07-15 Time 15:43 Rev Time 0.50
Received By eschneid Date 2013-06-19 Time 15:15 Sent To P
Notes
2013-07-15 16:21:34FAILED
  
 1) THE NEW GENERATOR AREA, INCLUDING THE ATS ETC., IS
 REQUIRED TO BE SCREENED WITH AN OPAQUE FENCE AND
 LANDSCAPE. THIS IS NOT SHOWN ON THE SITE DEVELOPMENT,
 ELECTRICAL OR LANDSCAPE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-06-19 15:15:58ESCHNEIDER