2013-06-24 15:01:54 | | | 13060522 | | 4855 FRED GLADSTONE DRIVE. | | NURSE CALL SYSTEM | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | INDICATE WIRING METHOD. PROVIDE SPECIFICATIONS AND | | LISTING FOR EQUIPMENT. NEC 110.3, 110.8, UL 1069 | | | | ROBERT LECKY | | ELECTRICAL PLANS REVIEW | | 561-805-6718 | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2013-07-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2013-07-09 |
Time |
05:53 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2013-07-09 |
Time |
05:47 |
Sent To |
|
|
Notes |
2013-07-09 05:53:37 | MORSE GERIATRIC CENTER | | 4847 FRED GLADSTONE DRIVE | | PERMIT # 13060522 | | FURNISH AND INSTALL COMPLETE (LV) NURSE CALL SYSTEM PER | | PLANS | | 2ND REVIEW | | | | 1. THE INSTALLATION OF THIS OR ANY LOW VOLTAGE SYSTEMS | | SHALL NOT INTERFERE WITH ANY FIRE WALLS, SMOKE | | COMPARTMENTS, FIRE OR SMOKE DAMPERS OR ANY OTHER LIFE | | SAFETY FEATURE OF THE BUILDING. | | | | 2. INSTALLATION METHODS SHALL BE APPROVED BY THE | | GOVERNING AUTHORITIES OF THE CITY OF WEST PALM BEACH. | | | | 3. WANDER MANAGEMENT OR NURSE CALL SYSTEMS SHALL NOT | | INTERFERE WITH ANY EXITING OR MEANS OF EGRESS FROM THE | | FACILITY. | | | | | | APPROVED. | | | | | | | | MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF | | WEST PALM BEACH FIRE RESCUE |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2013-06-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2013-06-20 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2013-06-20 |
Time |
07:01 |
Sent To |
|
|
Notes |
2013-06-20 08:30:51 | MORSE GERIATRIC CENTER | | 4847 FRED GLADSTONE DRIVE | | 120 BED SKILLED NURSING REPLACEMENT | | FURNISH AND INSTALL COMPLETE (LV) NURSE CALL SYSTEM PER | | PLANS | | | | 1. PLEASE PROVIDE CUT SHEETS FOR ALL EQUIPMENT PLANNED | | TO BE USED. | | | | 2. PLANS MAKE REFERENCE REGARDING "WANDER MANAGEMENT" | | SYSTEM. PLEASE PROVIDE MORE DETAILS ON THIS SYSTEM AND | | HOW DOES IT FUNCTION. | | | | 3. PLEASE DESCRIBE FURTHER NOTE # 3 WHICH STATES | | "COORDINATE RESIDENT DETECTION SENSORS WITH DOOR LOCK | | HARDWARE, FIRE ALARM DOOR OVERRIDE AND ELEVATOR | | CONTROLS". | | | | 4. VALUE EXCEEDS $ 5000.00 DOLLARS. PLANS ARE NOT | | SIGNED AND SEALED. | | | | 5. PLEASE INDICATE HOW LOW VOLTAGE NURSE CALL SYSTEMS | | WILL NOT INTERFERE WITH ANY FIRE WALLS, SMOKE | | COMPARTMENTS, FIRE DAMPERS, ETC. | | | | DENIED | | | | | | MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF | | WEST PALM BEACH FIRE RESCUE | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-07-13 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-07-13 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-07-02 |
Time |
09:12 |
Sent To |
|
|
Notes |
2013-07-02 09:13:03 | TO FIRE | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-06-24 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-06-24 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-06-15 |
Time |
09:17 |
Sent To |
|
|
Notes |
2013-06-15 09:17:22 | INCOMING SENT TO FIRE BOX . JW |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |