Plan Review Details - Permit 13060522
Plan Review Stops For Permit 13060522
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-13 Cont ID  
Sent By dharvey Date 2013-07-13 Time 09:47 Rev Time 0.00
Received By dharvey Date 2013-07-13 Time 09:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-24 Cont ID  
Sent By dharvey Date 2013-06-24 Time 15:01 Rev Time 0.00
Received By dharvey Date 2013-06-24 Time 14:45 Sent To  
Notes
2013-06-24 15:01:54 
 13060522
 4855 FRED GLADSTONE DRIVE.
 NURSE CALL SYSTEM
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE WIRING METHOD. PROVIDE SPECIFICATIONS AND
 LISTING FOR EQUIPMENT. NEC 110.3, 110.8, UL 1069
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-805-6718
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-07-09 Cont ID  
Sent By mcarsill Date 2013-07-09 Time 05:53 Rev Time 0.00
Received By mcarsill Date 2013-07-09 Time 05:47 Sent To  
Notes
2013-07-09 05:53:37MORSE GERIATRIC CENTER
 4847 FRED GLADSTONE DRIVE
 PERMIT # 13060522
 FURNISH AND INSTALL COMPLETE (LV) NURSE CALL SYSTEM PER
 PLANS
 2ND REVIEW
  
 1. THE INSTALLATION OF THIS OR ANY LOW VOLTAGE SYSTEMS
 SHALL NOT INTERFERE WITH ANY FIRE WALLS, SMOKE
 COMPARTMENTS, FIRE OR SMOKE DAMPERS OR ANY OTHER LIFE
 SAFETY FEATURE OF THE BUILDING.
  
 2. INSTALLATION METHODS SHALL BE APPROVED BY THE
 GOVERNING AUTHORITIES OF THE CITY OF WEST PALM BEACH.
  
 3. WANDER MANAGEMENT OR NURSE CALL SYSTEMS SHALL NOT
 INTERFERE WITH ANY EXITING OR MEANS OF EGRESS FROM THE
 FACILITY.
  
  
 APPROVED.
  
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-20 Cont ID  
Sent By mcarsill Date 2013-06-20 Time 08:30 Rev Time 0.00
Received By mcarsill Date 2013-06-20 Time 07:01 Sent To  
Notes
2013-06-20 08:30:51MORSE GERIATRIC CENTER
 4847 FRED GLADSTONE DRIVE
 120 BED SKILLED NURSING REPLACEMENT
 FURNISH AND INSTALL COMPLETE (LV) NURSE CALL SYSTEM PER
 PLANS
  
 1. PLEASE PROVIDE CUT SHEETS FOR ALL EQUIPMENT PLANNED
 TO BE USED.
  
 2. PLANS MAKE REFERENCE REGARDING "WANDER MANAGEMENT"
 SYSTEM. PLEASE PROVIDE MORE DETAILS ON THIS SYSTEM AND
 HOW DOES IT FUNCTION.
  
 3. PLEASE DESCRIBE FURTHER NOTE # 3 WHICH STATES
 "COORDINATE RESIDENT DETECTION SENSORS WITH DOOR LOCK
 HARDWARE, FIRE ALARM DOOR OVERRIDE AND ELEVATOR
 CONTROLS".
  
 4. VALUE EXCEEDS $ 5000.00 DOLLARS. PLANS ARE NOT
 SIGNED AND SEALED.
  
 5. PLEASE INDICATE HOW LOW VOLTAGE NURSE CALL SYSTEMS
 WILL NOT INTERFERE WITH ANY FIRE WALLS, SMOKE
 COMPARTMENTS, FIRE DAMPERS, ETC.
  
 DENIED
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-13 Cont ID  
Sent By dharvey Date 2013-07-13 Time 09:47 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 09:12 Sent To  
Notes
2013-07-02 09:13:03TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-24 Cont ID  
Sent By dharvey Date 2013-06-24 Time 15:02 Rev Time 0.00
Received By dharvey Date 2013-06-15 Time 09:17 Sent To  
Notes
2013-06-15 09:17:22INCOMING SENT TO FIRE BOX . JW