Plan Review Details - Permit 13060375
Plan Review Stops For Permit 13060375
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By jwitmer Date 2013-07-02 Time 07:52 Rev Time 0.00
Received By jwitmer Date 2013-07-02 Time 07:03 Sent To  
Notes
2013-07-02 07:21:28BUILDING PLAN REVIEW
 PERMIT: 13060375
 ADD: 3501 N MILITARY TRAIL
 CONT: HEDRICK BROTHERS CONSTRUCTION
 TEL: (561)689-8880
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JULY 02/2013
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 REDLINED DRAWINGS:
  
 1) SHEET 5 & 14A OF 18 HANDICAPPED RAMP HANDRAIL END
 SECTIONS SHOW A RAIL NOT COMPLYING WITH 2010 FBC
 505.10.1 AND FIGURE 505.10.1 AND 307.2 PROTRUSION
 LIMITS. 307.2 PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH
 FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM)
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH.
  
 2) SHEET 11 OF 18 THE VIEWING PLATFORM DETAIL DOES NOT
 DOES NOT PROVIDE THE HEIGTH REQUIREMENTS OF THE
 GAURDRAIL 2010 FBC-B 1013.2.
  
 3) SHEET 4 & 13 OF 18 DO NOT PROVIDE THE WIDTH OF THE
 INTERMEDIATE RAMPS AS DESCRIBED IN 2010
 FBC-ACCESSBILITY CODE 405.7.4 CHANGE IN DIRECTION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-14 Cont ID  
Sent By jwitmer Date 2013-06-14 Time 09:18 Rev Time 0.00
Received By jwitmer Date 2013-06-14 Time 07:00 Sent To  
Notes
2013-06-14 08:27:32BUILDING PLAN REVIEW
 PERMIT: 13060375
 ADD: 3501 N MILITARY TRAIL
 CONT: HEDRICK BROTHERS CONSTRUCTION
 TEL: (561)689-8880
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 14/2013
 ACTION: DENIED
  
 1) SHEET 5 & 14A OF 18 HANDICAPPED RAMP HANDRAIL END
 SECTIONS SHOW A RAIL NOT COMPLYING WITH 2010 FBC
 505.10.1 AND FIGURE 505.10.1 AND 307.2 PROTRUSION
 LIMITS. 307.2 PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH
 FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM)
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH.
  
 2) SHEET 11 OF 18 THE VIEWING PLATFORM DETAIL DOES NOT
 DOES NOT PROVIDE THE HEIGTH REQUIREMENTS OF THE
 GAURDRAIL 2010 FBC-B 1013.2.
  
 3) SHEET 4 & 13 OF 18 DO NOT PROVIDE THE WIDTH OF THE
 INTERMEDIATE RAMPS AS DESCRIBED IN 2010
 FBC-ACCESSBILITY CODE 405.7.4 CHANGE IN DIRECTION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-21 Cont ID  
Sent By dharvey Date 2013-06-21 Time 12:06 Rev Time 0.00
Received By dharvey Date 2013-06-21 Time 11:34 Sent To  
Notes
2013-06-21 12:07:30PERMIT ISSUED WITH THE FOLLOWING PROVISO:
  
 SITE LIGHTING EQUIPMENT GROUNDING CONDUCTORS SHALL BE
 THE SAME SIZE AS THE UNGROUNDED CONDUCTORS (FULL SIZE)
 PER THE FAE ENGINEER OF RECORD. NEC 250.94, 250.122
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-06-25 Cont ID  
Sent By Mgonzale Date 2013-06-25 Time   Rev Time 1.00
Received By mgonzale Date 2013-06-25 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-15 Cont ID  
Sent By wjolin Date 2013-06-15 Time 10:26 Rev Time 0.00
Received By wjolin Date 2013-06-15 Time 09:39 Sent To  
Notes
2013-06-15 10:22:273501 NORTH MILITARY TRAIL
 PERMIT #13060375
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SPACES UNDERNEATH A GRANDSTAND SHALL BE KEPT FREE OF
 FLAMMABLE OR COMBUSTIBLE MATERIALS UNLESS PROTECTED BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
  
 THE OWNER SHALL PROVIDE FOR NOT LESS THAN ANNUAL
 INSPECTION AND REQUIRED MAINTENANCE OF EACH OUTDOOR
 GRANDSTAND TO ENSURE SAFE CONDITIONS.
  
 THE OWNER IS RESPONSIBLE FOR HAVING AN INSPECTION OF
 THE OUTDOOR GRANDSTANDS CONDUCTED ANNUALLY. THESE
 INSPECTIONS SHOULD ENSURE THAT OUTDOOR GRANDSTANDS ARE
 STRUCTURALLY SOUND.
  
 AT LEAST BIENNIALLY (2-YEARS), THE INSPECTION SHALL BE
 PERFORMED BY A PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT, OR INDIVIDUAL CERTIFIED BY THE MANUFACTURER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-02 Cont ID  
Sent By jwitmer Date 2013-07-02 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2013-06-27 Time 16:37 Sent To  
Notes
2013-07-01 16:38:07SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-25 Cont ID  
Sent By shill Date 2013-06-25 Time 13:56 Rev Time 0.00
Received By shill Date 2013-06-11 Time 16:30 Sent To  
Notes
2013-06-12 16:36:07*EXPEDITED*
 C--22

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-18 Cont ID  
Sent By Ahansen Date 2013-06-18 Time   Rev Time  
Received By   Date 2013-06-17 Time   Sent To  
Notes
2013-06-17 13:27:196/17/13- ALEX