Plan Review Details - Permit 13060366
Plan Review Stops For Permit 13060366
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-20 Cont ID  
Sent By dharvey Date 2013-06-20 Time 13:25 Rev Time 0.00
Received By dharvey Date 2013-06-20 Time 13:22 Sent To FIRE
Notes
2013-06-20 13:26:28BY RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-19 Cont ID  
Sent By dharvey Date 2013-06-19 Time 10:48 Rev Time 0.00
Received By dharvey Date 2013-06-19 Time 10:40 Sent To  
Notes
2013-06-19 10:48:3813060366
 221 CLEMATIS STREET #2A
 ACCESS CONTROL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE THE WIRING METHOD, CABLE TYPE, WIRE SIZE, FIRE
 RATING AND CONDUIT SCHEDULE. PROVIDE A LISTING ON THE
 EQUIPMENT. NEC 110.3, 300.21, 725.136
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-26 Cont ID  
Sent By lphilmor Date 2013-06-26 Time 11:05 Rev Time 0.00
Received By lphilmor Date 2013-06-21 Time 13:24 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-14 Cont ID  
Sent By lphilmor Date 2013-06-14 Time 14:05 Rev Time 0.00
Received By lphilmor Date 2013-06-14 Time 13:37 Sent To E
Notes
2013-06-14 14:05:33221 CLEMATIS, SUITE 2A
 PERMIT # 13060366
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. PLEASE INDICATE IF DOORS ARE ELECTRIC STRIKE OR
 MAGNETIC LOCKS.
 2. INDICATE THE METHOD FOR RELEASING THE CONTROL DEVICE
 - PANIC HARDWARE, ETC.
 3. PLEASE VERIFY IF READER #2 IS LOCATED AT THE STEEL
 FIRE DOOR.
 4. PROVIDE A SIGNED COPY OF WORK CONTRACT TO INCLUDE
 LABOR AND MATERIALS.
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-06-28 Cont ID  
Sent By dharvey Date 2013-06-28 Time 09:53 Rev Time 0.00
Received By dharvey Date 2013-06-24 Time 12:50 Sent To  
Notes
2013-06-24 12:50:54(SUBMITTAL BROUGHT IN MID REVIEW) TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-28 Cont ID  
Sent By dharvey Date 2013-06-28 Time 09:53 Rev Time 0.00
Received By dharvey Date 2013-06-19 Time 08:39 Sent To  
Notes
2013-06-20 08:40:04SENT TO ELECTRIC UNDER $5K BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-19 Cont ID  
Sent By dharvey Date 2013-06-19 Time 10:48 Rev Time 0.00
Received By dharvey Date 2013-06-11 Time 13:15 Sent To  
Notes
2013-06-12 13:17:37SENT TO FIRE SHELF FOR REVIEW. JG.