Plan Review Details - Permit 13060321
Plan Review Stops For Permit 13060321
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-02 Cont ID  
Sent By rmcdouga Date 2013-08-02 Time 16:13 Rev Time 0.00
Received By rmcdouga Date 2013-08-02 Time 14:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-27 Cont ID  
Sent By rmcdouga Date 2013-06-27 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2013-06-27 Time 10:11 Sent To  
Notes
2013-06-27 10:21:052010 FBC
  
 1) SUBMIT TWO COPIES OF UTILITY EASEMENT RELEASE FORMS.
  
 2) SPECIFY HOW THE NEW CHILLER WILL BE ANCHORED TO THE
 SLAB TO RESISTS WINDLOADS. FBC 1609.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-10 Cont ID  
Sent By dharvey Date 2013-07-10 Time 10:13 Rev Time 0.00
Received By dharvey Date 2013-07-10 Time 10:00 Sent To  
Notes
2013-07-10 10:13:28BY RL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-02 Cont ID  
Sent By rmcdouga Date 2013-08-02 Time 16:13 Rev Time 0.00
Received By rmcdouga Date 2013-07-26 Time 15:10 Sent To  
Notes
2013-07-29 15:10:29SENT TO C21 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-23 Cont ID  
Sent By shill Date 2013-07-23 Time 13:36 Rev Time 0.00
Received By shill Date 2013-06-10 Time 10:01 Sent To  
Notes
2013-06-27 10:02:36C21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-08-02 Cont ID  
Sent By hmoser Date 2013-08-02 Time 14:33 Rev Time 0.00
Received By hmoser Date 2013-08-02 Time 14:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-06-27 Cont ID  
Sent By hmoser Date 2013-06-27 Time 13:13 Rev Time 0.00
Received By hmoser Date 2013-06-27 Time 13:07 Sent To  
Notes
2013-06-27 13:13:01PLANS DENIED PROVIDE A DETAIL ON THE PLANS FROM
 THE ENGINEER HOW THE PIPE STANDS ARE GOING TO BE TIED
 TO THE WALL.
 PROVIDE A DETAIL ON HOW THE CHILLER IS TO BE TIED DOWN
 TO THE SLAB.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-16 Cont ID  
Sent By avann Date 2013-07-16 Time 12:03 Rev Time 0.00
Received By ajones Date 2013-07-10 Time 16:00 Sent To  
Notes
***NONE***