Plan Review Details - Permit 13060246
Plan Review Stops For Permit 13060246
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-17 Cont ID  
Sent By jgomez Date 2013-06-17 Time 09:17 Rev Time 0.00
Received By jgomez Date 2013-06-17 Time 09:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-07 Cont ID  
Sent By rmcdouga Date 2013-06-07 Time 12:55 Rev Time 0.00
Received By rmcdouga Date 2013-06-07 Time 12:55 Sent To  
Notes
2013-06-07 13:12:542010 FBC
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED (NOA NO.
 08--0410.09) REQUIRES RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING AT THE CORNER AND PERIMETER AREAS TO BE
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, ARCHITECT OR ROOF CONSULTANT.
 SEE LIMITATION NUMBER 7 ON PAGE 38 OF THE NOA. DCA RULE
 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-17 Cont ID  
Sent By jgomez Date 2013-06-17 Time 09:15 Rev Time 0.00
Received By jgomez Date 2013-06-15 Time 09:59 Sent To  
Notes
2013-06-15 09:59:41INCOMING SENT TO ROBERT MCGOUGALS' DESK BOX . JW