Plan Review Details - Permit 13060068
Plan Review Stops For Permit 13060068
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-26 Cont ID  
Sent By jwitmer Date 2013-07-26 Time 12:00 Rev Time 0.00
Received By jwitmer Date 2013-07-26 Time 11:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-05 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 11:54 Rev Time 0.00
Received By jwitmer Date 2013-07-05 Time 10:05 Sent To  
Notes
2013-07-05 11:54:49BUILDING PLAN REVIEW
 PERMIT: 13060068
 ADD: 1475 CENTREPARK BLVD # 140
 CONT: CHANDLIER CONSTRUCTION
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 05/2013
 ACTION: DENIED
  
 NOTE: WHERE THERE ARE DIFFERENCES BETWEEN TWO CODES,
 THE MOST STRIGENT SHALL APPLY.
  
 1) SHEET A-2 THE BREAK ROOM IS APPROXIMATELY 835 SQ FT,
 SINCE THIS AREA IS OVER THE 750 SQ FT EXCEPTION 3 OF
 303.1 IT DOES CONSTITUTE AN A2 OCCUPANCY HAVING TO MEET
 THE FOLLOWING:
 1A) 2010 FBC-B TABLE 1015.1 EXCEEDS 49 OCCUPANTS WILL
 NEED TWO MEANS OF EGRESS
 1B) 2010 FBC-B 1015.2.1 EXC # 2 THE EXIT DOORS NEED TO
 BE A MINIMUM OF 1/3RD THE LONGEST DIAGONAL DISTANCE
 APART.
 1C) 2010 FBC-B 1014.3 EXC # 1 100 FT COMMON PATH OF
 TRAVEL IS EXCEEDED, BOTH DOORS FROM THE BREAK ROOM LEAD
 TO THE SAME COMMON PATH OF TRAVEL UNTIL YOU HAVE A
 CHOICE OF TRAVEL AT THE FRONT ENTRY.
  
 2) THE CONFERENCE ROOM BY ITSELF BECAUSE IT IS UNDER
 750 SQ FT WOULD BE CONSIDERED BUSINESS OCCUPANCY PLEASE
 PROVIDE DOCUMENTATION THAT THE COMBINED ASSEMBLY USAGE
 AREAS FOR THE WHOLE FLOOR DOES NOT EXCEED 10% OF THE
 FLOOR AREA AREA LIMITATION 508.2.1 THEN UNDER THE 2010
 FBC-B THE CONFERENCE ROOM WOULD BE CONSIDERED BUSINESS
 OCCUPANCY.
  
 SEE BOAF INFORMAL INTERPRETATION 6506
 BOAF
 INFORMAL INTERPRETATION
 REPORT NUMBER 6506
  
 DATE: THU JUN 3 2010
 REPORT: 6506
 CODE: BUILDING CODE YEAR: 2007
 SECTION: 508.3.1
 QUESTION:
 IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING
 SECTION 508.3.1, EXCEPTION 1, TO NOT REQUIRE FIRE
 SEPARATION BETWEEN THE
 PRIMARY OCCUPANCY AND MULTIPLE ACCESSORY OCCUPANCIES,
 WHEN EACH ACCESSORY OCCUPANCY IS LESS THAN 750 SQ. FEET
 EACH OR
 ONLY WHEN THE TOTAL OF ALL ACCESSORY OCCUPANCIES IS
 LESS THAN 750 SQ. FEET IN AREA?
 COMMENT:
 AN EXAMPLE WOULD BE A BUSINESS OCCUPANCY WITH ONE
 ACCESSORY AREA OF 700SF FOR GATHERINGS AND MEETINGS AND
 A SECOND
 ACCESSORY AREA OF 650SF FOR FITNESS AND WORKOUT. IS THE
 EXCEPTION LIMITATION OF 750 S.F. MAX APPLIED TO EACH
 ACCESSORY AREA, IN
 WHICH CASE THIS BUILDING WOULD COMPLY, OR TO THE
 COMBINED TOTAL OF THE TWO ACCESSORY AREAS, IN WHICH
 CASE IT WOULD NOT?
 ANSWER:
 NO. CONSIDERING BOTH SPACES TO BE ASSEMBLY USES LOCATED
 ON THE SAME FLOOR, THE EXCEPTION TO FLORIDA BUILDING
 CODE - BUILDING
 SECTION 508.3.1 WOULD NOT REQUIRE SEPARATION OF EITHER
 SPACE. HOWEVER, THE SECTION TO WHICH THE EXCEPTION
 RELATES WOULD LIMIT THE AGGREGATE ACCESSORY OCCUPANCIES
 TO 10% OF THE AREA OF THE FLOOR ON WHICH THEY ARE
 LOCATED. IF THE AREA OF TWO COMBINED ASSEMBLY USES
 EXCEEDED 10%, THEN AT LEAST ONE OF THE ASSEMBLY USES
 WOULD REQUIRE FIRE RESISTANT RATED SEPARATION OF 2
 HOURS IN A NON-SPRINKLED BUILDING AND 1 HOUR IN A
 BUILDING SPRINKLED THROUGHOUT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By dharvey Date 2013-06-27 Time 12:00 Rev Time 0.00
Received By dharvey Date 2013-06-27 Time 11:30 Sent To  
Notes
2013-06-27 12:01:19BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-07-30 Cont ID  
Sent By wjolin Date 2013-07-30 Time 12:44 Rev Time 0.00
Received By wjolin Date 2013-07-30 Time 11:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-15 Cont ID  
Sent By wjolin Date 2013-06-15 Time 11:21 Rev Time 0.00
Received By wjolin Date 2013-06-15 Time 10:39 Sent To  
Notes
2013-06-15 11:21:501475 CENTERPARK BOULEVARD - SUITE #140
 PERMIT #13060068
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2009 EDITION WITH FLORIDA AMENDMENTS.)
  
 BREAK ROOM #110 APPEARS TO BE 775 SQ.FT. WHICH WOULD
 RESULT IN AN OCCUPANT LOAD OF 52 PERSONS (775 SQ.FT. /
 15 SQ.FT. PER PERSON) WHICH WOULD MAKE THIS AN ASSEMBLY
 OCCUPANCY.
  
 BREAK ROOM #110: PER SECTION 7.2.1.4.2, DOORS SERVING
 AN OCCUPANT LOAD OF 50 OR MORE PERSONS SHALL SWING IN
 THE DIRECTION OF EGRESS.
  
 BREAK ROOM #110: PER SECTION 12.2.5.1.2, THE COMMON
 PATH OF TRAVEL FOR ASSEMBLY OCCUPANCIES WITH AN
 OCCUPANT LOAD OF MORE THAN 50 PERSONS IS LIMITED TO 20
 FEET.
  
 BREAK ROOM #110: WHILE THE TWO EXIT ACCESS DOORS ARE
 LOCATED MORE THAN 1/3 THE DISTANCE OF THE DIAGONAL OF
 THE ROOM, BOTH DOORS LEAD TO THE SAME CORRIDOR WHEREBY
 ONE FIRE EVENT COULD SACRIFICE BOTH EXIT ACCESS POINTS.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS (50 PERSONS PER THE FLORIDA BUILDING
 CODE), PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 ASSEMBLY USE SPACES BREAK ROOM #110 (775 SQ.FT.) AND
 CONFERENCE ROOM #101 (286 SQ.FT.) HAVE A COMBINED AREA
 (1,061 SQ.FT.) THAT EXCEEDS 10% OF THE TENANT SPACE SO
 THESE AREAS CANNOT BE CONSIDERED ACCESSORY TO THE
 BUSINESS OCCUPANCY. FOR NON-SEPARATED MIXED USE
 OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY
 REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE
 BUILDING. PER SECTION NFPA 101 SECTION 6.1.14.1.2,
 WHERE EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED NON-SEPARATED OCCUPANCY.
  
 UPDATE THE OCCUPANT LOAD AND CALCULATIONS TO SHOW 15
 SQ.FT. PER PERSON FOR THE ASSEMBLY USE AREAS.
  
 SHEET E2.1: THE SOUTH EXIT DOORS IS NOT MARKED WITH AN
 EXIT SIGN.
  
 SHEET FA2.1: ANOTHER FIRE ALARM NOTIFICATION APPLIANCE
 APPEARS TO BE NEEDED AT THE SOUTHEAST AREA OF OPEN
 OFFICE #105.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-30 Cont ID  
Sent By wjolin Date 2013-07-30 Time 12:44 Rev Time 0.00
Received By wjolin Date 2013-07-19 Time 14:58 Sent To  
Notes
2013-07-19 14:59:16INCOMING SENT TO B19 . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-12 Cont ID  
Sent By hmoser Date 2013-07-12 Time 09:09 Rev Time 0.00
Received By hmoser Date 2013-06-04 Time 10:08 Sent To  
Notes
2013-06-05 10:09:35INCOMING SENT TO B19 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-12 Cont ID  
Sent By hmoser Date 2013-07-12 Time 09:09 Rev Time 0.00
Received By hmoser Date 2013-07-10 Time 15:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-07 Cont ID  
Sent By lwagner Date 2013-06-07 Time 08:19 Rev Time 0.00
Received By lwagner Date 2013-06-06 Time 15:37 Sent To  
Notes
***NONE***