Plan Review Details - Permit 13060053
Plan Review Stops For Permit 13060053
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-05 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2013-07-05 Time 09:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By jwitmer Date 2013-06-12 Time 16:31 Rev Time 0.00
Received By jwitmer Date 2013-06-12 Time 16:31 Sent To  
Notes
2013-06-12 16:50:25BUILDING PLAN REVIEW
 PERMIT: 13060053
 ADD: 5200 N FLAGLER DR
 CONT: DURHAM BROTHERS INC
 TEL: (561)315-1835
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 12/2013
 ACTION: DENIED
  
 1) SHEET A1 THE CONVERSION FROM A BATHROOM TO RESTROOM
 DOES NOT MEET THE 2010 FL ACCESSIBILITY CODE.
 PLEASE REVIEW 2010 FL ACCESSIBILITY CODE SECTION
 604.3.1, FIGURE 604.3.1 & FIGURE 604.8.1.6.
  
 1A) 2010 FL ACC. CODE 202.4 ALTERATIONS AFFECTING
 PRIMARY FUNCTION AREAS.
 AN AREA OF A BUILDING OR FACILITY CONTAINING A MAJOR
 ACTIVITY FOR WHICH THE BUILDING OR FACILITY IS INTENDED
 IS A PRIMARY FUNCTION AREA. DEPARTMENT OF JUSTICE ADA
 REGULATIONS STATE, ?ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 1B) 2010 FBC-ACC CODE 603.2.3 DOOR SWING SEE EXCEPTION
 # 2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By dharvey Date 2013-06-27 Time 12:08 Rev Time 0.00
Received By dharvey Date 2013-06-27 Time 12:02 Sent To  
Notes
2013-06-27 12:08:28BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-07-17 Cont ID  
Sent By wjolin Date 2013-07-17 Time 15:10 Rev Time 0.00
Received By wjolin Date 2013-07-17 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-07-10 Cont ID  
Sent By wjolin Date 2013-07-10 Time 16:18 Rev Time 0.00
Received By wjolin Date 2013-07-10 Time 16:00 Sent To M
Notes
2013-07-10 16:18:245200 NORTH FLAGLER DRIVE
 PERMIT #13060053
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVIEW #2 COMMENTS:
 THE ARCHITECTURAL RESPONSE LETTER INDICATES THE BURNER
 WILL BE REMOVED FROM THE PROJECT; HOWEVER, THE PLANS
 STILL SHOW THE 4-BURNER RANGE.
  
 A COMMERCIAL OR DOMESTIC OVEN WILL REQUIRE A TYPE II
 MECHANICAL HOOD UNLESS THE WARMING APPLIANCE IS LISTED
 FOR USE WITHOUT A HOOD.
  
 THE PLANS INDICATE A DECREASE IN OCCUPANT LOAD FROM 190
 PERSONS TO 64 PERSONS. PROVIDE A SEATING OR FURNITURE
 PLAN JUSTIFYING THE DECREASE IN OCCUPANT LOAD.
  
 THE REVIEW COMMENTS FROM REVIEW #1 HAVE NOT BEEN
 ADEQUATELY ADDRESSED.
  
  
 REVIEW #1 COMMENTS:
 PLANS SHOW A 4-BURNER RANGE IN THE KITCHEN AREA.
 COOKING OPERATIONS THAT MAY RESULT IN THE PRODUCTION OF
 SMOKE OR GREASE-LADEN VAPORS SHALL BE PROTECTED WITH A
 CLASS I MECHANICAL EXHAUST HOOD EQUIPPED WITH AN
 AUTOMATIC WET-CHEMICAL FIRE SUPPRESSION SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF
 HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (ASSEMBLY) OF THE SPACE, SHALL BE SEPARATED FROM
 NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR
 BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
  
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE
 MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED
 DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN
 STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-05 Cont ID  
Sent By wjolin Date 2013-06-05 Time 10:57 Rev Time 0.00
Received By wjolin Date 2013-06-05 Time 10:45 Sent To  
Notes
2013-06-05 10:56:585200 NORTH FLAGLER DRIVE
 PERMIT #13060053
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS SHOW A 4-BURNER RANGE IN THE KITCHEN AREA.
 COOKING OPERATIONS THAT MAY RESULT IN THE PRODUCTION OF
 SMOKE OR GREASE-LADEN VAPORS SHALL BE PROTECTED WITH A
 CLASS I MECHANICAL EXHAUST HOOD EQUIPPED WITH AN
 AUTOMATIC WET-CHEMICAL FIRE SUPPRESSION SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF
 HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (ASSEMBLY) OF THE SPACE, SHALL BE SEPARATED FROM
 NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR
 BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
  
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE
 MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED
 DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN
 STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-17 Cont ID  
Sent By wjolin Date 2013-07-17 Time 15:10 Rev Time 0.00
Received By wjolin Date 2013-07-12 Time 08:48 Sent To  
Notes
2013-07-15 08:48:35SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-08 Cont ID  
Sent By shill Date 2013-07-08 Time 11:37 Rev Time 0.00
Received By shill Date 2013-06-04 Time 09:04 Sent To  
Notes
2013-06-05 09:26:26INCOMING SENT TO B15 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2013-07-13 Cont ID  
Sent By hmoser Date 2013-07-13 Time 12:36 Rev Time 0.00
Received By hmoser Date 2013-07-13 Time 12:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-07-08 Cont ID  
Sent By shill Date 2013-07-08 Time 11:37 Rev Time 0.00
Received By shill Date 2013-07-08 Time 11:37 Sent To  
Notes
2013-07-08 11:37:30SEE ISSUED PERMIT 13060836 (SAME SCOPE AS SHOWN IN THIS
 PLAN)
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-07-10 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2013-07-05 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By jwitmer Date 2013-06-12 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2013-06-07 Time 08:21 Sent To  
Notes
2013-06-12 16:56:20PLUMBING PLAN REVIEW
 PERMIT: 13060053
 ADD: 5200 N FLAGLER DR
 CONT: DURHAM BROTHERS INC
 TEL: (561)315-1835
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 12/2013
 ACTION: DENIED
  
 1) 2010 FBC-P THE PLANS INDICATE THAT THIS SPACE IS
 DESIGNED TO HOLD 190 OCCUPANTS, PLEASE SEE TABLE
 403.1(1) A3 ASSEMBLY REQUIRING 2 WATER CLOSETS FOR EACH
 SEX, A DRINKING FOUNTAIN AND SERVICE SINK.
  
 2) PLEASE REVIEW 2010 FL ACCESSIBILITY CODE 602.4 &
 602.7 FOR A HIGH- LOW DRINKING FOUNTAIN.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-06-10 Cont ID  
Sent By ajones Date 2013-06-10 Time 15:28 Rev Time 0.00
Received By ajones Date 2013-06-10 Time 15:28 Sent To  
Notes
***NONE***