Plan Review Details - Permit 13051101
Plan Review Stops For Permit 13051101
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2013-06-24 Cont ID  
Sent By shill Date 2013-06-24 Time 16:58 Rev Time 0.00
Received By shill Date 2013-06-24 Time 16:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-06-21 Cont ID  
Sent By shill Date 2013-06-21 Time 16:37 Rev Time 0.00
Received By shill Date 2013-06-21 Time 16:37 Sent To  
Notes
2013-06-21 16:38:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE INSTALLATION PROPOSED IS FOR 160MPH, EXPOSURE B.
 THIS PARCEL IS LOCATED IN THE 170MPH, EXPOSURE D WIND
 ZONE (SEE 2ND PLAN REVIEW).
  
 THIS ITEM WILL BE REDLINED UPON REQUEST AND ISSUED.
 ALTERNATIVELY, CONTRACTOR CAN OBTAIN ENGINEERING.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-06-14 Cont ID  
Sent By shill Date 2013-06-14 Time 16:24 Rev Time 0.00
Received By shill Date 2013-06-14 Time 16:24 Sent To  
Notes
2013-06-14 16:25:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. CONTRACTOR HAS WRITTEN "#9" ON THE COVER OF THE NOA.
  
 THE ENGINEERING PROVIDED BY CERTAINTEED IS FOR ASSEMBLY
 E2 IN THE NOA WHICH IS ON PAGE 8.
  
 IF AN ASSEMBLY ON PAGE 9 IS PROPOSED, INDICATE WHICH OF
 THE TWO ASSEMBLIES IS TO BE INSTALLED AND PROVIDE
 ENGINEERING FOR ENHANCED FASTENING, SEE GENERAL
 LIMITATION #7 ON THE LAST PAGE OF THE NOA.
  
 IF CONTRACTOR ELECTS TO USE ASSEMBLY E2 WITH THE
 ENGINEERING PROVIDED BY CERTAINTEED, TWO SETS REQUIRED.
 CONTRACTOR MAY PROVIDE ONLY THE SHEET WITH INFORMATION
 WHICH PERTAINS TO THIS JOB.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-06-07 Cont ID  
Sent By shill Date 2013-06-07 Time 16:43 Rev Time 0.00
Received By shill Date 2013-06-07 Time 16:43 Sent To  
Notes
2013-06-07 16:46:12****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. THE ASSEMBLY SELECTED, W15 ON PAGE 6, DOES NOT MEET
 DESIGN PRESSURE REQUREMENTS FOR THIS ZONE 3 FOR THIS
 JOB. ZONE 3 EXPOSURE D REQUIRES -116.2. MINIMUM FBC R
 TABLE 301.2(2) AND (3).
  
 THE ASSEMBLY SELECTED HAS A LIMITATION OF -90 PSF.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-01 Cont ID  
Sent By shill Date 2013-06-01 Time 14:22 Rev Time 0.00
Received By shill Date 2013-06-01 Time 14:22 Sent To  
Notes
2013-06-01 14:24:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE ASSEMBLY SELECTED HAS A DESIGN PRESSURE
 LIMITATION OF -67.5. AS MEAN ROOF HEIGHT WAS NOT
 PROVIDED, IT CANNOT BE DETERMINED WHETHER OR NOT THIS
 COMPLIES FOR ZONE 2. HOWEVER, THIS DOES NOT COMPLY FOR
 ZONE 3.
  
 SEE GENERAL LIMITATION #7, RAS 117 CALCULATIONS TO BE
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT, FBC R 301.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-21 Cont ID  
Sent By shill Date 2013-06-21 Time 16:39 Rev Time 0.00
Received By shill Date 2013-06-18 Time 14:47 Sent To  
Notes
2013-06-20 14:50:03GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-14 Cont ID  
Sent By shill Date 2013-06-14 Time 16:25 Rev Time 0.00
Received By shill Date 2013-06-13 Time 09:30 Sent To  
Notes
2013-06-13 09:30:24SENT TO SAMANTHA'S DESK FOR REVIEW. JG.