Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-07 Cont ID  
Sent By wjolin Date 2013-06-07 Time 09:35 Rev Time 0.00
Received By wjolin Date 2013-06-07 Time 09:23 Sent To M
Notes
2013-06-07 09:30:391755 PALM BEACH LAKES BOULEVARD - PB MALL BUILDING J-4
 PERMIT #13050877
 MASTER #12110060
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 SHEET FP-1 "FIRE PROTECTION NOTE #5": RETAIL SHOULD BE
 DESIGNED TO ORDINARY HAZARD GROUP 2 @ 0.20 GPM/SQ.FT.
 DENSITY TO THE MATCH THE HYDRAULIC CALCULATIONS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-11 Cont ID  
Sent By hmoser Date 2013-06-11 Time 08:55 Rev Time 0.00
Received By hmoser Date 2013-05-24 Time 11:34 Sent To  
Notes
2013-05-25 11:34:26IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-06-11 Cont ID  
Sent By hmoser Date 2013-06-11 Time 08:55 Rev Time 0.00
Received By hmoser Date 2013-06-11 Time 08:46 Sent To  
Notes
***NONE***