Plan Review Details - Permit 13050829
Plan Review Stops For Permit 13050829
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-06-13 Cont ID  
Sent By jwitmer Date 2013-06-13 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2013-06-13 Time 13:00 Sent To  
Notes
2013-06-13 13:34:06BUILDING PROVISO:
 PROVIDE CODE COMPLIANCE FOR 2010 FBC-B 1008.1.9.8
 ELECTROMAGNETICALLY LOCKED EGRESS DOORS.
 DOORS TO TENANT SPACES IN GROUP B SHALL BE PERMITTED TO
 BE ELECTROMAGNETICALLY LOCKED IF EQUIPPED WITH LISTED
 HARDWARE THAT
 INCORPORATES A BUILT-IN SWITCH AND MEET THE
 REQUIREMENTS BELOW:
  
 1. THE LISTED HARDWARE THAT IS AFFIXED TO THE DOOR LEAF
 HAS AN OBVIOUS METHOD OF OPERATION THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
  
 2. THE LISTED HARDWARE IS CAPABLE OF BEING OPERATED
 WITH ONE HAND.
  
 3. OPERATION OF THE LISTED HARDWARE RELEASES TO THE
 ELECTROMAGNETIC LOCK AND UNLOCKS THE DOOR IMMEDIATELY.
  
 4. LOSS OF POWER TO THE LISTED HARDWARE AUTOMATICALLY
 UNLOCKS THE DOOR.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-28 Cont ID  
Sent By dharvey Date 2013-06-28 Time 07:14 Rev Time 0.00
Received By dharvey Date 2013-06-27 Time 14:59 Sent To  
Notes
2013-06-28 07:14:06PLANS NOTED FOR CORRECTION OF APPLICABLE CODES TO BE
 APPLIED. DISCUSSED MOUNTING REQUIREMENTS OF
 TRANSFORMER, BONDING OF COLD WATER AND OTHER ISSUES
 WITH AMY (ENGINEER) FOR ADDITIONAL ITEMS THAT MAY NEED
 TO CORRECTED OR MODIFIED DEPENDING ON FIELD CONDITIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-13 Cont ID  
Sent By lphilmor Date 2013-06-13 Time 14:51 Rev Time 0.00
Received By lphilmor Date 2013-06-13 Time 11:06 Sent To  
Notes
2013-06-13 13:09:30525 OKEECHOBEE BLVD, SUITE 860
 PERMIT # 13050829
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 COVER SHEET - UPDATE THE CODE LIST TO REFERENCE THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS
  
 COVER SHEET - "FIRE PROTECTION SYSTEMS SHALL REMAIN
 ACTIVE DURING DEMOLITION AND RENOVATION ACTIVITIES. IN
 THE EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected]) OR
 IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY."
  
 SHEET A-1.0 - THE TENANT SPACE IS FUNCTIONING AS A
 MULTIUSE OCCUPANCY - BUSINESS AND ASSEMBLY. FOR
 NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST STRINGENT
 FIRE AND LIFE SAFETY REQUIREMENTS OF EACH OCCUPANCY
 SHALL APPLY TO THE BUILDING. PER FBC SECTION 508.2
 AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE
 THAN TEN PERCENT IN WHICH THEY ARE LOCATED.
  
 PER SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN
 OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE
 OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY.
  
 SHEET A -1.0 - FOR DOOR #820 OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE.
  
 SHEET E -1.0 PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED
 EGRESS DOORS ARE PERMITTED PROVIDED THAT ALL SEVEN OF
 THE FOLLOWING CRITERIA ARE MET:
 1.A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2.LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3.THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4.THE MANUAL RELEASE DEVICE SHALL BE READILY ACCESSIBLE
 AND CLEARLY IDENTIFIED BY A SIGN THAT READS PUSH TO
 EXIT.
 5.WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL RESULT
 IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6.ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7.ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER SYSTEM
 OR AUTOMATIC DETECTION SYSTEM SHALL AUTOMATICALLY
 UNLOCK THE DOORS IN THE DIRECTION OF EGRESS, AND THE
 DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM
 HAS BEEN MANUALLY RESET.
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-06-28 Time   Rev Time 0.00
Received By rregueir Date 2013-05-23 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By rregueir Date 2013-06-27 Time 11:11 Rev Time 0.00
Received By rregueir Date 2013-06-27 Time 11:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-10 Cont ID  
Sent By lwagner Date 2013-07-10 Time 10:27 Rev Time 0.00
Received By lwagner Date 2013-07-10 Time 10:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-07-08 Cont ID  
Sent By rregueir Date 2013-07-08 Time 11:24 Rev Time 0.00
Received By rregueir Date 2013-07-08 Time 11:24 Sent To  
Notes
***NONE***