Plan Review Details - Permit 13050779
Plan Review Stops For Permit 13050779
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-31 Cont ID  
Sent By jwitmer Date 2013-05-31 Time 16:45 Rev Time 0.00
Received By jwitmer Date 2013-05-31 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-19 Cont ID  
Sent By dharvey Date 2013-06-19 Time 15:31 Rev Time 0.00
Received By dharvey Date 2013-06-19 Time 15:31 Sent To  
Notes
2013-06-19 15:32:26PERMIT ISSUED WITH THE FOLLOWING PROVISO:
  
 1. COMMERCIAL EQUIPMENT LIKELY TO BE SERVICE WHILE
 ENERGIZED MUST HAVE SAFETY WARNING LABEL TO PROTECT
 FROM ARC FLASH HAZARD PER NEC 110.16
 2. CONFERENCE ROOM FLOOR BOX CONDUCTORS MUST BE RATED
 FOR WET LOCATION PER NEC 300.5B
 3. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS CU'S TO
 HAVE MOCP OF 30/2. PANEL A SHOWS 50/2 AND PANEL B SHOWS
 4-/2. PEASE REVISE
 4. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS AHU#2 TO
 HAVE MOCP OF 40/2. PANEL B SHOWS 50/2. PLEASE REVISE.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-05 Cont ID  
Sent By dharvey Date 2013-06-05 Time 10:18 Rev Time 0.00
Received By dharvey Date 2013-06-05 Time 10:18 Sent To  
Notes
2013-06-05 10:22:556-5-13
 FIRST REVIEW
 1. COMMERCIAL EQUIPMENT LIKELY TO BE SERVICE WHILE
 ENERGIZED MUST HAVE SAFETY WARNING LABEL TO PROTECT
 FROM ARC FLASH HAZARD PER NES 110.16
 2. CONFERENCE ROOM FLOOR BOX CONDUCTORS MUST BE RATED
 FOR WETLOCATION PER NEC 300.5B
 3. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS CU'S TO
 HAVE MOCP OF 30/2. PANEL A SHOWS 50/2 AND PANEL B SHOWS
 4-/2. PLEASE REVISE
 4. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS AHU#2 TO
 HAVE MOCP OF 40/2. PANEL B SHOWS 50/2. PLEASE REVISE.
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-08 Cont ID  
Sent By wjolin Date 2013-06-08 Time 10:23 Rev Time 0.00
Received By wjolin Date 2013-06-08 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-14 Cont ID  
Sent By hmoser Date 2013-06-14 Time 11:25 Rev Time 0.00
Received By hmoser Date 2013-05-22 Time 12:09 Sent To  
Notes
2013-05-24 12:09:57B--10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-06-14 Cont ID  
Sent By hmoser Date 2013-06-14 Time 11:25 Rev Time 0.00
Received By hmoser Date 2013-06-14 Time 11:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-30 Cont ID  
Sent By lwagner Date 2013-05-30 Time 13:50 Rev Time 0.00
Received By lwagner Date 2013-05-30 Time 13:05 Sent To  
Notes
***NONE***