Plan Review Details - Permit 13050770
Plan Review Stops For Permit 13050770
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2013-05-29 Cont ID  
Sent By shill Date 2013-05-29 Time 11:11 Rev Time 0.00
Received By shill Date 2013-05-29 Time 11:11 Sent To  
Notes
2013-05-29 11:12:345/29 ASSIGNED 6 NEW "@" STOPS PER JOSH MILLS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-18 Cont ID  
Sent By jwitmer Date 2013-09-18 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2013-09-18 Time 08:52 Sent To  
Notes
2013-09-18 08:55:15BUILDING PLAN REVIEW
 PERMIT:13050770
 ADD: MASTER PLAN NEW & MODIFIED TROLLEY SHELTERS
 CONT: TBD
 CONTACT: VIVEK GALAV
 TEL: (561)494-1061
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SEPT 18/ 2013
 ACTION: DENIED
  
 1) 2ND REQUEST. THE MODIFIED AND NEW TROLLEY SHELTERS
 ARE GOING TO BE MASTERED WE WILL NEED THE SHOP DRAWINGS
 THAT PROVIDE THE FASTENING DETAILS FOR ALL OF THE
 FRAMING MEMBERS. THE 700 SERIES OF SHEETS INDICATE ALL
 CONNECTIONS ARE TO BE WELDED OR CONCEALED FASTENERS
 SHOP DRAWING ARE TO INCLUDE ALL CONNECTION METHODS FOR
 ARCHIETECT REVIEW. 2010 WPB ADMINISTRATIVE CODE,
 CHAPTER 1 ADMINISTRATION, 2010 EDITION.107.3.5.1.1(8)
 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL BUILDINGS,
 STRUCTURAL.
  
 2) PROVISO: NOT PART OF THIS PERMIT. SHEET A2.02 ROOF
 PLANS FOR NEW AND RENOVATED SHELTERS ALSO INDICATES THE
 USE OF SOLAR PHOTOVOLTIAC SYSTEMS, PLEASE NOTE THIS
 SYSTEM WILL REQUIRE A SEPERATE ELECTRICAL PERMIT AND
 ASSOCIATED FEES. PLEASE BACK OUT THE VALUE FOR THIS
 SYSTEM OUT OF THE BUILDING COST TO BE COVERED UNDER THE
 PHOTOVOLTIAC ELECTRIC PERMIT. 109.3 WPB ADMINISTRATIVE
 CODE, BUILDING PERMIT VALUATION.
  
 3) 2ND REQUEST. SHEET A2.02 IN THE ROOFING NOTES
 DESCRIBES A ROOFING SYSTEM, KEMPEROL 2K-PUR: FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) (D) ROOFING PRODUCTS AND ASSEMBLIES PLEASE
 SUBMIT 2 COPIES OF PRODUCT APPROVAL, PLEASE CIRCLE THE
 SYSTEM THAT WILL BE ATTACHED TO ALUMINUM TUBING/ DECK
 AS DEPICTED ON A2.02. A ENGINEER MAY DO RATIONAL
 ANYLSIS IF THE PRODUCT WAS TESTED ON A STEEL DECK TO
 THE ALUMINUM DECK/ TUBING.
  
 4) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-03 Cont ID  
Sent By jwitmer Date 2013-06-03 Time 13:48 Rev Time 0.00
Received By jwitmer Date 2013-06-03 Time 13:48 Sent To  
Notes
2013-06-03 14:26:18BUILDING PLAN REVIEW
 PERMIT:13050770
 ADD: MASTER PLAN NEW & MODIFIED TROLLEY SHELTERS
 CONT: TBD
 CONTACT: VIVEK GALAV
 TEL: (561)494-1061
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 03/ 2013
 ACTION: DENIED
  
 1) THE MODIFIED AND NEW TROLLEY SHELTERS ARE GOING TO
 BE MASTERED WE WILL NEED THE SHOP DRAWINGS THAT PROVIDE
 THE FASTENING DETAILS FOR ALL OF THE FRAMING MEMBERS.
 THE 700 SERIES OF SHEETS INDICATE ALL CONNECTIONS ARE
 TO BE WELDED OR CONCEALED FASTENERS SHOP DRAWING ARE TO
 INCLUDE ALL CONNECTION METHODS FOR ARCHIETECT REVIEW.
 2010 WPB ADMINISTRATIVE CODE, CHAPTER 1 ADMINISTRATION,
 2010 EDITION.107.3.5.1.1(8) MINIMUM PLAN REVIEW
 CRITERIA COMMERCIAL BUILDINGS, STRUCTURAL.
  
 2) SHEET A2.02 ROOF PLANS FOR NEW AND RENOVATED
 SHELTERS ALSO INDICATES THE USE OF SOLAR PHOTOVOLTIAC
 SYSTEMS, PLEASE NOTE THIS SYSTEM WILL REQUIRE A
 SEPERATE ELECTRICAL PERMIT AND ASSOCIATED FEES. PLEASE
 BACK OUT THE VALUE FOR THIS SYSTEM OUT OF THE BUILDING
 COST TO BE COVERED UNDER THE PHOTOVOLTIAC ELECTRIC
 PERMIT. 109.3 WPB ADMINISTRATIVE CODE, BUILDING PERMIT
 VALUATION.
  
 3) SHEET A2.02 IN THE ROOFING NOTES DESCRIBES A ROOFING
 SYSTEM, KEMPEROL 2K-PUR: FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) (D) ROOFING PRODUCTS AND ASSEMBLIES PLEASE
 SUBMIT 2 COPIES OF PRODUCT APPROVAL, PLEASE CIRCLE THE
 SYSTEM THAT WILL BE ATTACHED TO ALUMINUM TUBING/ DECK
 AS DEPICTED ON A2.02. A ENGINEER MAY DO RATIONAL
 ANYLSIS IF THE PRODUCT WAS TESTED ON A STEEL DECK TO
 THE ALUMINUM DECK/ TUBING.
  
 4) SHEET S1.0 INDICATES THE STRUCTURES WERE DESIGNED TO
 A "C" EXPOSURE, THE WORST CASE EXPOSURE OCCURS @ DATURA
 & FLAGLER A EXPOSURE D LOCATION.
 1609.4.3 EXPOSURE CATEGORIES. EXPOSURE D. EXPOSURE D
 SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS
 DEFINED BY SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND
 DIRECTION FOR A DISTANCE OF AT LEAST 5,000 FEET (1524
 M) OR 20 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS
 GREATER. EXPOSURE D SHALL EXTEND INLAND FROM THE
 SHORELINE FOR A DISTANCE OF 600 FEET (183 M) OR 20
 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER
 FROM AN EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS
 SENTENCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-07-11 Cont ID  
Sent By Mgonzale Date 2013-07-11 Time   Rev Time 1.00
Received By mgonzale Date 2013-07-11 Time   Sent To Z
Notes
2013-07-11 09:09:50CALL 811 BEFORE STARTING.
  
 NO CONFLICTS WITH WATER OR SEWER. (AS OER GIS)
 FIELD LOCATES REQUIRED.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-18 Cont ID  
Sent By mcarsill Date 2013-06-18 Time 16:41 Rev Time 0.00
Received By mcarsill Date 2013-06-18 Time 16:38 Sent To  
Notes
2013-06-18 16:40:57WEST PALM BEACH TROLLEY SHELTERS
 NEW AND EXISTING SHELTERS
 CITY OF WEST PALM BEACH
 PERMIT # 13050770
  
 1. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 APPROVED
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-18 Cont ID  
Sent By jwitmer Date 2013-09-18 Time 08:56 Rev Time 0.00
Received By jwitmer Date 2013-09-17 Time 15:00 Sent To  
Notes
2013-09-17 15:00:24SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-23 Cont ID  
Sent By shill Date 2013-07-23 Time 13:45 Rev Time 0.00
Received By shill Date 2013-05-22 Time 10:04 Sent To  
Notes
2013-05-23 10:05:21C--15

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-23 Cont ID  
Sent By aaponte Date 2013-07-23 Time 13:37 Rev Time 0.00
Received By aaponte Date 2013-05-28 Time 16:52 Sent To  
Notes
2013-07-23 13:40:14PENDING MODIFICATION AS DISCUSSED AT THE 7/17/13
 MEETING.