Plan Review Details - Permit 13050713
Plan Review Stops For Permit 13050713
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-07 Cont ID  
Sent By jwitmer Date 2013-08-02 Time 13:01 Rev Time 0.00
Received By jwitmer Date 2013-08-01 Time 14:21 Sent To  
Notes
2013-08-02 12:39:32BUILDING PLAN REVIEW
 PERMIT: 13050713
 ADD: 313 DATURA ST
 CONT: ANDERSON-MOORE CONSTRUCTION
 TEL: (561)753-7400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: AUGUST 02/ 2013
 ACTION: DENIED
  
 1-2)COMPLIED.
  
 3) COMPLIED. 8/06/ 2013 2010 FLORIDA FIRE PREVENTION
 CODE SECTION 101. 7.2.2.6.3.1(5) SPECIAL PROVISIONS FOR
 OUTSIDE STAIRS.
  
  
 4) COMPLIED. 6/20/2013
  
 5) COMPLIED 8/06/2013 2010 FLORIDA FIRE PREVENTION CODE
 SECTION 101. 7.2.2.6.3.1(5) SPECIAL PROVISIONS FOR
 OUTSIDE STAIRS.
  
  
 6) COMPLIED 6/20/2013.
  
 7) COMPLIED 8/07/13
  
 8) COMPLIED.
  
 9) COMPLIED. 8/06/2013 2010 FLORIDA FIRE PREVENTION
 CODE SECTION 101. 7.2.2.6.3.1(5) SPECIAL PROVISIONS FOR
 OUTSIDE STAIRS.
  
 10-11) COMPLIED.
  
 12-13) COMPLIED. SIGNED & SEALED COVER LETTER FROM THE
 DESIGNER OF RECORD THAT PRODUCT APPROVALS REQUIRED BY
 RULE 9N3 WERE REVIEWD. LIST OF REVIEWED PRODUCT
 APPROVALS ARE LISTED WITH ASSOCIATED NOA NUMBER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By jwitmer Date 2013-06-12 Time 15:21 Rev Time 0.00
Received By jwitmer Date 2013-06-12 Time 10:35 Sent To  
Notes
2013-06-12 12:33:34BUILDING PLAN REVIEW
 PERMIT: 13050713
 ADD: 313 DATURA ST
 CONT: ANDEERSON-MOORE CONSTRUCTION
 TEL: (561)753-7400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 12/ 2013
 ACTION: DENIED
  
 1) ) SHEET LS-01 EXISTING STAIR # 1 THE PLANS SHOW A
 DOORWAY UNDER THE STAIR, PLEASE PROVIDE A CROSS SECTION
 AND CODE COMPLIANCE FOR 2010 FBC-B 1009.6.3 ENCLOSURES
 UNDER STAIRS.
  
 2) SHEET LS-01 THE ELEVATOR LOBBY RESTROOMS DOORS
 107-108, PLEASE REVIEW 2010 FL ACCESSIBILITY CODE
 SECTION DOORS IN SERIES 404.2.6, SEE 603.2.3 EX # 2
 THIS MAY HELP.
  
 3) SHEET A-1.01 DOOR # 11 VERSES A-6.01 INDICATES A ?
 HR DOOR. PLEASE REVIEW 2010 FBC-B
 1026.6, 1022.3 SECTION 715 TABLE 715.4 1 HR EXIT
 ENCLOSURES, 1 HR OPENING PROTECTIVE?S, ALSO REVIEW 2007
 FBC-B COMMENTARY FIGURE 1023.6(1) CROSS HATCHED AREA
 REQUIRES 1 HOUR OPENING PROTECTIVE?S WITHIN 10 FOOT OF
 DOORWAY AND LANDINGS.
  
 4) COMPLIED. 6/20/2013 SHEET A-1.01 EXIT FROM 3RD FLOOR
 TO 2ND FLOOR STAIR # 1, YOU HAVE TO LEAVE THE STAIR
 ENCLOSURE AND THEN GO BECK INTO THE STAIR ENCLOSE FROM
 THE 2ND FLOOR TO 1ST FLOOR. 2010 FEBC- 705.2, EXCEPTION
 # 2 MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF
 THE FLORIDA BUILDING CODE, BUILDING AND THE FLORIDA
 FIRE PREVENTION CODE UNDER WHICH THE BUILDING WAS
 CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF
 EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO LIFE.BUIULDING &
 FIRE OFFICIALS AGREE CONSIDERED TO BE CODE COMPLIANT AT
 TIME BUILDING WAS BUILT.
  
 5) LS-02 VERSES A-1.01 2ND FLOOR THE PATH THAT LEADS TO
 THE NEW EXTERIOR STAIR. THE WINDOWS APPEAR TO SHOW A
 FIRE RATING AND ALSO A WATER CURTAIN. SHEET A-6.01
 INDICATES 45 MINUTE RATED, PLEASE SEE 2007 FBC-B CODE
 COMMENTARY FIGURE 1023.6(1).
  
 6) COMPLIED 6/20/2013. THIS IS A BUILDING TYPE V-B.
 ZERO LOT LINE EXTERIOR WALLS TO BE 1 HOUR FIRE SISTANCE
 RATED. THE GLASS BLOCK WILL BE CONSIDERED INFILL WALL
 AND WILL ALSO BE REQUIRED TO BE 1 HOUR RATED SINCE 2010
 FBC-B TABLE 705.8 DOES NOT ALLOW OPENINGS IN WALLS 0-3
 FEET FROM THE PROPERTY LINE.
  
 7) SHEET A-1.01 INDICATES NEW ROOF TOP A/C STANDS,
 PLEASE PROVIDE THE ATTACHMENT OF THE STANDS TO THE ROOF
 STRUCTURE AS WELL AS THE EQUIPMENT TO THE STAND.
 PLEASE REVIEW 2010 FBC-B SECTION 1609.8 ROOFTOP
 STRUCTURES AND EQUIPMENT.
  
 8) SHEET A-1.01 INDICATES NEW ROOF TOP A/C STANDS, THE
 ROOF TOP STANDS ARE WITHIN 3?-0? OF THE PARAPET,
 SECTION 5/ A-1.03 DOES NOT INDICATE HOW TALL THE
 PARAPET IS? SEE 2010 FBC-B
 1013.5 MECHANICAL EQUIPMENT.
  
 9) SHEET A-1.02 THIRD FLOOR, WINDOW # 17 AND DOOR 304
 WILL NEED TO BE 1 HOUR FIRE RATED, AGAIN 1026.6, 1022.3
 SECTION 715 TABLE 715.4 1 HR EXIT ENCLOSURES, 1 HR
 OPENING PROTECTIVE?S, ALSO REVIEW 2007 FBC-B COMMENTARY
 FIGURE 1023.6(1) CROSS HATCHED AREA REQUIRES 1 HOUR
 OPENING PROTECTIVE?S WITHIN 10 FOOT OF DOORWAY AND
 LANDINGS.
  
 10) SHEET A-5.10 KITCHEN ROOM 303 MICROWAVE HEIGHT MUST
 MEET THE REACH RANGES, PROVIDE COMPLIANCE WITH 2010 FL
 ACCESSIBILITY CODE 308 REACH RANGES AND 309 OPERABLE
 PARTS.
  
 11) A-1.01 AND S-1.01 BOTH INDICATE WHAT APPEARS TO BE
 SLOPED FLOORS, PLEASE PROVIDE THE HEIGHT DIFFERENCE IN
 FLOORS AND THE DISTANCE THE SLOPED FLOOR WILL BE, TO
 DETERMINE IF CONSIDERED GRADE OR RAMP WITH REQUIRED
 HANDRAILS. ACCESSIBILITY CODE ADVISORY 505.1 GENERAL.
 HANDRAILS ARE REQUIRED ON RAMP RUNS WITH A RISE GREATER
 THAN 6 INCHES (150 MM) (SEE 405.8) AND ON CERTAIN
 STAIRWAYS (SEE 504). HANDRAILS ARE NOT REQUIRED ON
 WALKING SURFACES WITH RUNNING SLOPES LESS THAN 1:20.
 HOWEVER, HANDRAILS ARE REQUIRED TO COMPLY WITH 505 WHEN
 THEY ARE PROVIDED ON WALKING SURFACES WITH RUNNING
 SLOPES LESS THAN 1:20 (SEE 403.6). SECTIONS 505.2,
 505.3, AND 505.10 DO NOT APPLY TO HANDRAILS PROVIDED ON
 WALKING SURFACES WITH RUNNING SLOPES LESS THAN 1:20 AS
 THESE SECTIONS ONLY REFERENCE REQUIREMENTS FOR RAMPS.
  
 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 13) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2014-08-08 Cont ID  
Sent By jwitmer Date 2014-08-08 Time 09:07 Rev Time 0.00
Received By jwitmer Date 2014-08-08 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-20 Cont ID  
Sent By dharvey Date 2013-08-20 Time 16:42 Rev Time 0.00
Received By dharvey Date 2013-08-20 Time 16:34 Sent To  
Notes
2013-08-20 16:42:16PREVIOUS ITEMS NOTED CLEARED UP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-04 Cont ID  
Sent By dharvey Date 2013-06-04 Time 16:17 Rev Time 0.00
Received By dharvey Date 2013-06-04 Time 16:17 Sent To  
Notes
2013-06-04 16:22:506-4-13
 FIRST REVIEW
 PLEASE CORRECT PANEL SCHEDULES HP2 AND LP1. THEY BOTH
 SHOW A FEED TO AHU 1-2 AND CU 1-2. PLEASE REVIEW AND
 CORRECT.
 ALSO, CU 1-3 AND 1-4 STATE A MOCP AS 15 AMPS ON THE M
 DRAWINGS. THERE IS A 20 AMP CIRCUIT BREAKER SHOWN IN
 THE PANEL SCHEDULE PLEASE CORRECT
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-08-15 Cont ID  
Sent By wjolin Date 2013-08-15 Time 11:49 Rev Time 0.00
Received By wjolin Date 2013-08-15 Time 11:16 Sent To  
Notes
2013-08-15 11:49:05313 DATURA STREET
 PERMIT #13050713
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE ALARM: HEAT AND SMOKE DETECTOR SHOULD NOT BE
 INSTALLED AT THE TOP OF THE ELEVATOR SINCE THERE WILL
 NOT BE ANY SPRINKLER PROTECTION AT THIS LOCATION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-07 Cont ID  
Sent By wjolin Date 2013-06-07 Time 13:20 Rev Time 0.00
Received By wjolin Date 2013-06-05 Time 10:58 Sent To  
Notes
2013-06-05 13:08:26313 DATURA STREET
 PERMIT #13050713
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101
 REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION
 WITH FLORIDA AMENDMENTS.)
  
 GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL
 BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES
 IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL - ELEVATOR RECALL: PER SECTION 9.4.3.2, ALL
 EXISTING ELEVATORS HAVING A TRAVEL DISTANCE OF 25 FEET
 OR MORE ABOVE OR BELOW THE LEVEL THAT BEST SERVES THE
 NEEDS OF EMERGENCY PERSONNEL FOR FIRE-FIGHTING OR
 RESCUE PURPOSES SHALL CONFORM TO THE FIRE FIGHTERS.
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.3, SAFETY
 CODE FOR EXISTING ELEVATORS AND ESCALATORS.
  
 SHEET LS-01: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET LS-01 - EXISTING STAIR #1: PER SECTION 7.2.2.5.3,
 ENCLOSED, USABLE SPACES WITHIN EXIT ENCLOSURES SHALL BE
 PROHIBITED, INCLUDING UNDER STAIRS, UNLESS THE SPACE
 UNDER THE STAIRS MEETS THE FOLLOWING REQUIREMENTS:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THE SAME FIRE RESISTANCE AS THE EXIT
 ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE STAIR ENCLOSURE.
 (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE
 OR OTHERWISE HAZARDOUS MATERIALS.
  
 SHEET LS-02: EXISTING STAIR #1 (SECOND FLOOR) INDICATES
 OCCUPANTS FROM THE THIRD FLOOR MUST EXIT THE PROTECTED
 STAIR ENCLOSURE AND THEN RE-ENTER THE PROTECTED STAIR
 ENCLOSURE TO EXIT THE BUILDING. SECTION 7.1.3.2.2
 REQUIRES AN EXIT ENCLOSURE TO PROVIDE A CONTINUOUS
 PROTECTED PATH OF TRAVEL TO AN EXIT DISCHARGE. THIS
 APPLIES TO NEW AND EXISTING CONDITIONS PER NFPA 1
 SECTIONS 14.3.2 AND 1.3.1.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 SHEET E1.1-1.3: PROVIDE EMERGENCY LIGHTING FOR EXTERIOR
 STAIRS AND EXTERIOR ROOF EGRESS PATH LEADING TO THE
 EXIT DISCHARGE (ALLEY). EMERGENCY ILLUMINATION SHALL BE
 PROVIDED FOR A MINIMUM OF .5 HOURS IN THE EVENT OF
 FAILURE OF NORMAL LIGHTING. EMERGENCY LIGHTING
 FACILITIES SHALL BE ARRANGED TO PROVIDE INITIAL
 ILLUMINATION THAT IS NOT LESS THAN AN AVERAGE OF 1
 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN 0.1
 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT FLOOR
 LEVEL.
  
 SHEET FA-1: NO FIRE ALARM NOTIFICATION APPLIANCES
 PROVIDED IN TOILET #118, TOILET #112, TOILET #113,
 OFFICE SPACE #111, OR CORRIDOR #103.
  
 SHEET FA-1: FIRE ALARM SYSTEM SHALL BE FULLY
 ADDRESSABLE.
  
 ELECTRICAL: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 FIRE SPRINKLER: THE RETAIL (MERCANTILE OCCUPANCY)
 SHOULD BE DESIGN FOR ORDINARY HAZARD GROUP 1 OR GROUP 2
 IN LIEU OF THE LIGHT HAZARD DESIGNATION INDICATED ON
 THE PLAN.
  
 FIRE SPRINKLER: PROVIDE CURRENT HYDRANT FLOW TEST
 INFORMATION ON THE PLANS.
  
 FIRE SPRINKLER: REGULAR STANDARD SPRAY SPRINKLERS ARE
 NO LONGER AN ACCEPTABLE METHOD FOR PROTECTING GLAZING
 TO ACHEIVE A 1-HOUR FIRE RATED SEPARATION. CURRENTLY,
 ONLY TYCO "WINDOW SPRINKLERS" ARE LISTED TO ACHIEVE A
 ONE-HOUR OR TWO-HOUR FIRE RATED EQUIVALENT FOR
 PROTECTING GLAZING ASSEMBLIES.
  
 TYCO WINDOW SPRINKLERS: IF THE DESIGN INTENT IS TO USE
 TYCO WINDOW SPRINKLERS (IN LIEU OF FIRE-RATED GLASS) TO
 ACHIEVE A FIRE RATED SEPARATION, THE SPRINKLERS MUST BE
 INSTALLED ACCORDING TO THE UL LISTING DATA AND SHALL
 WET THE ENTIRE GLAZING SURFACE. SPRINKLERS CANNOT BE
 USED TO PROTECT OPERABLE DOORS OR WINDOWS. THE WINDOW
 SPRINKLERS DO NOT ALLOW HORIZONTAL WINDOW MULLIONS AND
 REQUIRE THE GLASS CURTAIN WALL TO BE ATTACHED TO A
 THREE FOOT HIGH PONY WALL TO KEEP COMBUSTIBLE MATERIALS
 AT LEAST TWO INCHES AWAY FROM THE GLAZING. PAY SPECIAL
 ATTENTION TO THE GLAZING ASSEMBLY AS THE SPRINKLER
 POSITIONING VARIES FOR BUTT-GLAZED INSTALLATIONS
 COMPARED TO VERTICAL MULLION INSTALLATIONS. VERTICAL
 MULLIONS SHALL BE OF A DEPTH THAT PREVENTS COLD
 SOLDERING OF ADJACENT SPRINKLERS. THE SPRINKLER DESIGN
 SHOULD INDICATE WHICH WINDOW SPRINKLER MODEL WILL BE
 USED (HORIZONTAL SIDEWALL OR PENDENT VERTICAL
 SIDEWALL).
  
 FIRE SPRINKLER: CONFIRM THE EXISTING ATTACHED STORAGE
 BUILDING (INDICATED AS NIC) IS PROTECTED BY THE
 AUTOMATIC SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-08 Cont ID  
Sent By jwitmer Date 2014-08-08 Time 09:07 Rev Time 0.00
Received By jwitmer Date 2014-08-08 Time 09:02 Sent To  
Notes
2014-08-08 09:03:30ROUTED TO ELECTRIC D. HAYES DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2013-08-20 Cont ID  
Sent By dharvey Date 2013-08-20 Time 16:47 Rev Time 0.00
Received By dharvey Date 2013-07-17 Time 16:31 Sent To  
Notes
2013-07-18 16:34:41C40
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-12 Cont ID  
Sent By jwitmer Date 2013-06-12 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2013-05-21 Time 09:37 Sent To  
Notes
2013-05-23 09:38:01B--9

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-08-22 Cont ID  
Sent By jwitmer Date 2013-08-22 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2013-08-22 Time 11:28 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-08-02 Cont ID  
Sent By jwitmer Date 2013-08-02 Time 12:39 Rev Time 0.00
Received By jwitmer Date 2013-08-02 Time 12:39 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By jwitmer Date 2013-06-12 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2013-06-12 Time 15:22 Sent To  
Notes
2013-06-12 15:22:43BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-08-14 Cont ID  
Sent By hmoser Date 2013-08-14 Time 14:58 Rev Time 0.00
Received By hmoser Date 2013-08-14 Time 14:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-06-04 Cont ID  
Sent By hmoser Date 2013-06-04 Time 14:41 Rev Time 0.00
Received By hmoser Date 2013-06-04 Time 13:20 Sent To  
Notes
2013-06-04 14:41:40PLANS DENIED
 1) PROVIDE DUCT SIZE ON ALL DUCT.
 PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL ON CONDENSER STAND TIED TO ROOF
 IF NOT EXISTING . PROVIDE A DETAIL ON CONDENSER TIED TO
 STAND.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-08-08 Cont ID  
Sent By lwagner Date 2013-08-08 Time 09:40 Rev Time 0.00
Received By lwagner Date 2013-08-02 Time 09:47 Sent To  
Notes
2013-08-02 15:06:13FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-05-29 Cont ID  
Sent By lwagner Date 2013-05-29 Time 15:39 Rev Time 0.00
Received By lwagner Date 2013-05-29 Time 10:18 Sent To  
Notes
2013-05-29 15:35:44FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P-8: THE WATER CLOSETS ON THE 3RD FLOOR
 ISOMETRIC ARE NOT VENTED.
 901.2.1 VENTING REQUIRED.
 EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
  
 2. SHEET P-8: THREE WATER CLOSETS ARE NOT VENTED ON THE
 1ST FLOOR. IF THE FIRST FLOOR RESTROOMS ARE A CIRCUIT
 VENT, A VERTICAL DRY VENT IS REQUIRED BETWEEN THE TWO
 MOST UPSTREAM WATER CLOSETS.
 911.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
 3. SHEET P-8: AS SHOWN, THE TWO WATER CLOSETS FOR ROOMS
 118 & 108 ARE VENTED WITH A HORIZONTAL DRY VENT.
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6
 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 4. PLEASE PROVIDE PIPE SIZES FOR ROOF DRAINAGE SHOWN ON
 P-2 THROUGH P-5 PER TABLE 1106.2(1) & 1106.3
  
 5. A HI/LO DRINKING FOUNTAIN WILL BE REQUIRED ON THE
 1ST FLOOR PER PLUMBING TABLE 403.1 AND FBC
 ACCESSIBILITY 211.1 GENERAL.
 WHERE DRINKING FOUNTAINS ARE PROVIDED ON AN EXTERIOR
 SITE, ON A FLOOR, OR WITHIN A SECURED AREA THEY SHALL
 BE PROVIDED IN ACCORDANCE WITH 211.
  
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2013-08-13 Cont ID  
Sent By aaponte Date 2013-08-13 Time 16:27 Rev Time 0.00
Received By aaponte Date 2013-08-13 Time 16:27 Sent To  
Notes
2013-08-13 16:28:42PROVISO: 1. GROUND COVER OR TREE GRATES WILL BE
 REQUIRED ON TREES ALONG SIDEWALK. FINAL APPROVAL BY
 PLANNING DIVISION REQUIRED.
 2. PROPOSED FENCE ON REAR SHALL BE A MAXIMUM 6 FEET IN
 HEIGHT.
2013-07-22 11:00:547/22/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-05-31 Cont ID  
Sent By aaponte Date 2013-05-31 Time 16:18 Rev Time 0.00
Received By aaponte Date 2013-05-28 Time 16:50 Sent To  
Notes
2013-05-31 16:24:181.NEW MECHANICAL EQUIPMENT ON ROOF TOP SHALL BE
 ENCLOSED AND SCREENED IN SUCH A MANNER THAT THE
 ENCLOSURE IS DESIGNED AS AN INTEGRAL PART OF THE
 OVERALL BUILDING DESIGN (SEC 94-109).
 2. PLEASE INDICATE THE LOCATION OF THE PROPERTY LINE ON
 ALL FLOOR PLANS AND ELEVATIONS.
 3. ANY ENCROACHMENTS INTO THE ROW WILL REQUIRE AN
 AERIAL EASEMENT (PROPOSED ALUCOBOND PANEL MAY BE
 ANCROACHING INTO ROW).
 4. PLEASE INDICATE LOCATION OF GARAGE DISPOSAL.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439