Plan Review Stops For Permit 13050652 |
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2013-06-20 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-06-20 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-06-20 |
Time |
15:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2013-06-13 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-06-13 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-06-13 |
Time |
15:23 |
Sent To |
|
|
Notes |
2013-06-13 15:36:47 | 6-13-13 - 4TH REVIEW | | | | CONTRACTOR PROVIDED A CUT SHEET FOR THE UNDERGROUND | | CABLES. WHEN I CHECKED WITH THE MANUFACTURER, THEY SAID | | THE CABLES HE PROVIDED WERE FOR INDOOR USE ONLY. | | | | ALSO, THE CONTRACTOR PROVIDED A CUT SHEET FOR THE | | OUTDOOR RATED CAMERAS. HOWEVER, THE CAMERA NUMBER ON | | THE DRAWINGS DOESN'T AGREE WITH THE CUT SHEET NUMBER. | | | | CONTRACTOR NEEDS TO COME IN AND DISCUSS THIS WITH THE | | PLAN REVIEWER OR THE CHEIF ELECTRICAL INSPECTOR | | | | VB |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2013-05-29 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-05-29 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-05-29 |
Time |
13:07 |
Sent To |
|
|
Notes |
2013-05-29 13:08:49 | 5-29-13 | | FAILED AGAIN | | STILL WAITING FOR INFORMATION FOR A WET LISTING FOR | | CAMERAS AND UNDERGROUND CABLES TO THE CAMERAS AS SHOW | | ON PLAN | | VB |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2013-05-28 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-05-28 |
Time |
09:58 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-05-28 |
Time |
09:58 |
Sent To |
|
|
Notes |
2013-05-28 09:59:00 | 5-28-13 | | FAILED AGAIN - | | STILL NEED SPEC SHEETS SHOWING OURDOOR USE CABLES AND | | EQUIPMENT | | VB |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-05-20 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-05-20 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-05-20 |
Time |
15:55 |
Sent To |
|
|
Notes |
2013-05-20 15:56:32 | 5-20-13 | | | | PROVIDE SPECS SHOWING OUTDOOR EQUIPMENT THAT IS SHOWN | | ON PLAN IS RATED FOR WET LOCATION | | | | PROVIDE SPECS FOR WET LOCATION CABLE FOR OUTDOOR | | EQUIPMENT SHOWN ON PLAN | | | | VB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-06-20 |
Time |
08:53 |
Sent To |
|
|
Notes |
2013-06-20 08:53:59 | SENT TO ELECTRICAL UNDER $5K BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2013-06-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-06-20 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-06-11 |
Time |
13:26 |
Sent To |
|
|
Notes |
2013-06-12 13:26:42 | SENT TO ELECTRICAL SHELF FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-06-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-29 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-23 |
Time |
09:35 |
Sent To |
|
|
Notes |
2013-06-12 13:25:25 | LASST REVIEW DONE ON 5/29/13. JG. | 2013-05-25 09:36:13 | UNDER 5 K ELECTRIC |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-05-25 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2013-05-20 |
Time |
09:34 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2013-05-20 |
Time |
15:16 |
Sent To |
|
|
Notes |
2013-05-20 15:16:51 | SENT TO ELECTRIC BOX. |
|
|