Plan Review Details - Permit 13050618
Plan Review Stops For Permit 13050618
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-07-03 Cont ID  
Sent By shill Date 2013-07-03 Time 09:07 Rev Time 0.00
Received By shill Date 2013-07-03 Time 09:07 Sent To  
Notes
2013-07-03 09:09:19PROVISO
  
 SEPARATE PERMIT FOR SHUTTERS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-07-02 Cont ID  
Sent By shill Date 2013-07-02 Time 16:36 Rev Time 0.00
Received By shill Date 2013-07-02 Time 16:33 Sent To  
Notes
2013-07-02 16:33:38****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. IMPACT PROTECTION REQUIRED FOR NEW SLIDERS, FBC R
 301.2.1.2.
  
 PROVIDE EITHER IMPACT SLIDING GLASS DOOR PRODUCT
 APPROVALS, OR IMPACT PROTECTION PRODUCT APPROVALS. IF
 SHUTTERS ARE PROPOSED, COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 3. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-18 Cont ID  
Sent By shill Date 2013-06-18 Time 10:11 Rev Time 0.00
Received By shill Date 2013-06-18 Time 10:11 Sent To  
Notes
2013-06-18 10:23:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SCOPE NOT CLEAR.
  
 WINDOW PRODUCT APPROVAL SUBMITTED, NO WINDOW
 REPLACEMENT SHOWN ON PLAN.
  
 PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, SIZES,
 WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. IMPACT PROTECTION REQUIRED FOR NEW SLIDERS, FBC R
 301.2.1.2.
  
 PROVIDE EITHER IMPACT SLIDING GLASS DOOR PRODUCT
 APPROVALS, OR IMPACT PROTECTION PRODUCT APPROVALS. IF
 SHUTTERS ARE PROPOSED, COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
  
 3. EXPEDITED REQUEST HAS BEEN VOIDED AS WE WERE UNABLE
 TO ACCOMODATE THAT REQUEST (AND NO FEES CHARGED). IF
 YOU WISH FOR THE SECOND REVIEW TO BE EXPEDITED, PLEASE
 COMPLETE ANOTHER EXPEDITED REQUEST FORM.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By rmcdouga Date 2013-07-02 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2013-07-02 Time 08:45 Sent To  
Notes
2013-07-02 08:45:36SENT TO S HILL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-14 Cont ID  
Sent By rmcdouga Date 2013-06-14 Time 15:46 Rev Time 0.00
Received By rmcdouga Date 2013-06-14 Time 15:46 Sent To  
Notes
2013-06-14 15:54:322010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) SUBMIT TWO SETS OF ELECTRICAL PLANS SHOWING THE
 LOCATIONS OF EXISTING AND RELOCATED OUTLETS AND THAT
 ALL WORK COMPLIES WITH THE 2008 NATIONAL ELECTRICAL
 CODE. CITY AMENDMENTS 107.2.1
  
 2) MULTIWIRE BRANCH CIRCUITS ARE REQUIRED TO COMPLY
 WITH NEC 210.4.
  
 3) ARC-FAULT PROTECTION IS REQUIRED TO COMPLY WITH NEC
 210.4.
  
 4) TAMPER RESISTANT RECEPTACLES ARE REQUIRED TO COMPLY
 WITH NEC 406.11.
  
 5) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED SMOKE
 DETECTORS.
  
 6) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-06-05 Cont ID  
Sent By fmittner Date 2013-06-05 Time 14:04 Rev Time 0.00
Received By fmittner Date 2013-06-05 Time 14:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-02 Cont ID  
Sent By shill Date 2013-07-02 Time 16:33 Rev Time 0.00
Received By shill Date 2013-06-21 Time 10:45 Sent To  
Notes
2013-06-21 10:46:13ONLY ADDRESSING ELECTRICAL COMMENTS. SUBMITTAL SENT TO
 MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-18 Cont ID  
Sent By shill Date 2013-06-18 Time 10:37 Rev Time 0.00
Received By shill Date 2013-05-17 Time 17:01 Sent To  
Notes
2013-06-12 11:10:346/12 TO RM DESK FOR ELEC/PLUMBING REVIEWS
2013-06-06 09:28:336/6/13 IN MISC. #1
2013-05-17 17:01:58EXPEDITED
 ROUTED TO ZONING BOX FOR HISTORIC REVIEW

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-14 Cont ID  
Sent By rmcdouga Date 2013-06-14 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2013-06-14 Time 15:26 Sent To  
Notes
2013-06-14 15:28:07REMOVE AND REPLACE EXISTING FIXTURES IN SAME LOCATIONS.
 A PLUMBING SUB-PERMIT IS REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-05 Cont ID  
Sent By fmittner Date 2013-06-05 Time 14:04 Rev Time 0.00
Received By fmittner Date 2013-06-05 Time 14:04 Sent To  
Notes
***NONE***