Plan Review Details - Permit 13050607
Plan Review Stops For Permit 13050607
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-04 Cont ID  
Sent By dharvey Date 2013-06-04 Time 09:21 Rev Time 0.00
Received By dharvey Date 2013-06-04 Time 09:21 Sent To  
Notes
2013-06-04 09:22:266-4-13
 CORRECTIONS MADE. WIND LOAD CALCS AND WET LOCATION
 CABLE SPECS SUBMITTED
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-21 Cont ID  
Sent By dharvey Date 2013-05-21 Time 10:23 Rev Time 0.00
Received By dharvey Date 2013-05-21 Time 10:23 Sent To  
Notes
2013-05-21 10:26:165-21-13
 PROVIDE SPEC SHEET FOR ALL COMMUNICATION CABLES. SHOW
 LISTED WET LOCATION IF BEING INSTALLED UNDERGROUND
 PROVIDE ENGINEERED DETAIL AND WIND LOAD CALCULATIONS
 FOR POLE AND FOUNDATION PER SOUTH FLORIDA REQUIREMENTS
 PLEASE NOTE THAT ALL SPLICES AND CONDUCTORS UNDERGROUND
 MUST BE LISTED FOR WET LOCATION
 ALL WORK TO MEET 2008 NEC
 VB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-04 Cont ID  
Sent By dharvey Date 2013-06-04 Time 09:20 Rev Time 0.00
Received By dharvey Date 2013-06-04 Time 09:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-04 Cont ID  
Sent By dharvey Date 2013-05-21 Time 09:18 Rev Time 0.00
Received By dharvey Date 2013-05-17 Time 14:54 Sent To  
Notes
2013-05-17 14:55:20SENT TO ELECTRICAL SHELF FOR REVIEW. JG.