Plan Review Details - Permit 13050533
Plan Review Stops For Permit 13050533
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2013-07-11 Time 16:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-31 Cont ID  
Sent By jwitmer Date 2013-05-31 Time 12:56 Rev Time 0.00
Received By jwitmer Date 2013-05-31 Time 12:55 Sent To  
Notes
2013-05-31 13:02:45BUILDING PLAN REVIEW
 PERMIT: 13050533
 ADD: 801 VILLAGE BLVD # 306
 CONT: KCA CONSTRUCTION, INC
 TEL: (561)361-1491
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/31/2013
 ACTION: DENIED
  
 1) SHEET A-2 INDICATES NEW STORERONTDOOR AND WINDOW:
 PLANS DO NOT INDICATE TO WHAT WIND CRITERIA THIS
 PROJECT WAS DESIGNED TOO,
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-05 Cont ID  
Sent By dharvey Date 2013-07-05 Time 13:59 Rev Time 0.00
Received By dharvey Date 2013-07-05 Time 13:44 Sent To  
Notes
2013-07-05 13:59:44BY RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-23 Cont ID  
Sent By dharvey Date 2013-05-23 Time 10:12 Rev Time 0.00
Received By dharvey Date 2013-05-23 Time 10:12 Sent To  
Notes
2013-05-23 10:16:315-23-13
  
 1. PROVIDE LOAD CALCULATIONS PER NEC 220
 2. FLUORESCENT FIXTURES TO MEET NEC 410.130G
 3. LIGHTING CONTROLS REQUIRED PER FLORIDA ENERGY CODE
 505.2.2
 4. IDENTIFY DISCONNECTS PER NEC 110.22A
 5. PER NEC 210.62, SHOW WINDOW RECEPTACLES ARE REQUIRED
 FOR EVERY 12 FT OF STORE FRONT
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-07-05 Cont ID  
Sent By wjolin Date 2013-07-05 Time 12:59 Rev Time 0.00
Received By wjolin Date 2013-07-05 Time 12:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By wjolin Date 2013-05-28 Time 09:51 Rev Time 0.00
Received By wjolin Date 2013-05-28 Time 09:31 Sent To  
Notes
2013-05-28 09:51:49801 VILLAGE BOULEVARD - SUITE #306
 PERMIT #13050533
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 SHEET A2: THUMB-TURN LOCK/LATCH TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 SHEET A2: DRAWING HAS TEXT ON TOP OF OTHER TEXT WHICH
 CANNOT BE READ.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2013-07-02 Time 09:58 Sent To  
Notes
2013-07-03 09:58:33B04
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-04 Cont ID  
Sent By hmoser Date 2013-06-04 Time 11:44 Rev Time 0.00
Received By hmoser Date 2013-05-15 Time 16:32 Sent To  
Notes
2013-05-21 16:37:51B--4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-06-04 Cont ID  
Sent By hmoser Date 2013-06-04 Time 11:44 Rev Time 0.00
Received By hmoser Date 2013-06-04 Time 11:24 Sent To  
Notes
2013-06-04 11:43:53CALLED CONTRACTOR KEATH A/C CONTRACTOR WILL SUBMIT HIS
 OWN APPLICATION AND PLANS FOR PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By lwagner Date 2013-05-28 Time 15:09 Rev Time 0.00
Received By lwagner Date 2013-05-28 Time 14:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-05-28 Cont ID  
Sent By ajones Date 2013-05-28 Time 16:47 Rev Time 0.00
Received By ajones Date 2013-05-28 Time 16:47 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved