 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE SYSTEM WILL NEED TO BE PRESSURE TESTED TO 200 PSI
 BECAUSE BRANCH LINE PIPING HAS BEEN ADDED; IE THIS IS
 NOT A SIMPLE HEAD RELOCATION.
  
 REVISED HYDRAULIC CALCULATIONS WILL NEED TO BE
 SUBMITTED SHOWING THE USE AND ADDITIONAL FRICTION LOSS
 ASSOCIATED WITH THE VICFLEX FLEXIBLE SPRINKLER DROPS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-30 Cont ID  
Sent By rferguso Date 2013-05-30 Time 12:54 Rev Time 0.00
Received By rferguso Date 2013-05-30 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-07 Cont ID  
Sent By wjolin Date 2013-06-07 Time 12:25 Rev Time 0.00
Received By wjolin Date 2013-06-07 Time 12:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2013-06-06 Cont ID  
Sent By shill Date 2013-05-30 Time 14:29 Rev Time 0.00
Received By lmartine Date 2013-05-15 Time 16:43 Sent To  
Notes
2013-06-06 13:14:44NEEDS CONTRACTOR
2013-05-21 16:43:44IN MECH BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 08:39 Rev Time 0.00
Received By hmoser Date 2013-05-28 Time 08:31 Sent To FIRE
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved