Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-30 Cont ID  
Sent By shill Date 2013-05-30 Time 16:09 Rev Time 0.00
Received By shill Date 2013-05-30 Time 16:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-15 Cont ID  
Sent By shill Date 2013-05-15 Time 17:58 Rev Time 0.00
Received By shill Date 2013-05-15 Time 17:58 Sent To  
Notes
2013-05-15 18:09:04****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THIS APPEARS TO BE LOCATED IN EXPOSURE C, SEE FBC R
 301.2.1.4.3. PROVIDE MEAN ROOF HEIGHT. FOR 15' MRH,
 ZONE 3 DP REQUIRED PER FBC R TABLE 301.2(2) IS -95.7;
 FOR 20' IT IS -102. DESIGN PRESSURE OF -90 PROPOSED
 DOES NOT COMPLY WITH THE TABLE.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FAC9N-3. PROVIDE COVER SHEET FOR THE EVALUATION REPORT.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-30 Cont ID  
Sent By shill Date 2013-05-30 Time 16:46 Rev Time 0.00
Received By shill Date 2013-05-30 Time 15:25 Sent To  
Notes
2013-05-30 15:26:08SENT TO SAMANTHA'S DESK FOR REVIEW. JG.