Plan Review Details - Permit 13050441
Plan Review Stops For Permit 13050441
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-29 Cont ID  
Sent By jwitmer Date 2013-08-29 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2013-08-29 Time 06:45 Sent To  
Notes
2013-08-29 08:11:57PROVISO REVISION REQUIRED SEE DIGITAL SHEET A7.01:
  
 1) SEE HIGHLIGHTED AREA ACCESS AISLE MINIMUM WIDTH
 REQUIRED 44 INCHES OCCUPANT LOAD SEERVING > 50
 OCCUPANTS. FBC-B 1028.9.1. CURRENT WIDTH OF 2.34 FEET.
  
 2) SECOND AREA OF COMPLIANCE REQUIRED, COMPLY WITH
 FBC-B 1017.3 AISLE ACCESSWAY SHALL NOT EXCEED 30 FEET
 FROM ANY SEAT TO THE POINT WHERE A PERSON HAS TWO
 CHOICES OR MORE PATHS OF EGRESS TRAVEL TO SEPERATE
 EXITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-02 Cont ID  
Sent By jwitmer Date 2013-07-02 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2013-07-01 Time 16:02 Sent To  
Notes
2013-07-02 11:35:05BUILDING PLAN REVIEW
 REVISION: 13050441
 PERMIT: 12100295
 ADD: 477 S ROSEMARY # 169
 CONT: CRAFT
 TEL: (561)275-8770
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 02/2013
 ACTION: DENIED
  
 1) REVISION IS MISSING THE CITY PACE APPROVAL STAMP.
  
 2) THE LAST REVISIONS REVIEWED BY THE CITY OF WEST PALM
 BEACH ARE DATED 2/01/2013. PLEASE PROVIDE A NARATIVE
 FOR THE ARCHITECTURAL SHEETS LISTING WHAT THE REVISIONS
 ARE FOR EACH PAGE SINCE THE LAST REVIEW DATE THIS WILL
 GREATLY HELP IN THE REVIEW PROCESS FOR QUESTIONS AND
 TIME SAKE. 2010 WEST PALM BEACH ADMINISTRATIVE CODE
 CHAPTER 1 AMENDMENTS FLORIDA BUILDING CODE. 107.2
 CONSTRUCTION DOCUMENTS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-09-04 Cont ID  
Sent By dharvey Date 2013-09-04 Time 07:46 Rev Time 0.00
Received By dharvey Date 2013-09-04 Time 07:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-13 Cont ID  
Sent By dharvey Date 2013-06-13 Time 08:43 Rev Time 0.00
Received By dharvey Date 2013-06-13 Time 08:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-08-24 Cont ID  
Sent By wjolin Date 2013-08-24 Time 12:21 Rev Time 0.00
Received By wjolin Date 2013-08-24 Time 12:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-26 Cont ID  
Sent By wjolin Date 2013-06-26 Time 11:04 Rev Time 0.00
Received By wjolin Date 2013-06-25 Time 14:18 Sent To  
Notes
2013-06-25 15:30:50477 SOUTH ROSEMARY AVENUE - SUITE #169
 TRACKING #13050441
 PERMIT #12100295
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A102 - COVERED PATIO #104: PROVIDE THE INTERIOR
 WALL CLASSIFICATION INFORMATION (FLAME SPREAD AND SMOKE
 DEVELOPMENT) FOR THE PROPOSED PATION ENCLOSURE SYSTEM.
 THE INTERIOR FINISH MATERIALS FOR WALLS AND CEILINGS
 SHALL MEET THE SMOKE DEVELOPMENT (0-450) AND FLAME
 SPREAD (76-200) REQUIREMENTS FOR CLASS C INTERIOR
 FINISHES PER NFPA 101. CURTAINS, DRAPES AND OTHER
 LOOSELY HANGING FINISHINGS/DECORATIONS SHALL MEET THE
 FLAME PROPAGATION CRITERIA OF NFPA 701 (MATERIAL WILL
 SELF EXTINGUISH ONCE DIRECT FIRE FLAME HAS BEEN
 REMOVED).
  
 SHEET A102 - COVERED PATIO #104: THE SOUTH EGRESS DOOR
 APPEARS TO BE COVERED OR ELIMINATED BY THE PATIO
 ENCLOSURE SYSTEM.
  
 SHEET A502: SHORT RUNS OF STEPS SHALL HAVE A TREAD
 DEPTH OF AT LEAST 13-INCHES. PROVIDE A CONTRASTING
 STRIPE ON EACH STEPPING SURFACE OF THE LEADING EDGE OR
 TREAD NOSING TO MAKE THE PRESENCE OF AN ELEVATION
 CHANGE READILY APPARENT TO OCCUPANTS.
  
 SHEET A701: COVERED PATIO #104 APPEARS TO HAVE A
 DIFFERENT SEATING PLAN THAN FROM WHAT WAS PREVIOUSLY
 APPROVED. AN EXIT DOOR APPEARS TO HAVE BEEN REMOVED AND
 THE EXIT PATH IS OBSTRUCTED BY TABLES AND CHAIRS.
  
 SHEET A708: IF THE SUSPENDED CEILING PANELS ARE LOCATED
 WITHIN 18" OF THE CEILING, FIRE SPRINKLER PROTECTION
 WILL BE NEEDED BELOW THE SUSPENDED CEILING PANELS.
 SPRINKLER OBSTRUCTIONS LOCATED WITHIN 18" BELOW THE
 SPRINKLER PREVENT THE SPRAY PATTERN FROM FULLY
 DEVELOPING.
  
 SHEET E2: NO ILLUMINATED EXIT SIGNS OR EMERGENCY
 LIGHTING PROVIDED FOR THE NEWLY ENCLOSED COVERED PATIO
 #104.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-08-29 Cont ID  
Sent By lwagner Date 2013-08-29 Time 15:14 Rev Time 0.00
Received By lwagner Date 2013-08-29 Time 14:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-06-24 Cont ID  
Sent By lwagner Date 2013-06-24 Time 10:59 Rev Time 0.00
Received By lwagner Date 2013-06-24 Time 10:51 Sent To  
Notes
2013-06-24 10:59:50SEPARATE APPLICATION AND PERMIT REQUIRED FOR FUEL GAS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-11 Cont ID  
Sent By rregueir Date 2013-09-11 Time 12:57 Rev Time 0.00
Received By rregueir Date 2013-08-20 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-02 Cont ID  
Sent By jwitmer Date 2013-07-02 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2013-05-14 Time 16:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-08-29 Cont ID  
Sent By rregueir Date 2013-08-29 Time 09:03 Rev Time 0.00
Received By rregueir Date 2013-08-29 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-06-26 Cont ID  
Sent By rregueir Date 2013-06-26 Time 13:32 Rev Time 0.00
Received By rregueir Date 2013-06-26 Time 13:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-08-29 Cont ID  
Sent By lwagner Date 2013-08-29 Time 15:14 Rev Time 0.00
Received By lwagner Date 2013-08-29 Time 14:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-24 Cont ID  
Sent By lwagner Date 2013-06-24 Time 10:58 Rev Time 0.00
Received By lwagner Date 2013-06-24 Time 10:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2013-09-09 Time   Rev Time 0.00
Received By rregueir Date 2013-09-09 Time 12:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-08-29 Cont ID  
Sent By eschneid Date 2013-08-29 Time 15:04 Rev Time 1.00
Received By eschneid Date 2013-08-29 Time 15:04 Sent To  
Notes
2013-08-29 15:05:38SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS.

Review Stop Z ZONING
Rev No 1 Status F Date 2013-06-25 Cont ID  
Sent By eschnide Date 2013-06-25 Time 22:37 Rev Time 2.00
Received By eschneid Date 2013-06-25 Time 22:37 Sent To  
Notes
2013-06-25 22:43:29FAILED
  
 1) THE CITYPLACE STAMP WAS NOT PROVIDED WITH THE
 REVISIONS.
  
 2) THE NEW COLORED WINDOW FILM SHOWN ON SHEET A201 IS
 NOT PERMITTED. IT SHALL REMAIN CLEAR GLAZING.
2013-06-24 18:04:406/25/13