Plan Review Stops For Permit 13050286 |
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2013-05-10 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2013-05-10 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2013-05-10 |
Time |
12:48 |
Sent To |
|
|
Notes |
2013-05-10 13:00:50 | ****PROVISO**** | | ELECTRICAL BONDING | | 310.1.1 CSST. | | CORRUGATED STAINLESS STEEL TUBING (CSST) GAS PIPING | | SYSTEMS SHALL BE BONDED TO THE ELECTRICAL SERVICE | | GROUNDING ELECTRODE SYSTEM AT THE POINT WHERE THE GAS | | SERVICE ENTERS THE BUILDING. THE BONDING JUMPER SHALL | | BE NOT SMALLER THAN 6 AWG COPPER WIRE OR EQUIVALENT. | | |
|
|