Plan Review Details - Permit 13050197
Plan Review Stops For Permit 13050197
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-06-06 Cont ID  
Sent By jgomez Date 2013-06-06 Time 12:09 Rev Time 0.00
Received By jgomez Date 2013-06-06 Time 12:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-04 Cont ID  
Sent By jgomez Date 2013-06-04 Time 13:39 Rev Time 0.00
Received By jgomez Date 2013-06-04 Time 13:39 Sent To  
Notes
2013-06-04 13:40:07BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE ENERGY CALCULATIONS. ACCORDING TO INFORMATION
 SUBMITTED AND WINDOW NOTE #2 FROM TABLE 402.A NEED TO
 USE FORM 405 TO COMPLY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-17 Cont ID  
Sent By jgomez Date 2013-05-17 Time 13:07 Rev Time 0.00
Received By jgomez Date 2013-05-17 Time 10:37 Sent To  
Notes
2013-05-17 13:31:59RESIDENTIAL (R3) RENOVATIONS, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS, INCLUDING WINDOW MULLIONS FOR BAY
 WINDOW IN DINING AREA.
  
 B) ROOF RIDGE VENT.
  
 C) FLAT ROOF. NOA 12-0227.18 SUBMITTED WAS SUPERSEDED
 BY MIAMI-DADE. VISIT THE MIAMI DADE WEBSITE AND
 DOWNLOAD CURRENT NOA.
 AND, PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 TO MEET THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 ***NOTE: IF NOA SUBMITTED REQUIRES RAS 117 CALCULATIONS
 TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By dharvey Date 2013-05-28 Time 08:48 Rev Time 0.00
Received By dharvey Date 2013-05-28 Time 08:48 Sent To  
Notes
2013-05-28 08:48:515-28-13
 CORRECTIONS MADE !
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-14 Cont ID  
Sent By dharvey Date 2013-05-14 Time 09:20 Rev Time 0.00
Received By dharvey Date 2013-05-14 Time 09:22 Sent To  
Notes
2013-05-14 09:29:585-14-13
  
 1. ALL ELECTRIC TO MEET 2008 NEC
 2. ALL NEW RECEPTS TO BE TAMPER RESISTANT PER NEC
 406.11
 3. SHOW "NEW" AND "EXISTING" DEVICES ON DRAWINGS
 4. INSTALL AFCI BREAKERS PER NEC 210.12B
 5. SMOKE ALARMS AS REQUIRED BY RBC 315 MUST HAVE CO
 PROTECTION AS WELL AS SMOKE.
 6. NEC TABLE 310.15 B6 SHOWS CONDUCTORS TO A 150A
 SERVICE TO BE #1, NOT #2
 VB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-04 Cont ID  
Sent By jgomez Date 2013-06-04 Time 15:45 Rev Time 0.00
Received By jgomez Date 2013-05-24 Time 11:43 Sent To  
Notes
2013-05-25 11:44:01GAVE TO VINNEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-17 Cont ID  
Sent By jgomez Date 2013-05-17 Time 13:40 Rev Time 0.00
Received By jgomez Date 2013-05-07 Time 14:52 Sent To  
Notes
2013-05-08 14:53:24SENT TO R14 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-17 Cont ID  
Sent By jgomez Date 2013-05-17 Time 12:31 Rev Time 0.00
Received By jgomez Date 2013-05-17 Time 12:31 Sent To  
Notes
2013-05-17 13:06:55MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE A/C CHANGE OUT FORM BEFORE
 INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-17 Cont ID  
Sent By jgomez Date 2013-05-17 Time 12:30 Rev Time 0.00
Received By jgomez Date 2013-05-17 Time 12:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-05-10 Cont ID  
Sent By ajones Date 2013-05-10 Time 10:30 Rev Time 0.00
Received By ajones Date 2013-05-10 Time 10:30 Sent To  
Notes
***NONE***