Plan Review Details - Permit 13050174
Plan Review Stops For Permit 13050174
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By jwitmer Date 2013-05-07 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2013-05-07 Time 07:32 Sent To Z
Notes
2013-05-07 12:11:29PROVISO:
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 A7 REQUIRES FINISH SLAB MINIMUM HEIGTH OF 12.5' NGVD
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-07 Cont ID  
Sent By jwitmer Date 2013-05-07 Time 11:44 Rev Time 0.00
Received By jwitmer Date 2013-05-06 Time 14:29 Sent To  
Notes
2013-05-06 14:33:30EXPEDITED
 GAVE TO JIM

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By jroach Date 2013-05-07 Time 10:10 Rev Time 0.00
Received By jroach Date 2013-05-07 Time 10:10 Sent To B
Notes
***NONE***