Plan Review Details - Permit 13050164
Plan Review Stops For Permit 13050164
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-06-13 Cont ID  
Sent By jwitmer Date 2013-06-13 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2013-06-13 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-06-06 Cont ID  
Sent By jwitmer Date 2013-06-06 Time 08:48 Rev Time 0.00
Received By jwitmer Date 2013-06-05 Time 07:30 Sent To  
Notes
2013-06-06 08:51:09BUILDING PLAN REVIEW
 PERMIT: 13050164
 ADD: 1801 S FLAGLER DR SUITE # PH-3
 CONT: PHILLIP E JOHNSON
 TEL: (561)262-1795
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JUNE 6 /2013
 ACTION: DENIED
 CALLED CONTRACTOR 5/04/13 NO RESPONCE
 CALLED CONTRACTOR 5/05/13 NO RESPONCE
  
  
 1) SHEET A-1 UNDER THE HEADING SITES CODE SECTION FOR
 BOTH FLOOR AND WALL INSULATION, RATHER THAN PROVIDING
 THE MANUFACTURERS SPEC ON THE MATERIAL TO BE INSTALLED
 ON THE FLOOR AS WELL AS WITHIN THE WALL CAVITIES FOR
 SOUND DEADENING. 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART...
  
 1A) 2ND REQUEST, FLOOR INSULATION, 2010 FBC-B 1207.3
 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B)2ND REQUEST, FLOOR TILE INSULATION/ FLAME SPREAD
 INDEX: 2010 FBC-B 603.1(2)(1) 1. INSULATION PLACED
 BETWEEN TWO LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT
 AN INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 100.
  
 1C) INFORMATIONAL, COMPLIED.
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-15 Cont ID  
Sent By jwitmer Date 2013-05-15 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2013-05-15 Time 07:33 Sent To  
Notes
2013-05-15 07:53:12BUILDING PLAN REVIEW
 PERMIT: 13050164
 ADD: 1801 S FLAGLER DR SUITE # PH-3
 CONT: PHILLIP E JOHNSON
 TEL: (561)262-1795
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 DATE:
 ACTION: DENIED
  
 1) SHEET A-1 UNDER THE HEADING SITES CODE SECTION FOR
 BOTH FLOOR AND WALL INSULATION, RATHER THAN PROVIDING
 THE MANUFACTURERS SPEC ON THE MATERIAL TO BE INSTALLED
 ON THE FLOOR AS WELL AS WITHIN THE WALL CAVITIES FOR
 SOUND DEADENING. 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART...
  
 1A) FLOOR INSULATION, 2010 FBC-B 1207.3 STRUCTURE-BORNE
 SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FLOOR TILE INSULATION/ FLAME SPREAD INDEX: 2010
 FBC-B 603.1(2)(1) 1. INSULATION PLACED BETWEEN TWO
 LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT AN
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 100.
  
 1C) WALL INSULATION, 2010 FBC-B 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-04 Cont ID  
Sent By dharvey Date 2013-06-04 Time 16:40 Rev Time 0.00
Received By dharvey Date 2013-06-04 Time 16:40 Sent To  
Notes
2013-06-04 16:40:336-4-13
 CORRECTIONS MADE
 \VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-17 Cont ID  
Sent By dharvey Date 2013-05-17 Time 14:14 Rev Time 0.00
Received By dharvey Date 2013-05-17 Time 14:14 Sent To  
Notes
2013-05-17 14:37:095-17-13
  
 PROVIDE PANEL SCHEDULE - NEC 408.4A
 PROVIDE LOAD CALCS INCLUDING ALL NEW AND EXISTING LOADS
 - NEC 220
 ADD FEEDER RISER DIAGRAM - NEC 215.5
 ALL RECEPTACLES TO BE TAMPER RESISTANT - NEC 406.11
 ALL REQUIRED RECEPTS TO BE AFCI PROTECTED - NEC 210.12B
 BALCONY RECEPTS TO BE GFCI - NEC 210.8.A.3
 ALL WORK TO COMPLY WITH 2008 NEC
 SHOW CIRCUIT NUMBERS ON FLOOR PLAN
 MULTIWIRE CIRCUITS SHALL MEET NEC 210.4
 USE DEEP BOXES FOR 3 OR MORE CABLE ENTRIES TO ENSURE
 REQUIRED BOX FILL MINIMUM NEC 314.16
 VB
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By wjolin Date 2013-05-07 Time 13:11 Rev Time 0.00
Received By wjolin Date 2013-05-07 Time 13:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-06-13 Cont ID  
Sent By jwitmer Date 2013-06-13 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2013-06-11 Time 11:27 Sent To  
Notes
2013-06-12 11:28:05SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-12 Cont ID  
Sent By jgomez Date 2013-06-06 Time 11:25 Rev Time 0.00
Received By jgomez Date 2013-06-03 Time 15:54 Sent To  
Notes
2013-06-12 11:25:43LAST REVIEW DONE ON 6/6/13. JG.
2013-06-04 15:55:30GAVE TO VINNEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-21 Cont ID  
Sent By dharvey Date 2013-05-21 Time 13:34 Rev Time 0.00
Received By dharvey Date 2013-05-21 Time 13:34 Sent To  
Notes
2013-05-06 16:21:38INCOMING SENT TO B-04 BOX. JW

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-05-08 Cont ID  
Sent By lwagner Date 2013-05-08 Time 11:08 Rev Time 0.00
Received By lwagner Date 2013-05-08 Time 10:53 Sent To  
Notes
2013-05-08 11:08:14NO PLUMBING WORK IS SHOWN ON PLAN. A PLUMBING PERMIT
 WILL BE REQUIRED IF MORE WORK IS REQUIRED OTHER THAN
 FBC 2010 105.2 PLUMBING:
 3. THE REPLACEMENT OF COMMON HOUSEHOLD PLUMBING
 FIXTURES TO EXISTING SUPPLY LINES AND OUTLETS.
 THIS DOES NOT INCLUDE WATER HEATERS.