Plan Review Details - Permit 13050163
Plan Review Stops For Permit 13050163
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-09 Cont ID  
Sent By jwitmer Date 2013-05-09 Time 13:03 Rev Time 0.00
Received By jwitmer Date 2013-05-09 Time 12:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-13 Cont ID  
Sent By dharvey Date 2013-05-13 Time 16:21 Rev Time 0.00
Received By dharvey Date 2013-05-13 Time 16:21 Sent To  
Notes
2013-05-13 16:22:575-13-13
 PLEASE INSTALL WARNING LABEL PER N.E.C. 110.16 TO WARN
 OF ELECTRICAL HAZARDS..
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By wjolin Date 2013-05-07 Time 11:30 Rev Time 0.00
Received By wjolin Date 2013-05-07 Time 10:34 Sent To  
Notes
2013-05-07 11:16:414512 NORTH FLAGLER DRIVE - SUITE #201
 PERMIT #13050163
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-1.0: CONFERENCE ROOM #102 IS AN ASSEMBLY USE
 CALCULATED AT 15 SQ.FT. PER PERSON RESULTING IN AN
 OCCUPANT LOAD OF 18 PERSONS. PER SECTION 7.2.1.4.1, ANY
 DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE
 SIDE-HINGED OR PIVOTED SWINGING TYPE, AND SHALL BE
 INSTALLED TO BE CAPABLE OF SWINGING FROM ANY POSITION
 TO THE FULL REQUIRED WIDTH OF THE OPENING IN WHICH IT
 IS INSTALLED. BUSINESS AREAS WITH AN OCCUPANT LOAD NOT
 EXCEEDING 10 PERMITS HORIZONTAL-SLIDING DOOR
 ASSEMBLIES.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-13 Cont ID  
Sent By dharvey Date 2013-05-13 Time 16:23 Rev Time 0.00
Received By dharvey Date 2013-05-13 Time 16:23 Sent To  
Notes
2013-05-06 14:08:41EXPEDITED
 B--3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By hmoser Date 2013-05-07 Time 16:46 Rev Time 0.00
Received By hmoser Date 2013-05-07 Time 15:55 Sent To  
Notes
2013-05-07 16:46:09PASS PROVISO
 REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROL.
 FOR FRESH AIR AND EXHAUST. 2010 FLORIDA ENERGY CODE
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-08 Cont ID  
Sent By lwagner Date 2013-05-08 Time 10:52 Rev Time 0.00
Received By lwagner Date 2013-05-08 Time 10:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-05-10 Cont ID  
Sent By ajones Date 2013-05-10 Time 10:27 Rev Time 0.00
Received By ajones Date 2013-05-10 Time 10:27 Sent To  
Notes
***NONE***