Plan Review Details - Permit 13050152
Plan Review Stops For Permit 13050152
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-05 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 13:48 Rev Time 0.00
Received By jwitmer Date 2013-07-05 Time 13:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-15 Cont ID  
Sent By jwitmer Date 2013-05-15 Time 14:07 Rev Time 0.00
Received By jwitmer Date 2013-05-15 Time 13:47 Sent To  
Notes
2013-05-15 14:17:39BUILDING PLAN REVIEW
 PERMIT: 13050152
 ADD: 101 N CLEMATIS ST SUITE # 100
 CONT: TBD
 TEL: (813)833-3128
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MAY 15/ 2013
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED, THE PERMIT
 APPLICATION INDICATES THE RENOVATION IS TO BE A DISPLAY
 KITCHEN, IS THIS A WORKING KITCHEN WHERE FOOD WILL BE
 COOKED?
 THE BAR EXTENSION EXTENSION IS INDICATED TO BE 3'-6"
 TALL, PLEASE PROVIDE COMPLIANCE FOR 2010 FL
 ACCESSIBILITY CODE FOR EITHER 902.4.2 HEIGHT OR
 904.5.2, THE PLANS ARE NOT CLEAR IF THE BAR EXTENSION
 WILL BE USED BY THE STAFF OR IF IT WILL BE USED BY THE
 PATRONS? PLEASE REVIEW 226.2 DISPERSION PROVIDE CODE
 COMPLIANCE.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By dharvey Date 2013-07-02 Time 11:32 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 11:20 Sent To  
Notes
2013-07-02 11:33:10BY RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 16:00 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 16:00 Sent To  
Notes
2013-05-06 16:03:185-06-13
 1. PROVIDE ENGINEERED DRAWING FOR CEILING MOUNTER 30KVA
 TRANSFORMER
 2. PROVIDE PANEL SCHEDULE FOR MSB. SHOW AIC AND FAUILT
 CURRENT NEC 110.9 & 110.10
 3. IS PANEL SCHEDULED SHOWN ON E4 "K" OR "K2"? PLEASE
 SHOW BOTH SCHEDULES. NEC 408.4
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-20 Cont ID  
Sent By wjolin Date 2013-06-20 Time 15:18 Rev Time 0.00
Received By wjolin Date 2013-06-20 Time 15:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-05-16 Cont ID  
Sent By wjolin Date 2013-05-16 Time 13:34 Rev Time 0.00
Received By wjolin Date 2013-05-16 Time 13:18 Sent To  
Notes
2013-05-16 13:29:00101 NORTH CLEMATIS STREET - #100
 PERMIT #13050152
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SUBMIT PRODUCT DATA FOR FUTURE VENTLESS FRYER COMPLYING
 WITH FBCM 507.1(#2); OTHERWISE THE FOLLOWING WILL BE
 REQUIRED:
  
 DEEP FAT FRYER: COOKING OPERATIONS PRODUCING SMOKE OR
 GREASE-LADEN VAPORS SHALL BE PROTECTED WITH A CLASS I
 MECHANICAL EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC
 WET-CHEMICAL FIRE SUPPRESSION SYSTEM.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL BE
 LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
  
 PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-05 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 13:48 Rev Time 0.00
Received By jwitmer Date 2013-06-12 Time 14:17 Sent To  
Notes
2013-06-14 14:18:29B24
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 14:29 Rev Time 0.00
Received By hmoser Date 2013-05-06 Time 11:30 Sent To  
Notes
2013-05-07 10:07:05TO B13
2013-05-06 11:31:02INCOMING SENT TO B-03 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 14:29 Rev Time 0.00
Received By hmoser Date 2013-05-28 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-08 Cont ID  
Sent By lwagner Date 2013-05-08 Time 13:09 Rev Time 0.00
Received By lwagner Date 2013-05-08 Time 11:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-22 Cont ID  
Sent By aaponte Date 2013-05-22 Time 10:27 Rev Time 0.00
Received By aaponte Date 2013-05-22 Time 10:27 Sent To  
Notes
2013-05-22 10:27:51INTERIOR IMPROVEMENTS FOR NEW DISPLAY KITCHEN.