Plan Review Details - Permit 13050105
Plan Review Stops For Permit 13050105
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-10 Cont ID  
Sent By jwitmer Date 2013-07-10 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2013-07-10 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-08 Cont ID  
Sent By jwitmer Date 2013-05-08 Time 17:01 Rev Time 0.00
Received By jwitmer Date 2013-05-08 Time 15:40 Sent To  
Notes
2013-05-08 17:00:26BUILDING PLAN REVIEW
 PERMIT: 13050105
 ADD: 701 NORTHPOINT PKY # 400
 CONT: KAST CONSTRUCTION
 TEL: (561)689-2910
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/08/2013
 ACTION: DENIED
  
 1) SHEET A2 & A3 INDICATE THE USE OF SLIDING OR POCKET
 DOORS AS A PART OF A MEANS OF EGRESS. 2010 FBC-B 1008.1
 REQUIRES PIVOT OR SIDE SWINGING DOORS, PLEASE REVIEW
 EXCEPTION # 1 WHICH WILL ALLOW A SLIDING DOOR WHERE THE
 OCCUPANT LOAD IS LESS THAN 10.
  
 2) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.
  
 3) SHEET A-3 INDICATES A NEW BREAK ROOM WITH SINK, NO
 DETAILS WERE PROVIDED INDICATING COMPLIANCE WITH 2010
 FL ACCESSIBILITY CODE
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By dharvey Date 2013-07-02 Time 12:09 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 12:10 Sent To  
Notes
2013-07-02 12:10:06RESTAMP BY RL

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-15 Cont ID  
Sent By dharvey Date 2013-05-15 Time 15:15 Rev Time 0.00
Received By dharvey Date 2013-05-15 Time 15:15 Sent To  
Notes
2013-05-15 15:16:115-15-13
 APPROVED WITH EXCEPTION PER NOTES ON PLANS
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-21 Cont ID  
Sent By wjolin Date 2013-06-21 Time 14:25 Rev Time 0.00
Received By wjolin Date 2013-06-21 Time 14:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-05-07 Cont ID  
Sent By wjolin Date 2013-05-07 Time 14:10 Rev Time 0.00
Received By wjolin Date 2013-05-07 Time 13:20 Sent To  
Notes
2013-05-07 14:10:04701 NORTHPOINT PARKWAY - SUITE #400
 PERMIT #13050105
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, ?FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.?
  
 GENERAL: PER NFPA 101 SECTION 8.3.2.4, EACH FIRE
 BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS.
 CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND
 HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT
 MORE THAN 15 FEET ON CENTER.
  
 SHEET C1: THE BUSINESS OCCUPANCY LOAD CALCULATION
 INDICATES AN OCCUPANT LOAD OF 68 PERSONS; HOWEVER,
 THERE ARE THREE OR FOUR ROOMS THAT ARE ASSEMBLY USE
 AREAS THAT SHOULD BE CALCULATED USING AN OCCUPANT LOAD
 FACTOR OF 7 SQ.FT. OR 15 SQ.FT. PER PERSON.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A2/A3: THE ASSEMBLY USE AREAS (CAFE, CONFERENCE
 ROOM, BOARDROOM AND MULTIPURPOSE ROOM) EXCEED 10% OF
 THE TENANT SPACE TO BE CONSIDERED ACCESSORY TO THE
 BUSINESS OCCUPANCY.
  
 SHEET A2/A3: CONFERENCE ROOM AND CAFE ROOM HAVE SLIDING
 DOORS. PER NFPA 101 SECTION 7.2.1.4.1, ANY DOOR
 ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE
 SIDE-HINGED OR PIVOTED SWINGING TYPE, AND SHALL BE
 INSTALLED TO BE CAPABLE OF SWINGING FROM ANY POSITION
 TO THE FULL REQUIRED WIDTH OF THE OPENING IN WHICH IT
 IS INSTALLED, UNLESS OTHERWISE SPECIFIED AS
 FOLLOWS:WHERE PRIVATE GARAGES, BUSINESS AREAS,
 INDUSTRIAL AREAS, AND STORAGE AREAS WITH AN OCCUPANT
 LOAD NOT EXCEEDING 10 CONTAIN ONLY LOW OR ORDINARY
 HAZARD CONTENTS, DOOR OPENINGS TO SUCH AREAS AND
 PRIVATE GARAGES SHALL BE PERMITTED TO BE
 HORIZONTAL-SLIDING DOOR ASSEMBLIES.
  
 SHEET A3: FLEX STATION DOOR SWINGS OUT INTO THE
 CORRIDOR VERY NEAR THE ADJACENT TENANT'S CORRIDOR DOOR
 AND COULD CAUSE EGRESS DELAYS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE A FURNITURE PLAN.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS. AFTER THE BUILDING
 PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN THEN
 SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-10 Cont ID  
Sent By jwitmer Date 2013-07-10 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2013-06-04 Time 10:27 Sent To  
Notes
2013-06-05 10:51:47INCOMING SENT TO C-13 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 13:37 Rev Time 0.00
Received By hmoser Date 2013-05-03 Time 08:51 Sent To  
Notes
2013-05-06 08:58:53B--17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-07-10 Cont ID  
Sent By jwitmer Date 2013-07-10 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2013-07-10 Time 13:47 Sent To  
Notes
2013-07-10 13:49:53MECHANICAL APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 M2.1 DETAIL 2 CONTRACTOR TO PROVIDE A/C STAND PRODUCT
 APPROVAL AND METHOD OF ATTACHMENT TO ROOF DECK BY FIRST
 INSPECTION.
 2010 FBC-M 301.12 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. ROOF-MOUNTED MECHANICAL UNITS
 AND SUPPORTS SHALL BE SECURED TO THE STRUCTURE. THE USE
 OF WOOD ?SLEEPERS? SHALL NOT BE PERMITTED.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (G) PRE-ENGINEERED A/C STANDS
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 13:35 Rev Time 0.00
Received By hmoser Date 2013-05-28 Time 13:17 Sent To  
Notes
2013-05-28 13:34:19PROVIDE A DETAIL FROM THE ENGINEER ON THE CONDENSER
 STAND TIE DOWN TO ROOF (BOLT SIZE) AT FIRST INSPECTION
 PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-07 Cont ID  
Sent By lwagner Date 2013-06-07 Time 10:56 Rev Time 0.00
Received By lwagner Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-09 Cont ID  
Sent By lwagner Date 2013-05-09 Time 12:44 Rev Time 0.00
Received By lwagner Date 2013-05-09 Time 10:22 Sent To  
Notes
2013-05-09 12:45:43SINK TOP TO BE 34" MAX A.F.F.