Plan Review Details - Permit 13050004
Plan Review Stops For Permit 13050004
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-06-20 Cont ID  
Sent By jwitmer Date 2013-06-20 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2013-06-20 Time 16:46 Sent To  
Notes
2013-06-20 16:50:31BUILDING PLAN REVIEW
 PERMIT: 13050004
 ADD: 1701 S FLAGLER # 1502
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 DATE: JUNE 20/2013
 ACTION:BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) TILE, MARBLE FLOORS OR SIMILAR MATERIALS, 2010 FBC-B
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.
  
 2) 2010 FBC-B 603.2EXCEPTION # 1. INSULATION PLACED
 BETWEEN TWO LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT
 AN INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 100.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-06-11 Cont ID  
Sent By jwitmer Date 2013-06-11 Time 07:54 Rev Time 0.00
Received By jwitmer Date 2013-06-11 Time 07:01 Sent To  
Notes
2013-06-11 07:59:46BUILDING PLAN REVIEW
 PERMIT: 13050004
 ADD: 1701 S FLAGLER # 1502
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JUNE 11/2013
 ACTION: DENIED
  
 1) SEMI-COMPLIED. ENGINEERING EXPRESS HAS PROVIDED WIND
 DESIGN FOR HIGH RISE, FOR AN EXPOSURE D, THE END ZONE
 IS LABELED 3'-0". THIS UNIT WHICH IS AN END UNIT HAS
 ANOTHER UNIT BEHIND IT THE LEAST HORIZONTAL DIMENSION
 OF UNIT WHEN DOUBLED IS 68 FEET WIDE, 10 % OF THE LEAST
 DIMENSION WOULD BE 6'-8" (END ZONE), WINDOW MARK # 4
 WOULD BE LOCATED IN A END ZONE WITH HIGHER PRESSURES.
  
  
 2) 2ND REQUEST, 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SLIDERS AND SWING DOOR OK.
 (B) WINDOWS PLEASE CIRCLE TYPE OF GLASS TO BE ORDERED,
 NOTE ONLY ONE WILL WORK!!!!!!
 (B) MULLIONS PLEASE CIRCLE TYPE OF ANCHOR TO BE
 INSTALLED, NOTE TABLE 7 OF 22 THE FORMULA SHOWN ON THIS
 SHEET HAS TO BE COMPLETED TO COMPLETED TO CONVERT TO
 PRESSURES FOR BOTH THE MULLION AND FASTENERS.
  
 4A) COMPLIED. TILE MARBLE FLOORS OR SIMILAR MATERIALS,
 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 4B) 2ND REQUEST, PROTECTO WRAP. SPEC SHEET HAS NO DATA
 ON FLAME SPEAD. TILE MARBLE OR SIMILAR MATERIALS: 2010
 FBC-B 603.2EXCEPTION # 1. INSULATION PLACED BETWEEN TWO
 LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT AN
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 100.
  
 5-6) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-02 Cont ID  
Sent By jwitmer Date 2013-05-02 Time 12:58 Rev Time 0.00
Received By jwitmer Date 2013-05-02 Time 12:32 Sent To  
Notes
2013-05-02 12:51:52BUILDING PLAN REVIEW
 PERMIT: 13050004
 ADD: 1701 S FLAGLER # 1502
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MAY 02/2013
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES UNDER THE HEADING
 OF SCOPE OF WORK " REMOVAL AND REPLACE SLIDING GLASS
 DOORS & WINDOWS. THE PLANS DO NOT INDICATE THE
 REPLACEMENT OF EXTERIOR WINDOWS OR SLIDING GLASS DOORS.
 NO MENTION OF THE EXTERIOR SWING DOOR BEING REPLACED.
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS & MULLIONS
  
 4) THE PLANS INDICATE THE INTERIOR WALLS ARE BEING
 MOVED, NO MENTION OF FLOORING REPLACEMENT. IF FLOORING
 REPLACEMENT IS BEING TAKEN UNDER THIS PERMIT, PLEASE
 NOTE ON PLAN, AND COMPLY WITH:
 4A) TILE MARBLE FLOORS OR SIMILAR MATERIALS, 2010 FBC-B
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.
  
 4B) TILE MARBLE OR SIMILAR MATERIALS: 2010 FBC-B
 603.2EXCEPTION # 1. NSULATION PLACED BETWEEN TWO LAYERS
 OF NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 5) PLANS INDICATE WORK TO BE COMPLETED ON INTERIOR
 COMMON WALLS AND WILL NEED TO COMPLY WITH:
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 6) PLANS INDICATE WALLS TO BE REWORKED IN THE BATHROOM,
 2010 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
  
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
  
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-13 Cont ID  
Sent By dharvey Date 2013-06-13 Time 15:13 Rev Time 0.00
Received By dharvey Date 2013-06-13 Time 15:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-03 Time 13:19 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 13:18 Sent To  
Notes
2013-05-03 13:23:281. PROVIDE SMOKE ALARMS PER R-314.3.1
 2. COMPLY WITH NEC 210.12B FOR ALL OUTLETS TO BE AFCI
 3. PROVIDE TAMPER RESISTANT RECPTS FOR ALL REQUIRED
 OUTLETS PER NEC 406.11
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-06 Cont ID  
Sent By wjolin Date 2013-05-06 Time 14:55 Rev Time 0.00
Received By wjolin Date 2013-05-06 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-06-20 Cont ID  
Sent By jwitmer Date 2013-06-20 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2013-06-20 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2013-06-13 Cont ID  
Sent By jwitmer Date 2013-06-13 Time 16:45 Rev Time 0.00
Received By jwitmer Date 2013-06-10 Time 12:54 Sent To  
Notes
2013-06-10 12:54:31INCOMING SENT TO JW DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-24 Cont ID  
Sent By lmartine Date 2013-05-09 Time 12:06 Rev Time 0.00
Received By lmartine Date 2013-05-01 Time 17:21 Sent To  
Notes
2013-05-01 17:21:17EXPEDITED
 B--10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-09 Cont ID  
Sent By hmoser Date 2013-05-09 Time 12:58 Rev Time 0.00
Received By hmoser Date 2013-05-08 Time 15:45 Sent To  
Notes
2013-05-09 12:58:46PASS PROVISO
 REFER TO SECTION 601.4 BALANCED RETURN AIR
 2010 FBC (M) .
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By lwagner Date 2013-05-07 Time 13:47 Rev Time 0.00
Received By lwagner Date 2013-05-07 Time 13:16 Sent To  
Notes
***NONE***