2013-05-02 12:51:52 | BUILDING PLAN REVIEW |
| PERMIT: 13050004 |
| ADD: 1701 S FLAGLER # 1502 |
| CONT: MARYJULI CONSTRUCTION |
| TEL: (561)386-6032 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MAY 02/2013 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES UNDER THE HEADING |
| OF SCOPE OF WORK " REMOVAL AND REPLACE SLIDING GLASS |
| DOORS & WINDOWS. THE PLANS DO NOT INDICATE THE |
| REPLACEMENT OF EXTERIOR WINDOWS OR SLIDING GLASS DOORS. |
| NO MENTION OF THE EXTERIOR SWING DOOR BEING REPLACED. |
| |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| |
| 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| |
| 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| |
| 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| |
| 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| TABLE 1609.2(2) . |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS & MULLIONS |
| |
| 4) THE PLANS INDICATE THE INTERIOR WALLS ARE BEING |
| MOVED, NO MENTION OF FLOORING REPLACEMENT. IF FLOORING |
| REPLACEMENT IS BEING TAKEN UNDER THIS PERMIT, PLEASE |
| NOTE ON PLAN, AND COMPLY WITH: |
| 4A) TILE MARBLE FLOORS OR SIMILAR MATERIALS, 2010 FBC-B |
| 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES |
| BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A |
| PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE |
| AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| WITH ASTM E 492. |
| |
| 4B) TILE MARBLE OR SIMILAR MATERIALS: 2010 FBC-B |
| 603.2EXCEPTION # 1. NSULATION PLACED BETWEEN TWO LAYERS |
| OF NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| |
| 5) PLANS INDICATE WORK TO BE COMPLETED ON INTERIOR |
| COMMON WALLS AND WILL NEED TO COMPLY WITH: |
| 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 6) PLANS INDICATE WALLS TO BE REWORKED IN THE BATHROOM, |
| 2010 2509.2 BASE FOR TILE. |
| GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| |
| 2509.3 LIMITATIONS. |
| WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED |
| IN THE FOLLOWING LOCATIONS: |
| |
| 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| COMPARTMENTS. |
| |
| 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| |
| 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |