Plan Review Details - Permit 13041140
Plan Review Stops For Permit 13041140
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-15 Cont ID  
Sent By JWITMER Date 2013-06-15 Time 13:06 Rev Time 0.00
Received By jwitmer Date 2013-06-15 Time 12:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-02 Cont ID  
Sent By jwitmer Date 2013-05-02 Time 14:35 Rev Time 0.00
Received By jwitmer Date 2013-05-15 Time 13:19 Sent To  
Notes
2013-05-02 15:22:42BUILDING PLAN REVIEW
 PERMIT: 13041140
 ADD: 400 CLEMATIS ST SUITE # 101
 CONT: JOE SCHMIDT CONSTRUCTION INC.
 TEL: (561)248-8860
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/02/ 2013
 ACTION: DENIED
  
 1) THE SUBMITTED PLAN DOES NOT CLEARLY STATE WHERE WORK
 IS GOING TO BE ACCOMPLISHED UNDER THIS PERMIT. THE NEW
 CAMP ULTIMA IS A CHANGE OF OCCUPANCYTHE LAST KNOWN
 OCCUPANCY IN THIS SPACE WAS A RESTARAUNT, IF OCCUPANT
 LOAD UNDER 50 THEN CONSIDERED MERCANTILE IF OVER 50
 THEN IT WOULD OF BEEN CONSIDERED A2 ASSEMBLY
 RESTARAUNT. THE NEW OCCUPANCY IS TO BE A GYM WHICH IS A
 A3 OCCUPANCY. 2010 FLORIDA EXISTING BUILDING CODE
 SECTION 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY.
  
 2) 912.1.2 FIRE PROTECTION AND INTERIOR FINISH.
 THE PROVISIONS OF SECTIONS 912.2 AND 912.3 FOR FIRE
 PROTECTION AND INTERIOR FINISH, RESPECTIVELY, SHALL
 APPLY TO ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 912.2.2 FIRE ALARM AND DETECTION SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
 PLANS DO NOT INDICATE IF THERE IS A FIRE SPRINKLER
 SYSTEM WITHIN THIS BUILDING.
  
 912.3 INTERIOR FINISH.
 IN AREAS OF THE BUILDING UNDERGOING THE CHANGE OF
 OCCUPANCY CLASSIFICATION, THE INTERIOR FINISH OF WALLS
 AND CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION.
  
 3) 912.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.8. 912.8
 ACCESSIBILITY. EXISTING BUILDINGS THAT UNDERGO A CHANGE
 OF GROUP OR OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
  
 3A) 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING. THE NEW
 RECEPTIONIST COUNTER DOES NOT COMPLY WITH 2010 FL
 ACCESSIBILITY CODE
 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK
 WRITING SURFACES SHALL COMPLY WITH 902.3. 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3B) 2010 FL ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 PLEASE PROVIDE A ITEMIXED LIST WHERE AN ADDITIONAL
 $18,000.00 DOLLARS WILL BE SPENT IN ACCESSIBILITY
 UPGRADES TO THE ALTERED WORK AREAS. NOTE IF THE
 ACCESSIBLE ENTRANCE AND AND ACCESSIBLE ROUTE TO ALTERED
 AREAS DO NOT NEED ACCESSIBILITY UPDATES THEN THE
 RESTROOMS IN THE NEWLY CHANGED OCCUPANCY WOULD NEED TO
 SPEND AN ADDITIONAL $18,000.00 IN ACCESSIBILITY
 UPGRADES.
  
 4) PLEASE PROVIDE STRUCTURAL DETAILS HOW THE PROPOSED
 NEW DOORWAY WILL OCCUR STRUCTURALLY ? 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 5) PLEASE PROVIDE A LIFE SAFETY PLAN AND OCCUPANT COUNT
 FOR THE VARIOUS AREAS OF THE TENANT SPACE PLEASE USE
 TABLE 1004.1.1 FBC-B TO FIGURE WHAT THE TOTAL OCCUPANT
 LOAD WILL BE ?
  
 6) THE PLANS DO NOT INDICATE ANY EXIT LIGHTS,
 DIRECTIONALS NOR EMERGENCY LIGHTING FOR THIS TENANT
 2010 FBC-B 1006.3 EXIT SIGNS & 1006.1.6.2 SOURCES OF
 ILLUMINATION, BATTERY BACK UP?
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
 6)
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-12 Cont ID  
Sent By DHARVEY Date 2013-06-12 Time 14:00 Rev Time 0.00
Received By dharvey Date 2013-06-12 Time 14:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-15 Cont ID  
Sent By dharvey Date 2013-05-15 Time 13:20 Rev Time 0.00
Received By dharvey Date 2013-05-15 Time 13:20 Sent To  
Notes
2013-05-15 13:23:015-15-13
  
 1. PROVIDE PANEL SCHEDULE WITH UPDATED DIRECTORY
 SHOWING NEW WORK
 2. GFCI RECEPTACLE REQUIRED FOR DRINKING FOUNTAIN
 3. SHOW CIRCUIT NUMBERS ON FLOOR PLAN FOR AREAS OF NEW
 WORK
 4. SHOW "EXISTING TO LOCAL CIRCUITS" OR "NEW" CIRCUITS
 FOR RECEPTION AND SOFFIT LIGHTING AREAS
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-14 Cont ID  
Sent By WJOLIN Date 2013-06-14 Time 09:28 Rev Time 0.00
Received By wjolin Date 2013-06-14 Time 09:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-05-04 Cont ID  
Sent By wjolin Date 2013-05-04 Time 08:54 Rev Time 0.00
Received By wjolin Date 2013-04-30 Time 14:34 Sent To  
Notes
2013-05-04 08:54:25400 CLEMATIS STREET - SUITE #101
 PERMIT #13041140
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PARTIAL CHANGE OF OCCUPANCY FROM MERCANTILE
 (RESTAURANT) TO ASSEMBLY*****
  
 THE PERMIT APPLICATION INCORRECTLY INDICATES THE
 ADDRESS AS "NORTH" CLEMATIS STREET.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING OCCUPANT LOADS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1-1/2 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS
 TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES
 ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE.
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 NOTE: SEPARATE PLANS AND SUB-PERMITS ARE REQUIRED FOR
 THE MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-15 Cont ID  
Sent By jwitmer Date 2013-06-15 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2013-06-03 Time 08:43 Sent To  
Notes
2013-06-11 16:50:47*EXPEDITED*, REQUESTED 6/11/13
2013-06-04 08:50:13B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-17 Cont ID  
Sent By hmoser Date 2013-05-17 Time 09:22 Rev Time 0.00
Received By hmoser Date 2013-04-29 Time 09:28 Sent To  
Notes
2013-04-30 09:29:38B20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2013-06-15 Cont ID  
Sent By HMOSER Date 2013-06-15 Time 13:06 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2013-06-15 13:07:28NO MECHANICAL PLANS WERE SUBMITTED. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-17 Cont ID  
Sent By hmoser Date 2013-05-17 Time 09:22 Rev Time 0.00
Received By hmoser Date 2013-05-17 Time 09:13 Sent To  
Notes
2013-05-17 09:22:01NO MECHANICAL PLANS SUBMITTED.
 HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-05 Cont ID  
Sent By LWAGNER Date 2013-06-05 Time 14:26 Rev Time 0.00
Received By lwagner Date 2013-06-05 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By lwagner Date 2013-05-06 Time 12:42 Rev Time 0.00
Received By lwagner Date 2013-05-06 Time 10:24 Sent To  
Notes
2013-05-06 12:41:30FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 PENDING :
  
 PLEASE SEE BUILDING REVIEW COMMENTS ON ACCESSIBILITY.
  
 ***NOTE***
 TWO DRINKING FOUNTAINS ARE SHOWN AS EXISTING. IF THESE
 ARE SET AT WHEELCHAIR HEIGHT, THE NEW DRINKING FOUNTAIN
 SHOULD BE A HI/LO DRINKING FOUNTAIN PER ACCESSIBILITY
 211.2 OR A SINGLE FOUNTAIN SET AT A HEIGHT TO COMPLY
 WITH ACCESSIBILITY 602.7
  
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-10 Cont ID  
Sent By aaponte Date 2013-05-10 Time 09:25 Rev Time 0.00
Received By aaponte Date 2013-05-10 Time 09:25 Sent To  
Notes
2013-05-10 09:26:31INTERIOR RENOVATION. CAFE ALONG DIXIE CONVERTED INTO"
 CAMP ULTIMA"
2013-05-03 15:38:275/3/13