Plan Review Stops For Permit 13041131 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-06-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-06-13 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-06-13 |
Time |
10:58 |
Sent To |
|
|
Notes |
2013-06-13 11:26:39 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1- REVISE THE ENERGY CALCULATIONS: A) ITEM #15 IS | | TAKING THE "CV" CREDIT. PLANS NEED TO SHOW COMPLIANCE. | | B) BUILDING ORIENTATION NEEDS TO MATCH SURVEY. C) | | COMPLETE ALL THE INFORMATION ON TOP OF FORM. | | | | 2- PROVIDE PRODUCT APPROVAL FOR STORAGE BARN TYPE DOORS | | AS SHOWN ON PLANS. AND, ENGINEER OF RECORD TO | | REVIEW/APPROVE IT BEFORE SUBMITTAL. | | | | 3- REVISE ALL ROOF SHEATHING SPECIFICATIONS SHOWN ON | | ALL NOTES AND DETAILS. PROVIDE COMPLETE ENGINEERING | | ANALYSIS FOR ALT. METHOD SPECIFIED ON THE LAST SENTENCE | | OF SPECIFICATIONS OR DELETE THE ALT. METHOD. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-05-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-14 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-14 |
Time |
16:37 |
Sent To |
|
|
Notes |
2013-05-14 17:33:34 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- REVISE THE ENERGY CALCULATIONS: | | A) ITEM #9: ACCORDING TO PLANS THERE IS ONLY ONE 2X6 | | WALL WITH R19 INSULATION. OTHER WALLS ARE 2X4 WITH R11 | | INSULATION. REVISE TOTAL WALL AREA FOR EACH WALL TYPE | | TO MATCH PLANS. | | | | B) ITEM #15 IS TAKING THE "CF" AND "CV" CREDITS. | | PROVIDE COMPLETE SPECIFICATIONS ON PLANS SHOWING | | COMPLIANCE WITH THE "CV" CREDIT. SEC. 405.6.4 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | C) THERE IS NOT KITCHEN ON THIS ADDITION. REVISE PAGE | | 2. | | | | D) REVISE ROOF TYPE AND MATERIAL ON PAGE 2 TO MATCH | | PLANS. | | | | E) REVISE OVERHANG DEPTH AND SEPARATION ON PAGE 3 TO | | MATCH PLANS. NOTE, CONSIDER THE GABLE END WALL. ALSO, | | THERE IS MORE THAN 6" OVERHANG SEPARATION. | | | | F) COMPLETE ALL THE INFORMATION ON TOP OF FORM. BUILDER | | NAME, ETC. | | | | 2- PROVIDE SITE PLAN SHOWING LOCATION AND ORIENTATION | | OF PROPOSED STRUCTURE. SEC. 107.3.5.3 CITY AMENDMENTS | | TO FBC. | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: | | A) STORAGE DOUBLE DOORS AS SHOWN ON FRONT ELEVATION. | | | | B) ROOF SHINGLES. | | | | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY | | AMENDMENTS. | | | | 5- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. REQUIRED | | BY PALM BEACH COUNTY FOR THE RECORDS RETENTION. | | | | 6- SHEET A-1: A) REVISE THE BUILDING CATEGORY AND | | ALTERATION LEVEL SPECIFIED ON DESIGN PARAMETERS. THIS | | IS TYPE "VB" NOT "II" AND IS AN ADDITION. GARAGE IS | | DEMOLISHED AND NEW HABITABLE BUILDING IS CONSTRUCTED. | | THEREFORE, SEC. 407 OF 2010-FBC-EXISTING BUILDING | | APPLIES. | | | | B) REVISE GENERAL NOTES AS WELL TO REFLECT ITEM #5(A) | | ABOVE. | | | | 7- A) REVISE ALL ROOF SHEATHING SPECIFICATIONS SHOWN ON | | DETAILS, WALL SECTIONS AND ROOF FRAMING NOTES. ROOF | | ZONE #3 NEED TO BE NAILED AT 4"O.C. AS REQUIRED BY SEC. | | R803.2.3.1 OF 2010-FBC-RESIDENTIAL. | | | | B) SPECIFY/IDENTIFY THE ROOF ZONE #3 FOR GABLE ENDS AS | | REQUIRED BY FIGURE R803.2.3.1. SPECIFY DIMENSION (5'-0" | | MIN.). | | | | 8- LOCATION OF ATTIC ACCESS DOESN'T PROVIDE ENOUGH | | HEADROOM AND IS NOT "READILY ACCESSIBLE" AS REQUIRED BY | | SEC. R807.1 OF 2010 FBC-RESIDENTIAL. THIS MAY BE | | BLOCKED BECAUSE IS LOCATED IN STORAGE ROOM AND ROOM CAN | | BE LOCKED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-06-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-06-14 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-06-14 |
Time |
10:13 |
Sent To |
|
|
Notes |
2013-06-14 10:26:49 | 2010 FBC / 2008 NEC | | | | ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2008 NATIONAL | | ELECTRICAL CODE | | | | 1) NEW PANEL AND CIRCUIT BREAKERS SHALL COMPLY WITH THE | | 2008 NEC. | | | | 2) ARC-FAULT PROTECTION (COMBINATION TYPE) IS REQUIRED | | TO COMPLY WITH NEC 210.12B. | | | | 3) MULTIWIRE BRANCH CIRCUITS SHALL COMPLY WITH NEC | | 210.4. | 2013-06-13 10:55:26 | NEW DRAWINGS SUBMITTED. JG. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2013-05-03 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-05-03 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-05-03 |
Time |
09:49 |
Sent To |
|
|
Notes |
2013-05-03 09:50:23 | SEE NOTES ON ELECTRICAL DRAWING |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2013-06-13 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2013-06-13 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2013-06-13 |
Time |
14:36 |
Sent To |
|
|
Notes |
2013-06-13 14:37:20 | STORAGE CARRIAGE-STYLE DOORS MUST MATCH ELEVATIONS | | PROVIDED. PENDING PRODUCT APPROVALS. FRIEDERIKE | | 822-1457 |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2013-04-29 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2013-04-29 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2013-04-29 |
Time |
16:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-06-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-06-14 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-06-13 |
Time |
10:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-05-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-15 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-04-29 |
Time |
17:16 |
Sent To |
|
|
Notes |
2013-04-29 17:19:12 | EXPEDITED | | R--11 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2013-06-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-06-13 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-06-13 |
Time |
16:06 |
Sent To |
|
|
Notes |
2013-06-13 16:07:33 | IMPACT FEES PAID $1093.12. MU-2013-8830. JG. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2013-05-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-14 |
Time |
17:18 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-14 |
Time |
17:18 |
Sent To |
|
|
Notes |
2013-05-14 17:19:37 | PROVIDE COPY OF IMPACT FEES PAID RECEIPT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2013-06-14 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-06-14 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-06-14 |
Time |
15:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2013-05-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-15 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-15 |
Time |
10:42 |
Sent To |
|
|
Notes |
2013-05-15 11:09:16 | RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- EQUIPMENT SIZING CALCULATIONS NEED TO HAVE EQUIPMENT | | MODEL AND NUMBER AS REQUIRED BY SEC. 403.6 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE A/C DESIGN SHOWN ON PLAN. SEC. | | 107.2.1 CITY AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2013-06-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-06-13 |
Time |
17:14 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-06-13 |
Time |
17:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2013-05-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-05-15 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-05-15 |
Time |
11:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2013-06-13 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2013-06-13 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2013-06-13 |
Time |
14:37 |
Sent To |
|
|
Notes |
2013-06-13 11:27:34 | NEW DRAWINGS SUBMITTED. JG. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2013-04-29 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2013-04-29 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2013-04-29 |
Time |
16:02 |
Sent To |
|
|
Notes |
|
|