Plan Review Details - Permit 13041131
Plan Review Stops For Permit 13041131
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-14 Cont ID  
Sent By jgomez Date 2013-06-13 Time 10:58 Rev Time 0.00
Received By jgomez Date 2013-06-13 Time 10:58 Sent To  
Notes
2013-06-13 11:26:39BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE THE ENERGY CALCULATIONS: A) ITEM #15 IS
 TAKING THE "CV" CREDIT. PLANS NEED TO SHOW COMPLIANCE.
 B) BUILDING ORIENTATION NEEDS TO MATCH SURVEY. C)
 COMPLETE ALL THE INFORMATION ON TOP OF FORM.
  
 2- PROVIDE PRODUCT APPROVAL FOR STORAGE BARN TYPE DOORS
 AS SHOWN ON PLANS. AND, ENGINEER OF RECORD TO
 REVIEW/APPROVE IT BEFORE SUBMITTAL.
  
 3- REVISE ALL ROOF SHEATHING SPECIFICATIONS SHOWN ON
 ALL NOTES AND DETAILS. PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR ALT. METHOD SPECIFIED ON THE LAST SENTENCE
 OF SPECIFICATIONS OR DELETE THE ALT. METHOD.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-14 Cont ID  
Sent By jgomez Date 2013-05-14 Time 17:19 Rev Time 0.00
Received By jgomez Date 2013-05-14 Time 16:37 Sent To  
Notes
2013-05-14 17:33:34RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE THE ENERGY CALCULATIONS:
 A) ITEM #9: ACCORDING TO PLANS THERE IS ONLY ONE 2X6
 WALL WITH R19 INSULATION. OTHER WALLS ARE 2X4 WITH R11
 INSULATION. REVISE TOTAL WALL AREA FOR EACH WALL TYPE
 TO MATCH PLANS.
  
 B) ITEM #15 IS TAKING THE "CF" AND "CV" CREDITS.
 PROVIDE COMPLETE SPECIFICATIONS ON PLANS SHOWING
 COMPLIANCE WITH THE "CV" CREDIT. SEC. 405.6.4 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) THERE IS NOT KITCHEN ON THIS ADDITION. REVISE PAGE
 2.
  
 D) REVISE ROOF TYPE AND MATERIAL ON PAGE 2 TO MATCH
 PLANS.
  
 E) REVISE OVERHANG DEPTH AND SEPARATION ON PAGE 3 TO
 MATCH PLANS. NOTE, CONSIDER THE GABLE END WALL. ALSO,
 THERE IS MORE THAN 6" OVERHANG SEPARATION.
  
 F) COMPLETE ALL THE INFORMATION ON TOP OF FORM. BUILDER
 NAME, ETC.
  
 2- PROVIDE SITE PLAN SHOWING LOCATION AND ORIENTATION
 OF PROPOSED STRUCTURE. SEC. 107.3.5.3 CITY AMENDMENTS
 TO FBC.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) STORAGE DOUBLE DOORS AS SHOWN ON FRONT ELEVATION.
  
 B) ROOF SHINGLES.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 5- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. REQUIRED
 BY PALM BEACH COUNTY FOR THE RECORDS RETENTION.
  
 6- SHEET A-1: A) REVISE THE BUILDING CATEGORY AND
 ALTERATION LEVEL SPECIFIED ON DESIGN PARAMETERS. THIS
 IS TYPE "VB" NOT "II" AND IS AN ADDITION. GARAGE IS
 DEMOLISHED AND NEW HABITABLE BUILDING IS CONSTRUCTED.
 THEREFORE, SEC. 407 OF 2010-FBC-EXISTING BUILDING
 APPLIES.
  
 B) REVISE GENERAL NOTES AS WELL TO REFLECT ITEM #5(A)
 ABOVE.
  
 7- A) REVISE ALL ROOF SHEATHING SPECIFICATIONS SHOWN ON
 DETAILS, WALL SECTIONS AND ROOF FRAMING NOTES. ROOF
 ZONE #3 NEED TO BE NAILED AT 4"O.C. AS REQUIRED BY SEC.
 R803.2.3.1 OF 2010-FBC-RESIDENTIAL.
  
 B) SPECIFY/IDENTIFY THE ROOF ZONE #3 FOR GABLE ENDS AS
 REQUIRED BY FIGURE R803.2.3.1. SPECIFY DIMENSION (5'-0"
 MIN.).
  
 8- LOCATION OF ATTIC ACCESS DOESN'T PROVIDE ENOUGH
 HEADROOM AND IS NOT "READILY ACCESSIBLE" AS REQUIRED BY
 SEC. R807.1 OF 2010 FBC-RESIDENTIAL. THIS MAY BE
 BLOCKED BECAUSE IS LOCATED IN STORAGE ROOM AND ROOM CAN
 BE LOCKED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-14 Cont ID  
Sent By rmcdouga Date 2013-06-14 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2013-06-14 Time 10:13 Sent To  
Notes
2013-06-14 10:26:492010 FBC / 2008 NEC
  
 ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2008 NATIONAL
 ELECTRICAL CODE
  
 1) NEW PANEL AND CIRCUIT BREAKERS SHALL COMPLY WITH THE
 2008 NEC.
  
 2) ARC-FAULT PROTECTION (COMBINATION TYPE) IS REQUIRED
 TO COMPLY WITH NEC 210.12B.
  
 3) MULTIWIRE BRANCH CIRCUITS SHALL COMPLY WITH NEC
 210.4.
2013-06-13 10:55:26NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-03 Time 09:49 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 09:49 Sent To  
Notes
2013-05-03 09:50:23SEE NOTES ON ELECTRICAL DRAWING

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2013-06-13 Cont ID  
Sent By fmittner Date 2013-06-13 Time 14:36 Rev Time 0.00
Received By fmittner Date 2013-06-13 Time 14:36 Sent To  
Notes
2013-06-13 14:37:20STORAGE CARRIAGE-STYLE DOORS MUST MATCH ELEVATIONS
 PROVIDED. PENDING PRODUCT APPROVALS. FRIEDERIKE
 822-1457

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-04-29 Cont ID  
Sent By fmittner Date 2013-04-29 Time 16:02 Rev Time 0.00
Received By fmittner Date 2013-04-29 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-14 Cont ID  
Sent By jgomez Date 2013-06-14 Time 14:26 Rev Time 0.00
Received By jgomez Date 2013-06-13 Time 10:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-15 Cont ID  
Sent By jgomez Date 2013-05-15 Time 11:20 Rev Time 0.00
Received By jgomez Date 2013-04-29 Time 17:16 Sent To  
Notes
2013-04-29 17:19:12EXPEDITED
 R--11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-06-13 Cont ID  
Sent By jgomez Date 2013-06-13 Time 16:06 Rev Time 0.00
Received By jgomez Date 2013-06-13 Time 16:06 Sent To  
Notes
2013-06-13 16:07:33IMPACT FEES PAID $1093.12. MU-2013-8830. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-05-14 Cont ID  
Sent By jgomez Date 2013-05-14 Time 17:18 Rev Time 0.00
Received By jgomez Date 2013-05-14 Time 17:18 Sent To  
Notes
2013-05-14 17:19:37PROVIDE COPY OF IMPACT FEES PAID RECEIPT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-06-14 Cont ID  
Sent By hmoser Date 2013-06-14 Time 15:31 Rev Time 0.00
Received By hmoser Date 2013-06-14 Time 15:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-15 Cont ID  
Sent By jgomez Date 2013-05-15 Time 10:42 Rev Time 0.00
Received By jgomez Date 2013-05-15 Time 10:42 Sent To  
Notes
2013-05-15 11:09:16RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS NEED TO HAVE EQUIPMENT
 MODEL AND NUMBER AS REQUIRED BY SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C DESIGN SHOWN ON PLAN. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-13 Cont ID  
Sent By jgomez Date 2013-06-13 Time 17:14 Rev Time 0.00
Received By jgomez Date 2013-06-13 Time 17:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-15 Cont ID  
Sent By jgomez Date 2013-05-15 Time 11:20 Rev Time 0.00
Received By jgomez Date 2013-05-15 Time 11:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-06-13 Cont ID  
Sent By fmittner Date 2013-06-13 Time 14:37 Rev Time 0.00
Received By fmittner Date 2013-06-13 Time 14:37 Sent To  
Notes
2013-06-13 11:27:34NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-04-29 Cont ID  
Sent By fmittner Date 2013-04-29 Time 16:02 Rev Time 0.00
Received By fmittner Date 2013-04-29 Time 16:02 Sent To  
Notes
***NONE***