Plan Review Details - Permit 13040934
Plan Review Stops For Permit 13040934
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-21 Cont ID  
Sent By lmartine Date 2013-05-21 Time 15:07 Rev Time 0.00
Received By lmartine Date 2013-05-21 Time 15:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-13 Cont ID  
Sent By shill Date 2013-05-13 Time 14:52 Rev Time 0.00
Received By shill Date 2013-05-13 Time 14:52 Sent To FIRE
Notes
2013-05-13 15:08:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A DETAIL FOR THE UL ASSEMBLY REFERENCED IN
 THE FIRE RESPONSE LETTER, FBC 107.
  
 2. IT APPEARS THAT AN EXIT STAIR IS TO BE MODIFIED TO
 BE USED AS STORAGE. SEE FBC 1022, 1022.3. PROVIDE MORE
 INFORMATION REGARDING THE STAIR.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-08 Cont ID  
Sent By dharvey Date 2013-05-08 Time 08:24 Rev Time 0.00
Received By dharvey Date 2013-05-08 Time 08:24 Sent To  
Notes
2013-05-08 08:24:36PREVIOUS ITEMS COMPLIED WITH. DH
 PLACED IN MISC2 BOX

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 11:12 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 11:12 Sent To  
Notes
2013-05-06 11:13:395-06-13
 1. SHOW EXISTING PANEL LOCATION
 2. PROVIDE PANEL SCHEDULE. (SHOW "NEW" CIRCUIT) NEC
 408.4
 3. INDICATE CIRCUIT NUMBERS AT EACH NEW DEVICE ON FLOOR
 PLAN
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-05-17 Cont ID  
Sent By rferguso Date 2013-05-17 Time 11:05 Rev Time 0.00
Received By rferguso Date 2013-05-17 Time 11:05 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-04-30 Cont ID  
Sent By wjolin Date 2013-04-30 Time 12:06 Rev Time 0.00
Received By wjolin Date 2013-04-30 Time 11:52 Sent To E
Notes
2013-04-30 12:06:311608 SOUTH DIXIE HIGHWAY
 PERMIT #13040934
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: "GENERAL COMMERCIAL" IS NOT AN
 OCCUPANCY TYPE. IF THIS PERMIT IS FOR A SHELL PERMIT
 ONLY WITH NO TENANT PLEASE INDICATE.
 ORIGINAL COMMENT: PLANS DO NOT INDICATE THE OCCUPANCY
 TYPE THAT WILL BE OCCUPYING SPACE 3 & 4.
  
 RESPONSE COMMENT: PROVIDE DRAWING NOTE INDICATING WALL
 TO BE PERMANENTLY IDENTIFIED WITH THE NOTE BELOW.
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE
 SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE - NFPA
 101
  
 RESPONSE COMMENT: NO EGRESS INFORMATION PROVIDED FOR
 SPACE #6.
 ORIGINAL COMMENT: THE NEW FIRE BARRIER APPEARS TO
 ELIMINATE AN EXIT FROM SPACE #6. SHOW THE EXIT DOORS
 AND TRAVEL DISTANCES FOR SPACE #6.
  
 RESONSE COMMENT: INDICATE THE EXISTING LOCATIONS AND
 DIMENSION THE EXISTING SPRINKLER LOCATIONS WITH
 REFERENCE TO THE NEW PROPOSED WALL TO CONFIRM TO NO
 SPRINKLER ADDITIONS OR RELOCATIONS ARE REQUIRED.
 SEPARATE PLANS AND PERMITS ARE NEEDED TO RELOCATE THE
 EXISTING SPRINKLERS AROUND THE NEW FIRE BARRIER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-24 Cont ID  
Sent By wjolin Date 2013-04-24 Time 09:39 Rev Time 0.00
Received By wjolin Date 2013-04-24 Time 09:25 Sent To B
Notes
2013-04-24 09:39:151608 SOUTH DIXIE HIGHWAY
 PERMIT #13040934
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PLANS DO NOT INDICATE THE OCCUPANCY TYPE THAT WILL BE
 OCCUPYING SPACE 3 & 4.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE
 SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE ? NFPA
 101
  
 PROVIDE A UL LISTED WALL ASSEMBLY DETAIL.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE
 PENETRATION PROTECTION DETAILS.
  
 THE NEW FIRE BARRIER APPEARS TO ELIMINATE AN EXIT FROM
 SPACE #6. SHOW THE EXIT DOORS AND TRAVEL DISTANCES FOR
 SPACE #6.
  
 INDICATE THE LOCATION OF EXIT SIGNS, EMERGENCY LIGHTING
 AND FIRE EXTINGUISHERS.
  
 INDICATE ANY DUCTWORK PENETRATING THE NEW FIRE BARRIER.
  
 SEPARATE PLANS AND PERMITS ARE NEEDED TO RELOCATE THE
 EXISTING SPRINKLERS AROUND THE NEW FIRE BARRIER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-21 Cont ID  
Sent By lmartine Date 2013-05-21 Time 15:07 Rev Time 0.00
Received By lmartine Date 2013-04-30 Time 11:50 Sent To  
Notes
2013-05-07 11:06:29TO MISC 3
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-30 Cont ID  
Sent By wjolin Date 2013-04-30 Time 12:06 Rev Time 0.00
Received By wjolin Date 2013-04-23 Time 08:58 Sent To  
Notes
2013-04-24 16:25:554/24 TO ELEC
2013-04-24 08:57:57SENT TO FIRE BOX