Plan Review Stops For Permit 13040934 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-05-21 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2013-05-21 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2013-05-21 |
Time |
15:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-05-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-05-13 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-05-13 |
Time |
14:52 |
Sent To |
FIRE |
|
Notes |
2013-05-13 15:08:47 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. PROVIDE A DETAIL FOR THE UL ASSEMBLY REFERENCED IN | | THE FIRE RESPONSE LETTER, FBC 107. | | | | 2. IT APPEARS THAT AN EXIT STAIR IS TO BE MODIFIED TO | | BE USED AS STORAGE. SEE FBC 1022, 1022.3. PROVIDE MORE | | INFORMATION REGARDING THE STAIR. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-05-08 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-05-08 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-05-08 |
Time |
08:24 |
Sent To |
|
|
Notes |
2013-05-08 08:24:36 | PREVIOUS ITEMS COMPLIED WITH. DH | | PLACED IN MISC2 BOX |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-05-06 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-05-06 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-05-06 |
Time |
11:12 |
Sent To |
|
|
Notes |
2013-05-06 11:13:39 | 5-06-13 | | 1. SHOW EXISTING PANEL LOCATION | | 2. PROVIDE PANEL SCHEDULE. (SHOW "NEW" CIRCUIT) NEC | | 408.4 | | 3. INDICATE CIRCUIT NUMBERS AT EACH NEW DEVICE ON FLOOR | | PLAN | | VB |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2013-05-17 |
|
|
Cont ID |
|
Sent By |
rferguso |
Date |
2013-05-17 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
rferguso |
Date |
2013-05-17 |
Time |
11:05 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2013-04-30 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-04-30 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-04-30 |
Time |
11:52 |
Sent To |
E |
|
Notes |
2013-04-30 12:06:31 | 1608 SOUTH DIXIE HIGHWAY | | PERMIT #13040934 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | RESPONSE COMMENT: "GENERAL COMMERCIAL" IS NOT AN | | OCCUPANCY TYPE. IF THIS PERMIT IS FOR A SHELL PERMIT | | ONLY WITH NO TENANT PLEASE INDICATE. | | ORIGINAL COMMENT: PLANS DO NOT INDICATE THE OCCUPANCY | | TYPE THAT WILL BE OCCUPYING SPACE 3 & 4. | | | | RESPONSE COMMENT: PROVIDE DRAWING NOTE INDICATING WALL | | TO BE PERMANENTLY IDENTIFIED WITH THE NOTE BELOW. | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE | | SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE - NFPA | | 101 | | | | RESPONSE COMMENT: NO EGRESS INFORMATION PROVIDED FOR | | SPACE #6. | | ORIGINAL COMMENT: THE NEW FIRE BARRIER APPEARS TO | | ELIMINATE AN EXIT FROM SPACE #6. SHOW THE EXIT DOORS | | AND TRAVEL DISTANCES FOR SPACE #6. | | | | RESONSE COMMENT: INDICATE THE EXISTING LOCATIONS AND | | DIMENSION THE EXISTING SPRINKLER LOCATIONS WITH | | REFERENCE TO THE NEW PROPOSED WALL TO CONFIRM TO NO | | SPRINKLER ADDITIONS OR RELOCATIONS ARE REQUIRED. | | SEPARATE PLANS AND PERMITS ARE NEEDED TO RELOCATE THE | | EXISTING SPRINKLERS AROUND THE NEW FIRE BARRIER. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2013-04-24 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-04-24 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-04-24 |
Time |
09:25 |
Sent To |
B |
|
Notes |
2013-04-24 09:39:15 | 1608 SOUTH DIXIE HIGHWAY | | PERMIT #13040934 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. | | | | PLANS DO NOT INDICATE THE OCCUPANCY TYPE THAT WILL BE | | OCCUPYING SPACE 3 & 4. | | | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE | | SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE ? NFPA | | 101 | | | | PROVIDE A UL LISTED WALL ASSEMBLY DETAIL. | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE | | PENETRATION PROTECTION DETAILS. | | | | THE NEW FIRE BARRIER APPEARS TO ELIMINATE AN EXIT FROM | | SPACE #6. SHOW THE EXIT DOORS AND TRAVEL DISTANCES FOR | | SPACE #6. | | | | INDICATE THE LOCATION OF EXIT SIGNS, EMERGENCY LIGHTING | | AND FIRE EXTINGUISHERS. | | | | INDICATE ANY DUCTWORK PENETRATING THE NEW FIRE BARRIER. | | | | SEPARATE PLANS AND PERMITS ARE NEEDED TO RELOCATE THE | | EXISTING SPRINKLERS AROUND THE NEW FIRE BARRIER. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-05-21 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2013-05-21 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2013-04-30 |
Time |
11:50 |
Sent To |
|
|
Notes |
2013-05-07 11:06:29 | TO MISC 3 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-04-30 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-04-30 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-04-23 |
Time |
08:58 |
Sent To |
|
|
Notes |
2013-04-24 16:25:55 | 4/24 TO ELEC | 2013-04-24 08:57:57 | SENT TO FIRE BOX |
|
|