Plan Review Details - Permit 13040917
Plan Review Stops For Permit 13040917
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-03 Cont ID  
Sent By jwitmer Date 2013-07-03 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2013-07-03 Time 12:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-30 Cont ID  
Sent By jwitmer Date 2013-04-30 Time 15:01 Rev Time 0.00
Received By jwitmer Date 2013-04-30 Time 13:01 Sent To  
Notes
2013-04-30 13:07:36BUILDING PLAN REVIEW
 PERMIT: 13040917
 ADD: 7000 S DIXIE HWY SUITES 6 & 7
 CONT: TBD
 TEL: (561)313-9046
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/30/2013
 ACTION: DENIED
  
 NOTE: THE PLANS INDICATE THIS IS A CHANGE OF OCCUPANCY
 FROM A BUSINESS OCCUPANCY TO AN ASSEMBLY (A-3)
 OCCUPANCY. 2010 FBC-EXISTING BUILDING 901.3.1 PARTIAL
 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY.
  
 1) THE DESIGNER OF RECORD HAS NOT ELECTED TO IDENTIFY
 WHICH OPTION THEY WOULD LIKE TO DESIGN BY:
 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION.
  
 2) 912.4 MEANS OF EGRESS, GENERAL.
 HAZARD CATEGORIES IN REGARD TO LIFE SAFETY AND MEANS OF
 EGRESS SHALL BE IN ACCORDANCE WITH TABLE 912.4.
 912.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 SHOW COMMON PATH OF TRAVEL FBC-B 1014.3 FROM THE
 FURTHEST POINT IN THE PASTORS OFFICE TO THE 36" EXIT,
 IF OVER 75 FEET THEN A 2ND MEANS OF EGRESS IS REQUIRED
 WITH A 32 INCH CLEAR OPENING, MINIMUM OF 2'-10" DOOR.
 2010 FBC-B 1008.1.1.
  
 3) THE SUBMITTED PLAN INDICATES A NEW 36 INCH IMPACT
 DOOR, NO PRODUCT APPROVALS WERE SUBMITTED WILL NEED TO
 COMPLY WITH:
 3A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-10-22 Cont ID  
Sent By albarran Date 2013-10-22 Time 10:01 Rev Time 0.00
Received By albarran Date   Time   Sent To I
Notes
2013-10-22 10:32:17SENT TO SH DESK.
2013-10-22 10:01:38ACCORDING TO THE APPLICANT AND THE SCOPE OF THIS
 PERMIT, NO ELECTRICAL WORK IS BEING DONE. LIGHTING
 REQUIREMENTS FOR A PLACE OF ASSEMBLY ARE LOWER THAN
 THOSE FOR AN OFFICE, THEREFORE THE EXISTING CIRCUITS
 SHOULD BE SUFFICIENT. IF ANY ADDITIONAL WORK WILL BE
 DONE, A PERMIT WILL BE REQUIRED THEN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-07-01 Cont ID  
Sent By dharvey Date 2013-07-01 Time 11:01 Rev Time 0.00
Received By dharvey Date 2013-07-01 Time 11:01 Sent To  
Notes
2013-07-01 11:02:12 
 13040917
 7000 S DIXIE HWY, SUITE 5
 CHANGE OF USE FROM BUSINESS TO CHURCH
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS. PROVIDE AN PLAN SHOWING THE ELECTRICAL
 SYSTEM. SHOW ALL NEW AND EXISTING ELECTRICAL OUTLETS
 INCLUDING LIGHTING.
  
 VERIFY THAT THE REQUIRED WORKING CLEARANCES AND
 DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE
 ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26,
 240.24, 408.17
  
 VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION
 AND EXIT SIGNS. FBC 1006.2 1011.1
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH
 GFCI?S. NEC 422.51
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, AND SECURITY.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-17 Cont ID  
Sent By dharvey Date 2013-05-17 Time 13:07 Rev Time 0.00
Received By dharvey Date 2013-05-17 Time 13:07 Sent To  
Notes
2013-05-17 13:10:275-17-13
 OCCUPANCY IS NOT GREATER THAN 100, THEREFOR NEC 518 FOR
 SPECIAL OCCUPANCIES DOES NOT COME INTO PLAY.
  
 HOWEVER, A TYPICAL ELECTRICAL DRAWING MUST BE PROVIDED
 SHOWING SERVICE, FEEDERS, FIXTURES, RECEPTACLES,
 ETC....
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-07-03 Cont ID  
Sent By wjolin Date 2013-07-03 Time 13:32 Rev Time 0.00
Received By wjolin Date 2013-07-03 Time 13:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-06-14 Cont ID  
Sent By wjolin Date 2013-06-14 Time 11:44 Rev Time 0.00
Received By wjolin Date 2013-06-14 Time 11:43 Sent To  
Notes
2013-06-14 11:44:277000 SOUTH DIXIE HIGHWAY - SUITE #5
 PERMIT #13040917
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVIEW #2: PLAN REVIEW COMMENTS FROM REVIEW #1 WERE NOT
 ADDRESSED.
  
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101
 REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION
 WITH FLORIDA AMENDMENTS.)
  
 THE SPACE APPEARS TO HAVE AN OCCUPANT LOAD OF AT LEAST
 50 PERSONS WHEN USING A OCCUPANT LOAD FACTOR OF 15
 SQ.FT. PER PERSON (USING TABLES AND CHAIRS). IF ONLY
 CHAIRS OR STANDING ROOM IS BEING PROVIDED, AN OCCUPANT
 LOAD FACTOR OF 7 SQ.FT. PER PERSON MAY BE APPROPRIATE.
 ASSEMBLY: 368SQ.FT. + 349SQ.FT. / 15 SQ.FT. PER PERSON
 = 47.8 PERSONS
 BUSINESS: 173SQ.FT. / 100 SQ. FT. PER PERSON = 1.7
 PERSONS
 TOTAL = 49.53 PERSONS
  
 PROVIDE A SEATING/FURNITURE LAYOUT.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING.
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1-1/2 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS
 TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES
 ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 DOOR ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED
 DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN
 STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 THE INTERIOR FINISH MATERIALS FOR WALLS AND CEILINGS
 SHALL MEET THE SMOKE DEVELOPMENT (0-450) AND FLAME
 SPREAD (76-200) REQUIREMENTS FOR CLASS C INTERIOR
 FINISHES PER NFPA 101.
  
 CURTAINS, DRAPES AND OTHER LOOSELY HANGING
 FINISHINGS/DECORATIONS SHALL MEET THE FLAME PROPAGATION
 CRITERIA OF NFPA 701 (MATERIAL WILL SELF EXTINGUISH
 ONCE DIRECT FIRE FLAME HAS BEEN REMOVED).
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-05-04 Cont ID  
Sent By wjolin Date 2013-05-04 Time 12:04 Rev Time 0.00
Received By wjolin Date 2013-05-04 Time 11:37 Sent To  
Notes
2013-05-04 12:04:317000 SOUTH DIXIE HIGHWAY - SUITE #5
 PERMIT #13040917
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101
 REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION
 WITH FLORIDA AMENDMENTS.)
  
 THE SPACE APPEARS TO HAVE AN OCCUPANT LOAD OF AT LEAST
 50 PERSONS WHEN USING A OCCUPANT LOAD FACTOR OF 15
 SQ.FT. PER PERSON (USING TABLES AND CHAIRS). IF ONLY
 CHAIRS OR STANDING ROOM IS BEING PROVIDED, AN OCCUPANT
 LOAD FACTOR OF 7 SQ.FT. PER PERSON MAY BE APPROPRIATE.
 ASSEMBLY: 368SQ.FT. + 349SQ.FT. / 15 SQ.FT. PER PERSON
 = 47.8 PERSONS
 BUSINESS: 173SQ.FT. / 100 SQ. FT. PER PERSON = 1.7
 PERSONS
 TOTAL = 49.53 PERSONS
  
 PROVIDE A SEATING/FURNITURE LAYOUT.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING.
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1-1/2 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS
 TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES
 ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 DOOR ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED
 DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN
 STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE INTERIOR FINISH MATERIALS FOR WALLS AND CEILINGS
 SHALL MEET THE SMOKE DEVELOPMENT (0-450) AND FLAME
 SPREAD (76-200) REQUIREMENTS FOR CLASS C INTERIOR
 FINISHES PER NFPA 101.
  
 CURTAINS, DRAPES AND OTHER LOOSELY HANGING
 FINISHINGS/DECORATIONS SHALL MEET THE FLAME PROPAGATION
 CRITERIA OF NFPA 701 (MATERIAL WILL SELF EXTINGUISH
 ONCE DIRECT FIRE FLAME HAS BEEN REMOVED).
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-24 Cont ID  
Sent By shill Date 2013-10-24 Time 17:50 Rev Time 0.00
Received By shill Date 2013-10-16 Time 18:42 Sent To  
Notes
2013-10-16 18:42:46INCOMING SENT TO <$5K ELECTRICAL BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-03 Cont ID  
Sent By jwitmer Date 2013-07-03 Time 13:38 Rev Time 0.00
Received By jwitmer Date 2013-05-31 Time 17:49 Sent To  
Notes
2013-05-31 17:52:30C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-29 Cont ID  
Sent By shill Date 2013-05-29 Time 16:47 Rev Time 0.00
Received By shill Date 2013-04-23 Time 07:26 Sent To  
Notes
2013-04-24 07:30:14C16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2013-07-03 Cont ID  
Sent By jwitmer Date 2013-07-03 Time 13:38 Rev Time 0.00
Received By jwitmer Date 2013-07-03 Time 13:38 Sent To  
Notes
2013-07-03 13:40:54NO FEES DUE, STAMPED PLANS. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2013-07-03 Cont ID  
Sent By jwitmer Date 2013-07-03 Time 13:37 Rev Time 0.00
Received By jwitmer Date 2013-07-03 Time 13:37 Sent To  
Notes
2013-07-03 13:38:06BATHROOMS NO MECHANICAL WORK COMPLETED, NO CHANGE IN
 RESTROOMS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-17 Cont ID  
Sent By hmoser Date 2013-05-17 Time 13:38 Rev Time 0.00
Received By hmoser Date 2013-05-17 Time 13:24 Sent To  
Notes
2013-05-17 13:38:38PLANS DENIED
 PROVIDE MECHANICAL PLANS AND VENTILATION
 FOR BATHROOM EXHAUST AND OUTSIDE AIR.
 PER TABLE 403.3 FBC (M) AND SECTION
 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-05 Cont ID  
Sent By lwagner Date 2013-06-05 Time 09:05 Rev Time 0.00
Received By lwagner Date 2013-06-05 Time 08:59 Sent To  
Notes
2013-06-05 09:07:25ONE DRINKING FOUNTAIN IS FURNISHED USING THE EXEMPTION
 OF CHURCHES FROM ADA. SS. 553.501-513, F.S.
 ONE SHOWER IS CONVERTED TO MOP SINK
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-04-26 Cont ID  
Sent By lwagner Date 2013-04-26 Time 10:43 Rev Time 0.00
Received By lwagner Date 2013-04-26 Time 10:43 Sent To  
Notes
2013-04-26 10:37:25FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. WITH THE CHANGE OF OCCUPANCY TO A3 CHURCH,
 FBC PLUMBING 403.1 MINIMUM PLUMBING FACILITIES:
 A-3 = 1 HI/LO DRINKING FOUNTAIN PER 1,000 (SEE
 ACCESSIBILITY 211.2 FOR THE HI/LO REQUIREMENT).
 1 SERVICE SINK.
 UPDATE 5/28/13: A MINIMUM OF ONE DRINKING FOUNTAIN
 WOULD BE REQUIRED IF USING THE EXEMPTION OF CHURCHES
 FROM ADA. SS. 553.501-513, F.S.
  
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By avann Date 2013-05-28 Time 16:43 Rev Time 0.00
Received By ajones Date 2013-05-28 Time 16:43 Sent To  
Notes
2013-04-29 14:39:154/29/13