Plan Review Details - Permit 13040902
Plan Review Stops For Permit 13040902
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-14 Cont ID  
Sent By jwitmer Date 2013-06-13 Time 11:32 Rev Time 0.00
Received By jwitmer Date 2013-06-13 Time 11:32 Sent To  
Notes
2013-06-13 11:50:42BUILDING PLAN REVIEW
 PERMIT: 13040902
 ADD: 411 CLEMATIS ST/ 2ND FLOOR SUITE 230
 CONT: RANDOLPH &DEWDNEY
 TEL: (561)441-1186
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JUNE 14/ 2013
 ACTION: PROVISO
  
  
  
 BUILDING PROVISO:
 NO TENANT CAN OCCUPY THIS SPACE UNTIL CODE COMPLIANCE
 IS ACHIEVED WITH THESE ITEMS:
  
 1) PLEASE PROVIDE A SCALED PLAN SHOWING COMPLIANCE WITH
 2010 FBC-B 1014.3 EXCEPTION # 1, COMMON PATH OF TRAVEL
 FROM THE FURTHEST POINT IN THE SUITE. PLEASE BE AWARE
 THIS SPACE IS BELIEVED TO HAVE ONLY ONE MEANS OF EGRESS
 INTO AND OUT OF THIS SPACE. TWO ELEMENTS MUST BE IN
 CODE COMPLIANCE, THE FIRST IS COMMON PATH OF TRAVEL
 FROM THE FURHEST POINT, THE SECOND ISSUE IS OCCUPANT
 LOAD, THIS SPACE IS BEING FINISHED AS A WHITE BOX,
 PLEASE REALIZE IF ANY OCCUPANCY OTHER THAN BUSINESS
 LEASES THIS SPACE THE OCCUPANT LOAD WILL BE OVER 49 AND
 REQUIRE 2 MEANS OF EGRESS, 2010 FBC-B TABLE 1015.1.
 WITH THE TWO MEANS OF EGRESS THEY WOULD NEED TO BE
 1/3RD THE DIAGONAL OF THE ROOM APART, 2010 FBC-B
 1015.2.1.
 ON THE 1ST RESUBMISSION OF PLANS THE PLAN INDICATES ONE
 DOOR, WITH THE PLANS NOT DRAWN TO SCALE AND A DIAGONAL
 DISTANCE OF 88 FEET IT WILL APPEAR THAT THE TRAVEL
 DISTANCE WILL BE APPROXIMATELY 111 FEET REQUIRING A
 SECOND DOORWAY, THIS CAN'T BE DETERMINED UNTIL SCALED
 DRAWING WITH DIMENSIONS ARE SUBMITTED FOR REVIEW AND OR
 A FURNITURE PLAN WITH A COMMON PATH OF TRAVEL SHOWN NOT
 EXCEEDING 100 FT.
  
 2) . THE PLANS ALSO DO NOT PROVIDE COMPLIANCE WITH:
 2010 FBC-B 1006.3.1 EXITS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY DIRECTION OF
 EXIT ACCESS. EVERY EXIT SIGN SHALL BE SUITABLY
 ILLUMINATED BY A RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE VISIBLE IN BOTH
 NORMAL AND EMERGENCY LIGHTING.
  
 3) 2ND REQUEST. 1006.3.4 EXIT STAIR DOOR OR TACTILE
 SIGNAGE. TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING
 WITH ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-02 Cont ID  
Sent By jwitmer Date 2013-04-30 Time 11:25 Rev Time 0.00
Received By jwitmer Date 2013-04-30 Time 11:56 Sent To  
Notes
2013-04-30 12:28:06BUILDING PLAN REVIEW
 PERMIT: 13040902
 ADD: 411 CLEMATIS ST SUITE ??? 2ND FLOOR
 CONT: RANDOLPH &DEWDNEY
 TEL: (561)441-1186
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: APRIL 30/ 2013
 ACTION: DENIED
  
 1) THE PLANS INDICATE THIS SPACE IS APPROXIMATELY 4,000
 SQ FT IN AREA, PLEASE NOTE THE SUBMITTED PLANS DO NOT
 INDICATE WHAT TYPE WALL ASSEMBLY IS GOING TO BE
 INSTALLED TO CREATE A ONE HOUR FIRE PARTITION BETWEEN
 THIS SPACE AND ADJACENT TENANTS. PLEASE PROVIDE EITHER
 A UL LISTING, GYPSUM ASSOCIATION LISTING OR OTHER
 NATIONALLY RECOGNIZED ASSOCIATION. 2010 FBC-B 709.1(6).
  
 2) PLEASE PROVIDE A SCALED PLAN SHOWING COMPLIANCE WITH
 2010 FBC-B 1014.3 EXCEPTION # 1, COMMON PATH OF TRAVEL
 FROM THE FURTHEST POINT IN THE SUITE. PLEASE BE AWARE
 THIS SPACE IS BELIEVED TO HAVE ONLY ONE MEANS OF EGRESS
 INTO AND OUT OF THIS SPACE. TWO ELEMENTS MUST BE IN
 CODE COMPLIANCE, THE FIRST IS COMMON PATH OF TRAVEL
 FROM THE FURHEST POINT, THE SECOND ISSUE IS OCCUPANT
 LOAD, THIS SPACE IS BEING FINISHED AS A WHITE BOX,
 PLEASE REALIZE IF ANY OCCUPANCY OTHER THAN BUSINESS
 LEASES THIS SPACE THE OCCUPANT LOAD WILL BE OVER 49 AND
 REQUIRE
 2 MEANS OF EGRESS, 2010 FBC-B TABLE 1015.1. WITH THE
 TWO MEANS OF EGRESS THEY WOULD NEED TO BE 1/3RD THE
 DIAGONAL OF THE ROOM APART, 2010 FBC-B 1015.2.1.
  
 3) THE PLANS FAIL TO PROVIDE COMPLIANCE WITH 2010 FBC-B
 713.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 4) THE PLANS ALSO DO NOT PROVIDE COMPLIANCE WITH: 2010
 FBC-B 1006.3.1
 EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE LIGHT
 SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS
 SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY LIGHTING.
  
 5) 1006.3.4 EXIT STAIR DOOR OR TACTILE SIGNAGE. TACTILE
 SIGNAGE STATING ?EXIT? AND COMPLYING WITH ICC/ANSI
 A117.1, AMERICAN NATIONAL STANDARD FOR ACCESSIBLE AND
 USABLE BUILDINGS AND FACILITIES, SHALL BE INSTALLED
 ADJACENT TO THE LATCH SIDE OF THE DOOR 60 INCHES (1524
 MM) ABOVE THE FINISHED FLOOR TO THE CENTER LINE OF THE
 SIGN.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By dharvey Date 2013-05-07 Time 14:17 Rev Time 0.00
Received By dharvey Date 2013-05-07 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-06-14 Cont ID  
Sent By wjolin Date 2013-06-14 Time 12:40 Rev Time 0.00
Received By wjolin Date 2013-06-14 Time 12:37 Sent To  
Notes
2013-06-14 12:40:07411 CLEMATIS STREET - SUITE #230
 PERMIT #13040902
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 ALL BUILDING REVIEW COMMENTS SHALL BE ADHERED TO; NO
 OCCUPANCY PERMITED AT THIS TIME.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-06-12 Cont ID  
Sent By rferguso Date 2013-06-12 Time 11:49 Rev Time 0.00
Received By rferguso Date 2013-06-12 Time 11:49 Sent To B
Notes
2013-06-12 12:23:04411 CLEMATIS STREET
 PERMIT #13040902
 PLAN REVIEW COMMENTS - WEST PALM BEACH FIRE RESCUE
  
 * PLAN REVIEWED BY FIRE (FAILED).
 * SUBMIT SCALED PLANS TO DETERMINE PROPPER DISTANCE FOR
 COMMON PLATH OF TRAVEL
 * INDICATING THE EXACT LOCATION OF ALL EXISTING DOORS
 IN THE SPACE.
 * SUBMIT FURNITURE PLANS TO SHOW THE PROPPER ROUT AND
 DISTANCE FOR THE COMMON PATH OF TRAVEL.
 * ADDRESS ALL COMMENTS PREVIOUSLY MISSED FROM FIRE
 RESCUE'S REVIEW.
 * PLEASE INDICATE IF THE SPACE ACTUALLY A TENANT
 BUILDOUT OR A SHELL SPACE.
  
  
 RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE #(561) 804-4700

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-27 Cont ID  
Sent By wjolin Date 2013-04-27 Time 18:48 Rev Time 0.00
Received By wjolin Date 2013-04-27 Time 18:26 Sent To  
Notes
2013-04-27 18:48:55411 CLEMATIS STREET
 PERMIT #13040902
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO SUITE NUMBER PROVIDED ON PERMIT APPLICATION OR
 DRAWINGS.
  
 A NEW FIRE-RATED WALL APPEARS TO BE NEEDED BETWEEN
 TENANT SPACE #D2.107 AND SPACE #D2.202. PROVIDE A WALL
 DETAIL.
  
 PLANS DO NOT INDICATE IF ANY DUCTWORK WILL BE PASSING
 THROUGH THE NEW TENANT SEPARATION WALL.
  
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED
 WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM
 OR DEVICE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-13 Cont ID  
Sent By jwitmer Date 2013-06-13 Time 11:50 Rev Time 0.00
Received By jwitmer Date 2013-06-06 Time 11:21 Sent To  
Notes
2013-06-12 13:04:116/12 TO JW DESK
2013-06-07 11:25:40TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-24 Cont ID  
Sent By lmartine Date 2013-05-10 Time 13:42 Rev Time 0.00
Received By lmartine Date 2013-04-23 Time 11:48 Sent To  
Notes
2013-04-23 11:48:23B07

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-10 Cont ID  
Sent By aaponte Date 2013-05-10 Time 09:08 Rev Time 0.00
Received By aaponte Date 2013-05-10 Time 09:08 Sent To  
Notes
2013-05-10 09:09:12INTERIOR OFFICE IMPROVEMENTS ONLY.
2013-04-29 14:40:354/29/13