Plan Review Details - Permit 13040437
Plan Review Stops For Permit 13040437
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-14 Cont ID  
Sent By WITMER Date 2013-05-14 Time 17:30 Rev Time 0.00
Received By jwitmer Date 2013-05-14 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-13 Cont ID  
Sent By jwitmer Date 2013-04-13 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2013-04-13 Time 11:01 Sent To  
Notes
2013-04-13 11:41:29BUILDING PLAN REVIEW
 PERMIT: 13040437
 ADD: 701 S ROSEMARY AVE SUITE 137
 CONT: TBD
 TEL: (561)856-6655
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: APRIL 13/ 2013
 ACTION: DENIED
  
 1) PLANS FOR CITY PLACE REQUIRE A REVIEW BY CITY PLACE
 STAFF AND REVIEW OF APPROVAL STAMP ON THE PLANS BEFORE
 SUBMITTAL TO THE CITY FOR REVIEW AND ISSUANCE.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THE SHEET A-1 INDICATES A NEW LANDLORD STORAGE AREA,
 BUT NO PLANS WERE SUBMITTED WITH THE EXISTING FIRE
 SPRINKLER LAY OUT AND THE NEW FIRE SPRINKLER LAYOUT
 SINCE THE NEW TENANT SEPERATION WALL WILL IMPEDE THE
 FIRE SPRINKLER COVERAGE.
 2010 FBC-B 903.2.7 MERCANTILE
 2010 FBC-B 903.2.9 S-1 STORAGE
  
 3) THE NEW STORAGE AREA DOES NOT INDICATE ANY EMERGENCY
 LIGHTING DEVICES IN EITHER THE NEWLY FORMED TENANT
 SPACE OR COMMON EXIT PASSAGE WAY. 2010 FBC-B 1006.1.1
 MEANS OF EGRESS ILLUMINATION. 1006.1.6.2 BATTERY
 OPERATED ELECTRIC LIGHTS.
  
 4) THE PLANS ARE ALSO MISSING EXIT LIGHTING AND
 SIGNAGE, 2010 FBC-B 1006.3.1 EVERY EXIT SIGN SHALL BE
 SUITABLY ILLUMINATED BY A RELIABLE LIGHT SOURCE.
  
 5) THE PLANS ARE ALSO MISSING EXIT DOOR TACTILE
 SIGNAGE, 2010 FBC-B 1006.3.4.
  
 6) THE TENANT BUILD-OUT PLAN UNDER PERMIT # 13040438
 AND THIS PLAN HAS A DISCREPANCY AS TO WHERE THE TENANT
 SEPERATION WALL AND DOORWAY ARE LOCATED AND THE SHARED
 EXIT PASSAGE WAY BEGIN. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7 ) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-15 Cont ID  
Sent By dharvey Date 2013-05-15 Time 11:56 Rev Time 0.00
Received By dharvey Date 2013-05-15 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-04-24 Cont ID  
Sent By dharvey Date 2013-04-24 Time 07:21 Rev Time 0.00
Received By dharvey Date 2013-04-23 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-05-11 Cont ID  
Sent By WJOLIN Date 2013-05-11 Time 20:25 Rev Time 0.00
Received By wjolin Date 2013-05-11 Time 20:12 Sent To  
Notes
2013-05-11 20:17:51701 SOUTH ROSEMARY AVENUE - #137
 PERMIT #13040437
 SEE ALSO PERMIT #13040438
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PREVIOUS COMMENTS SATISFIED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-16 Cont ID  
Sent By wjolin Date 2013-04-16 Time 13:31 Rev Time 0.00
Received By wjolin Date 2013-04-16 Time 13:04 Sent To  
Notes
2013-04-16 13:21:05701 SOUTH ROSEMARY AVENUE - #137
 PERMIT #13040437
 SEE ALSO PERMIT #13040438
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION AND SHEET A-1 INDICATE THE
 PROJECT ADDRESS AS 701 SOUTH ROSEMARY AVENUE; HOWEVER,
 THE MEP SHEETS INDICATE AN ADDRESS OF 700 SOUTH
 ROSEMARY AVENUE. PLEASE COORDINATE THE CORRECT ADDRESS.
  
 SHEET M-1: NO FIRE DAMPER PROVIDED IN DUCTWORK
 PENETRATING LANDLORD STORAGE ROOM #102.
  
 GENERAL: EACH FIRE BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: LANDLORD STORAGE #102 DOES NOT INDICATE ANY OF
 THE FOLLOWING INFORMATION: COMMODITY CLASS OF
 COMBUSTIBLES (PER NFPA 13), QUANTITY, STORAGE
 ARRANGEMENT (RACKS, PILE, BIN, ETC.), STORAGE HEIGHT,
 AISLE LAYOUT, ETC.
  
 GENERAL: PROVIDE PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 GENERAL: NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED.
 PER FBC SECTION 907.1.1 CONSTRUCTION DOCUMENTS -
 "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE
 FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS,
 ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-17 Cont ID  
Sent By hmoser Date 2013-05-17 Time 14:41 Rev Time 0.00
Received By hmoser Date 2013-05-09 Time 11:43 Sent To  
Notes
2013-05-10 11:44:48B21
2013-05-06 11:50:20INCOMING SENT TO C-33 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-26 Cont ID  
Sent By lmartine Date 2013-04-24 Time 13:50 Rev Time 0.00
Received By lmartine Date 2013-04-12 Time 10:02 Sent To  
Notes
2013-04-12 10:03:41INCOMING SENT TO B-18, "EXPEDITED" . JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-17 Cont ID  
Sent By MOSER Date 2013-05-17 Time 14:41 Rev Time 0.00
Received By hmoser Date 2013-05-17 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-23 Cont ID  
Sent By hmoser Date 2013-04-23 Time 11:32 Rev Time 0.00
Received By hmoser Date 2013-04-23 Time 09:50 Sent To  
Notes
2013-04-23 11:32:29PLANS DENIED
 1) LANDLORD'S PLAN AND MECHANICAL PLAN
 PERMIT # 13040438 DO NOT MATCH.LANDLORD PLAN
 SHOWS MAKE UP AIR AND EXHAUST GOING TO LANDLORD'S
 STORAGE. FIRE DAMPERS ARE REQUIRED AT THE MAKE UP AIR
 AND EXHAUST WALL PENETRATION.
 PER SECTION 607.5.2 FIRE BARRIERS.
 LANDLORD'S PLAN SHOW FIRE DAMPERS AS NEW,
 MECHANICAL PLAN SHOWS FIRE DAMPERS AS EXISTING.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-04-18 Cont ID  
Sent By eschneid Date 2013-04-18 Time 14:32 Rev Time 0.25
Received By eschneid Date 2013-04-18 Time 14:32 Sent To  
Notes
***NONE***