2013-04-16 13:21:05 | 701 SOUTH ROSEMARY AVENUE - #137 |
| PERMIT #13040437 |
| SEE ALSO PERMIT #13040438 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| THE PERMIT APPLICATION AND SHEET A-1 INDICATE THE |
| PROJECT ADDRESS AS 701 SOUTH ROSEMARY AVENUE; HOWEVER, |
| THE MEP SHEETS INDICATE AN ADDRESS OF 700 SOUTH |
| ROSEMARY AVENUE. PLEASE COORDINATE THE CORRECT ADDRESS. |
| |
| SHEET M-1: NO FIRE DAMPER PROVIDED IN DUCTWORK |
| PENETRATING LANDLORD STORAGE ROOM #102. |
| |
| GENERAL: EACH FIRE BARRIER SHALL BE PERMANENTLY |
| IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| CENTER. |
| |
| GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| DOORS WITH EXIT SIGNS. |
| |
| GENERAL: LANDLORD STORAGE #102 DOES NOT INDICATE ANY OF |
| THE FOLLOWING INFORMATION: COMMODITY CLASS OF |
| COMBUSTIBLES (PER NFPA 13), QUANTITY, STORAGE |
| ARRANGEMENT (RACKS, PILE, BIN, ETC.), STORAGE HEIGHT, |
| AISLE LAYOUT, ETC. |
| |
| GENERAL: PROVIDE PORTABLE FIRE EXTINGUISHERS. |
| EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT |
| EXCEED 75 FEET. |
| |
| GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT, |
| SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE |
| REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS |
| FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC |
| FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE |
| SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| |
| GENERAL: NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. |
| PER FBC SECTION 907.1.1 CONSTRUCTION DOCUMENTS - |
| "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE |
| FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS, |
| ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE |
| BUILDING OFFICIAL." |
| |