Plan Review Details - Permit 13040405
Plan Review Stops For Permit 13040405
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-04-24 Cont ID  
Sent By jwitmer Date 2013-04-22 Time 07:19 Rev Time 0.00
Received By jwitmer Date 2013-04-22 Time 07:11 Sent To  
Notes
2013-04-22 08:04:18BUILDING PLAN REVIEW
 PERMIT: 13040405
 ADD: 801 S OLIVE DR # 906
 CONT: COUNIHAN CONST
 TEL: (561)722-6266
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/22/2013
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THIS BUILDING IS A HIGHRISE A BUILDING TYPE IA.
 SHEET A1 INDICATES THE REMOVAL OF ALL FLOORING WITHIN
 THE UNITPLEASE SUBMIT DOCUMENTATION OF CODE COMPLIANCE
 FOR THE FOLLOWING:
  
 1A) COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1A) FOR STONE, MARBLE OR CERAMIC TILE , 603.1.3.2
 EXCEPTION # 1.EXCEPTION: 1. INSULATION PLACED BETWEEN
 TWO LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT AN
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 100.
  
 1B) WOOD FLOORS IN HIGH RISE BUILDINGS 805.1.2 WOOD
 FINISH FLOORING.
 WOOD FINISH FLOORING IS PERMITTED TO BE ATTACHED
 DIRECTLY TO THE TOP SURFACE OF FIRE-RESISTANCE-RATED
 FLOOR ASSEMBLIES . PROVIDE MANUFACTURERS INSTALATION
 INSTRUCTIONS.
  
 2) 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-03 Time 14:33 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 14:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-03 Cont ID  
Sent By shill Date 2013-05-03 Time 14:44 Rev Time 0.00
Received By shill Date 2013-04-11 Time 10:08 Sent To  
Notes
2013-04-12 10:09:38B11

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-04-15 Cont ID  
Sent By lwagner Date 2013-04-15 Time 08:56 Rev Time 0.00
Received By lwagner Date 2013-04-15 Time 08:51 Sent To  
Notes
***NONE***