Plan Review Stops For Permit 13040379 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-04-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-04-17 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-04-17 |
Time |
16:34 |
Sent To |
|
|
Notes |
2013-04-17 16:34:28 | ****CORRECTIONS**** | | REVISED 5/9/13 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. TWO COMPLETE SETS OF DOCUMENTS ARE REQUIRED FOR | | ISSUANCE, FBC 107. ONLY ONE SET OF DRAWINGS/ENGINEERING | | SUBMITTED. | | | | 2. ENGINEER OF RECORD TO REVIEW MODIFIED PRODUCT | | APPROVAL, FBC 107. | | | | 3. CONFIRM THAT THE INSTALLED DOOR IS LESS THAN 82" | | HIGH, SEE "ANALYSIS AND FINDINGS" IN THE ENGINEER'S | | LETTER. IF THE INSTALLED DOOR IS TALLER THAN 82", | | ENGINEERING FOR THE ADA THRESHOLD IS TO BE REVISED. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-04-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-04-17 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-04-11 |
Time |
08:23 |
Sent To |
|
|
Notes |
2013-04-11 08:23:13 | TO SH DESK | | |
|
|
|