Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-18 Cont ID  
Sent By JWITMER Date 2013-06-18 Time 15:16 Rev Time 0.00
Received By jwitmer Date 2013-06-18 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-23 Cont ID  
Sent By jwitmer Date 2013-04-23 Time 13:06 Rev Time 0.00
Received By jwitmer Date 2013-04-23 Time 07:03 Sent To  
Notes
2013-04-23 13:03:55BUILDING PLAN REVIEW
 PERMIT: 13040308
 ADD: 2901 TUXEDO AVENUE
 CONT: WEST CONSTRUCTION
 TEL: (561)588-2027
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1 ST REVIEW
 DATE: APRIL 23/ 2013
 ACTION: DENIED
  
 1) SHEET A1.00:
 1A ) UNDER THE HEADING OF SITE CODE COMPLIANCE THE
 PLANS INDICATE 13 NEW PARKING SPACES BUT THERE IS A
 TOTAL OF 85 PARKING SPACES THAT WILL REQUIRE 4
 ACCESSIBLE PARKING SPACES SEE THE 2010 FL ACCESSIBILITY
 CODE TABLE 208.2.
  
 1B) THE PLANS ALSO SHOW THE 2 ACCESSIBLE PARKING SPACES
 GROUPED TOGETHER. THE 2010 FL ACCESSIBILITY CODE
 SECTION 208.3.1 WHEN PARKING SERVES MORE THAN ONE
 ACCESSIBLE ENTRANCE, PARKING SPACES COMPLYING WITH 502
 SHALL BE DISPERSED AND ON THE SHORTEST ACCESSIBLE ROUTE
 TO THE ACCESSIBLE ENTRANCE.
  
 1C) THE NEW PARKING SPACES SHOWN TO THE NORTH OF THE
 BUILDING ARE DOUBLE STRIPED TO THE CITY ZONING STANDARD
 BUT THE PARKING TO THE WEST OF THE BUILDING ARE SINGLE
 STRIPED AND ARE BEING RE-STRIPED. THEY WILL NEED TO BE
 DOUBLE STRIPED TO MEET THE CITY ZONING STANDARDS.
  
 1D) JUST A NOTE OF CAUTION ON THE REDESIGN, 2010 FL
 ACCESSIBILITY CODE 208.3.1 ALL SPACES MUST BE LOCATED
 ON AN ACCESSIBLE ROUTE THAT IS 44 INCHES WIDE AND SO
 THAT USERS ARE NOT COMPELLED TO WALK OR WHEEL BEHIND
 VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE.
  
 1E) THIS BUILDING IS LOCATED IN A FLOOD ZONE, A-9 AND
 WILL NEED FLOOD ZONE CERTIFICATES:
 1) BEFORE THE ISSUANCE OF THE PERMIT WITH PROPOSED
 ELEVATION OF FINISHED SLAB IN
 NGVD.
 2) ONCE THE FLOOR SLAB HAS BEEN POURED AND FINISHED.
 3) BEFORE THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY,
 OR CERTIFICATE OF
 COMPLETION.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET LS1.01:
 2A) NEW SUPPLY AND STORAGE ROOM # 116 AND OFFICE # 114,
 MISSING OCCUPANCY SEPARATION BETWEEN THESE OCCUPANCIES.
 THIS STORAGE AREA IS LARGER THAN 10 % OF THE BUILDING
 FOOTPRINT NO LONGER BEING CLASSIFIED AS A ACCESSORY
 OCCUPANCY. FBC-B 508.2.1.
  
 2B) THE NEW MECHANICAL ROOM # 129 AND STORAGE ROOMS TO
 THE EAST ARE MISSING THE OCCUPANCY SEPARATION WALL
 CLASSIFICATION WITH THE ASSEMBLY OCCUPANCY, FBC-B TABLE
 508.4.
  
 2C) THE NEW MECHANICAL ROOM # 123 INDICATES 2 OF THE
 WALLS WITH A OCCUPANCY SEPARATION RATING BUT MISSING
 THE OTHER 2 WALLS, FBC-B TABLE 508.2.5.
  
 2D) SHEET A.101 WALL TAGS IDENTIFYING WALL TYPE DO NOT
 INDICATE RATED WALL OCCUPANCY SEPARATION AS SHOWN ON
 THE LS PLAN. WALLS TYPES LOCATED ON SHEET A5.01 DOORS
 ON A7.01.
  
 3) SHEET A5.02
 3A) DETAIL # 5 NEW RAMP, PLEASE SEE HANDRAIL HEIGHT AT
 STAIR, 2010 FL ACCESSIBILITY CODE 505.4 HANDRAIL HEIGHT
 BETWEEN 34?-38?.
  
 3B) DETAIL # 5 ALSO IS MISSING THE HANDRAIL EXTENSIONS
 REQUIRED BY FL ACCESSIBILITY CODE 505.10.
  
 3C) DETAIL #9 THE WALL MOUNTED DETAIL INDICATES THE
 MINIMUM DISTANCE FROM THE WALL IS 2 ? INCHES PLEASE
 REVIEW 2010 FL ACCESSIBILITY CODE 505.5 CLEARANCE.
  
 3D) DETAIL # 6 & 8 THE BOTTOM LANDING IS NOT
 DIMENSIONED BUT SCALES OUT LESS THAN 5?-0? IN LENGTH (
 DIRECTION OF TRAVEL) SEE FL ACCESSIBILITY CODE 405.7.3.
  
 4A) SHEET A4.01, A4.02 & A5.04 BRICK WALL DETAILS 1 &
 2, PLEASE REVIEW 2010 FBC-B SECTION 2114.2 CONCRETE
 BEARING LEDGE. BRICK, STONE OR OTHER VENEER SHALL BE
 SUPPORTED BY A CONCRETE BEARING LEDGE AT LEAST EQUAL TO
 THE TOTAL THICKNESS OF THE BRICK, STONE OR OTHER
 VENEER, WHICH IS POURED INTEGRALLY WITH THE CONCRETE
 FOUNDATION. NO SUPPLEMENTAL CONCRETE FOUNDATION POURS
 WHICH WILL CREATE A HIDDEN COLD JOINT SHALL BE USED
 WITHOUT SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS
 THERE IS AN APPROVED PHYSICAL BARRIER. AN APPROVED
 PHYSICAL BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE
 WALL SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO
 EMBED IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS
 BELOW GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE
 APPLIED TO THE CAVITY CREATED BETWEEN THE VENEER AND
 THE FOUNDATION, IN LIEU OF A PHYSICAL BARRIER.
  
 EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL
 SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH
 TMS 402/ACI 530/ASCE 5, PROVIDED AT LEAST A 6-INCH (152
 MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL
 EXTERIOR EXISTS BETWEEN THE VENEER AND THE TOP OF ANY
 SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING
 COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK
 IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE.
  
 4B) PLANS DO NOT INDICATE HOW THE BRICK VENEER WILL BE
 ATTACHED TO THE CMU WALL, PROVIDE COMPLIANCE WITH 2010
 FBC-B 1405.6 ANCHORED MASONRY VENEER.
  
 5) COMPLIED SEE SHEET G0.01 FOR APPROVAL OF COMPONENTS
 & CLADDING PRODUCT APPROVALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
2013-04-17 16:08:25 
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-18 Cont ID  
Sent By dharvey Date 2013-06-18 Time 11:32 Rev Time 0.00
Received By dharvey Date 2013-06-18 Time 11:08 Sent To  
Notes
2013-06-18 11:32:33SENCOND REVIEW BY RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-07 Cont ID  
Sent By dharvey Date 2013-05-07 Time 10:23 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 14:45 Sent To  
Notes
2013-05-07 10:23:50SHEET E3.01 ? EXHAUST FAN TO REMAIN RUNNING UPON ANSUL
 ACTIVATION
 E6.01 GENERATOR REQUIRES EQUIPMENT GROUNDING CONDUCTOR,
 CONNECTED AFTER MAIN DISCONNECT AND INDICATION OF
 GENERATOR SIZE AND OCP
 PROVIDE AIC RATING OF SECOND 800A MAIN AT MDP
 FEEDER SCHEDULE CHART SHOWS EGC SPLIT FOR PARALLEL. EGC
 TO BE FULL SIZE PER 250.122 (F)
 PLEASE PROVIDE INFORMATION REGARDING TRANSFER AND
 TRANSFER SWITCH AS TO IF MAIN AND TRANSFER ARE ONE
 PIECE OF GEAR AND RATED FOR SERVICE ENTRANCE, HOW
 TRANSFER IS ACCOMPLISHED, 3 POLE OR 4 POLE, NEUTRALS
 AND GROUNDS ARE TO BE SEPARATED AFTER THE FIRST MEANS
 OF DISCONNECT. PLANS DO APPEAR CLEAR FOR THIS
 INFORMATION.
 PROVIDE AIC RATING OF CT CAN AND COORDINATE WITH
 SYSTEM.
 PROVIDE ENERGY CODE COMPLIANCE STATEMENT AND ENERGY
 BUDGET CALCULATIONS
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-07-19 Cont ID  
Sent By Mgonzale Date 2013-07-19 Time   Rev Time 1.00
Received By shill Date 2013-07-05 Time 10:07 Sent To FIRE
Notes
2013-07-19 15:42:54PASSED WITH PROVISO:
  
 #1 PROVIDE SEPERATE SUBMITTAL TO ENGINEERING SERVICES
 DEPARTMENT.
  
 #2 WATERMAIN EXTENSION PROPOSED IN ROW MUST BE
 PERMITTED THRU PALM BEACH COUNTY HEALTH DEPARTMENT.
  
 #3 ROW PERMIT IS ALSO REQUIRED.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-05-16 Cont ID  
Sent By wjolin Date 2013-04-27 Time 17:53 Rev Time 0.00
Received By wjolin Date 2013-04-27 Time 16:16 Sent To  
Notes
2013-04-27 17:42:152901 TUXEDO AVENUE
 PERMIT #13040308
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THIS IS A STATE FACILITY; THEREFORE, THE FLORIDA
 STATE FIRE MARSHAL'S OFFICE HAS JURISDICTION AND IS
 RESPONSIBLE FOR PLAN APPROVAL AND FIRE INSPECTIONS. WPB
 FIRE RESCUE WILL PERFORM A COURTESY FIRE PLAN REVIEW
 ONLY:
  
 ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 REFER TO
 NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH
 FLORIDA AMENDMENTS.)
  
 SHEET LS1.01: UPDATE THE CODE LIST TO REFERENCE THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, ?FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.?
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE BUILDING ADDRESS VISIBLE FROM THE
 STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND
 BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND
 SHALL CONTRAST THE BACKGROUND.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 SHEET LS1.01: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING
 FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM
 POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM
 THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET LS1.01 & A7.01: FOR ASSEMBLY OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS, PANIC/FIRE EXIT
 HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE THE
 LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED
 THAT WOULD NOT BE RELEASED BY THE PANIC/FIRE EXIT
 HARDWARE. CLEARLY INDICATE ALL DOORS TO BE EQUIPPED
 WITH PANIC OR FIRE EXIT HARDWARE.
  
 SHEET E4.01: PER SECTION 13.3.4.3.3, PROVIDE
 SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300
 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS.
  
 REHABILITATION: PER SECTION 43.6.4.1, IN A BUILDING
 WITH REHABILITATION WORK AREAS INVOLVING OVER 50
 PERCENT OF THE AGGREGATE BUILDING AREA, AUTOMATIC
 SPRINKLER SYSTEMS SHALL BE PROVIDED ON THE HIGHEST
 FLOOR CONTAINING A REHABILITATION WORK AREA AND ON ALL
 FLOORS BELOW IN ACCORDANCE WITH THE REQUIREMENTS OF
 OTHER SECTIONS OF THIS CODE APPLICABLE TO NEW
 CONSTRUCTION FOR THE OCCUPANCY. PER SECTION 12.3.5.2
 (NEW ASSEMBLY OCCUPANCY), ANY BUILDING CONTAINING ONE
 OR MORE ASSEMBLY OCCUPANCIES WHERE THE AGGREGATE
 OCCUPANT LOAD OF THE ASSEMBLY OCCUPANCIES EXCEEDS 300
 SHALL BE PROTECTED BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM. PER SECTION 43.8.1.2, AN ADDITION
 SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY WITH
 REGARD TO FIRE SAFETY OR THE MEANS OF EGRESS IN THE
 EXISTING BUILDING FOR WHICH THE ADDITION IS
 CONSTRUCTED.
  
 FIRE SPRINKLERS: FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 NOTE: SEPARATE SHOP DRAWINGS AND SUB-PERMITS NEEDED FOR
 FIRE ALARM, FIRE SPRINKLER, KITCHEN HOOD AND KITCHEN
 HOOD SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-04-18 Cont ID  
Sent By lwagner Date 2013-04-18 Time 09:36 Rev Time 0.00
Received By lwagner Date 2013-04-17 Time 10:06 Sent To  
Notes
2013-06-07 09:40:026/7/13 UPDATE
 U/G GAS IS P.E. SHOWN ON P 3.00 OK
2013-04-18 09:35:55FBC 2010 FUEL GAS REVIEW #1
 ***PROVISO***
  
 SHEET P3.00 THE GAS DIAGRAM LISTS THE MATERIAL AS
 SCHEDULE 40 METALIC PIPE. THE RUN FROM THE PROPANE TANK
 APPEARS TO BE UNDERGROUND. 404.9 PROTECTION AGAINST
 CORROSION. ZINC COATINGS (GALVANIZING) SHALL NOT BE
 DEEMED ADEQUATE PROTECTION FOR GAS PIPING UNDERGROUND.
 404.9.2 PROTECTIVE COATINGS AND WRAPPING.
 PIPE PROTECTIVE COATINGS AND WRAPPINGS SHALL BE
 APPROVED FOR THE APPLICATION AND SHALL BE FACTORY
 APPLIED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-19 Cont ID  
Sent By jwitmer Date 2013-07-19 Time 16:19 Rev Time 0.00
Received By jwitmer Date 2013-06-03 Time 16:03 Sent To  
Notes
2013-06-03 16:03:44C30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-03 Cont ID  
Sent By rmcdouga Date 2013-06-03 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2013-04-09 Time 11:09 Sent To  
Notes
2013-04-12 11:09:46SENT TO C30 SHELF FOR REVIEW. JG.

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2013-06-20 Cont ID  
Sent By ajones Date 2013-06-20 Time 09:49 Rev Time 0.00
Received By ajones Date 2013-06-20 Time 09:49 Sent To  
Notes
2013-06-20 09:50:15REQIRES SEPERATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-07-03 Cont ID  
Sent By hmoser Date 2013-07-03 Time 14:32 Rev Time 0.00
Received By hmoser Date 2013-07-03 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-18 Cont ID  
Sent By hmoser Date 2013-04-18 Time 15:09 Rev Time 0.00
Received By hmoser Date 2013-04-17 Time 13:56 Sent To  
Notes
2013-04-18 15:09:50PLANS DENIED
 1) NEW MECHANICAL ROOM # 129 IS MISSING FIRE DAMPERS
 INTO ROOMS 127 AND 128.
 PER SECTION 607.5.1 FIRE WALLS 2010 FBC (M)
 2) REFER TO SECTION 501.2.1 LOCATION OF EXHAUST
 OUTLETS.
 2010 FBC (M)
 3) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION.
 2010 FBC (M)
 4) PROVIDE ALL DUCT SIZE ON AIR HANDLER # 5 ON THE
 PLANS
 5) PROVIDE A DETAIL ON THE PLANS FROM THE ENGINEER ON
 HOW THE
 DEHUMIDIFIER STAND IS MOUNTED TO THE WALL.PER SECTION
 301.12
 WIND RESISTANCE
 6) PROVIDE A DETAIL FROM THE ENGINEER ON HOW THE
 EXHAUST FAN
 CURB IS TIED DOWN TO THE ROOF AND EXHAUST FAN IS TIED
 TO THE CURB .
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 7) PLEASE CLARIFY THE BATHROOM EXHAUST ON THE PLANS
 PER SECTION 107 FBC 2010
 8) KITCHEN HOOD REQUIRE SEPARATE APPLICATION PLANS AND
 PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2014-08-28 Cont ID  
Sent By shill Date 2014-08-28 Time 08:15 Rev Time 0.00
Received By shill Date 2014-08-28 Time 08:15 Sent To  
Notes
2014-08-28 08:15:19FINISHED CONSTRUCTION EC OK
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2014-08-27 Cont ID  
Sent By shill Date 2014-08-27 Time 15:09 Rev Time 0.00
Received By shill Date 2014-08-27 Time 15:09 Sent To  
Notes
2014-08-27 15:10:11EC SENT VIA EMAIL, PREPARED BY JORGE R. AVINO:
  
 PLEASE SEE ELEVATION CERTIFICATE INSTRUCTIONS:
  
 1. PLEASE EXPLAIN C2A AND B. TOP OF BOTTOM FLOOR IS
 19.97, NEXT HIGHER FLOOR IS 18.02. IT APPEARS THAT THE
 NUMBERS ARE REVERSED. EITHER REVISE OR CALL ME TO
 DISCUSS.
  
 2. ITEM A5, IF DEGREES, MINUTES, SECONDS FORMAT IS
 USED, SECONDS TO BE PROVIDED TO 1 DECIMAL PLACE OR
 BETTER
  
 EXAMPLE: 26? 42' 35.8",-80? 12' 1.3"
  
 3. ITEM C2E, LOWEST ELEVATION OF MACHINERY OR EQUIPMENT
 SERVICING THE BUILDING, AND THEN DESCRIBE IN COMMENTS.
 THE EQUIPMENT WAS DESCRIBED, ALONG WITH ELEVATION, IN
 THE COMMENTS SECTION, BUT THE ELEVATION NEEDS TO BE IN
 ITEM C2E (PER EMAIL FROM ISO AUDITOR).
  
 4. ITEM C2H, LOWEST ELEVATION OF STAIRS IS N/A, BUT THE
 BUILDING HAS STAIRS, PLEASE REVISE TO INCLUDE THE
 ELEVATION.
  
 PLEASE MAKE THESE CORRECTIONS (OR, IF YOU DISAGREE,
 CALL ME TO DISCUSS) AND MAIL A SIGNED AND SEALED
 ORIGINAL DIRECTLY TO ME. PLEASE USE THE IMPRESSION TYPE
 SEAL AND AN ORIGINAL SIGNATURE. SINCE THIS IS HOLDING
 UP A C.O., I'D RECOMMEND SENDING VIA OVERNIGHT OR
 SECOND DAY DELIVERY SERVICE.
  
 THANK YOU FOR YOUR COOPERATION AND PATIENCE. WITH EVERY
 COMMUNITY ASSISTANCE VISIT WITH FEMA (AKA "AUDIT") WE
 LEARN MORE ABOUT THESE ELEVATION CERTIFICATES!
  
 REGARDS,
  
 SAMANTHA
  
  
 SAMANTHA M. HILL
 BUILDING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-805-6724
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-07 Cont ID  
Sent By lwagner Date 2013-06-07 Time 09:42 Rev Time 0.00
Received By lwagner Date 2013-06-07 Time 09:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-04-18 Cont ID  
Sent By lwagner Date 2013-04-18 Time 09:48 Rev Time 0.00
Received By lwagner Date 2013-04-15 Time 13:34 Sent To  
Notes
2013-04-18 09:39:09 
 FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET PD2.00 A HOLE IS REQUIRED IN THE BOTTOM OF THE
 ABANDONED GREASE TRAP PER HEALTH DEPT.
  
 2. SHEET A6.03 THE ACCESSAIBLE SHOWER STALLS DO NOT
 MEET UFAS FIGURE 35(A) OR FBC ACCESSIBILITY FIGURE
 608.2.1 FOR CLEAR SPACE.
 CLEARANCE OF 36 INCHES (915 MM) WIDE MINIMUM BY 48
 INCHES (1220 MM) LONG MINIMUM MEASURED FROM THE CONTROL
 WALL SHALL BE PROVIDED.
  
 3. SHEET A6.05 DETAIL 10 PLEASE SUBMIT THE APPROVALS
 FOR THE LIQUID APPLIED WATERPROOFING.
 P-417.5.2.5 SHEET-APPLIED, LOAD-BEARING, BONDED,
 WATERPROOF MEMBRANES. SHEET-APPLIED, LOAD-BEARING,
 BONDED, WATERPROOF MEMBRANES SHALL MEET REQUIREMENTS OF
 ANSI A118.10 AND SHALL BE APPLIED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By jwitmer Date 2013-06-18 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2013-06-18 Time 09:09 Sent To  
Notes
2013-09-16 09:10:29OK PER PRODUCT APPROVALS. JW

Review Stop Z ZONING
Rev No 2 Status P Date 2013-06-20 Cont ID  
Sent By ajones Date 2013-06-20 Time 09:48 Rev Time 0.00
Received By ajones Date 2013-06-20 Time 09:48 Sent To  
Notes
2013-06-20 09:49:376/20/13- APPROVED,BUT THE LANDSCAPING PLANS ARE NOT
 PART OF THIS APPROVAL. A SEPERATE PERMIT IS REQUIRED.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2013-05-08 Cont ID  
Sent By avann Date 2013-05-08 Time 12:56 Rev Time 0.00
Received By ajones Date 2013-05-08 Time 12:56 Sent To  
Notes
2013-05-08 12:57:475-8-13 WAITING ON CONTRACTOR TO BRING IN SEPERATE
 APPLICATION FOR LANDSCAPING AND PARKING.
  
 ANGELLA VANN
 561-822-1441
 [email protected]
2013-04-23 09:34:424/23/13