Plan Review Details - Permit 13040277
Plan Review Stops For Permit 13040277
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-04-19 Cont ID  
Sent By jwitmer Date 2013-04-19 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2013-04-19 Time 09:54 Sent To  
Notes
2013-04-19 11:20:31BUILDING PLAN REVIEW
 PERMIT: 13040277
 ADD: 1801 S FLAGLER # 1711
 CONT: FREDRICK BLACK & ASSOCIATES
 TEL: (561)547-4772
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 DATE:
 ACTION: BUILDING PROVISO:
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET 1 UNDER THE HEADING FINISHES: REPLACE CERAMIC
 TILE IN BATHROOMS AND LAMINATED PARQUET ALL OTHER
 AREAS. "EASY MAT" SOUND PROOFING UNDERLAYMENT ECB75.
 NO PRODUCT DATA WAS SUBMITTED PROVIDING COMPLIANCE WITH
 THE LISTED CODE SECTIONS;
 2010 FBC-B 603.2
 1A) (CERAMIC TILE ) (1). INSULATION PLACED BETWEEN TWO
 LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT AN
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 100.
  
 1B) (WOOD PARQUET FLOORING) (2) INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 2) 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3) DOCUMENTS WILL NEED TO BE SUBMITTED TO THE DESIGNER
 OF RECORD FOR SHOP DRAWING STAMP REVIEW BEFORE
 SUBMITTAL TO THE BUILDING DEPARTMENT. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC...
  
 DOCUMENTS WILL NEED TO BE IN AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE FRAMING INSPECTION APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-04-30 Cont ID  
Sent By dharvey Date 2013-04-30 Time 15:08 Rev Time 0.00
Received By dharvey Date 2013-04-30 Time 15:08 Sent To  
Notes
2013-04-30 15:10:00PROVIDE AFCI TYPE BREAKERS AND TAMPER RESISTANT
 RECEPTACLES AS REQUIRED BY THE N E C

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-04-20 Cont ID  
Sent By wjolin Date 2013-04-20 Time 10:35 Rev Time 0.00
Received By wjolin Date 2013-04-20 Time 10:28 Sent To  
Notes
2013-04-20 10:35:281801 SOUTH FLAGLER DRIVE - #1711
 PERMIT #13040277
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EXISTING APARTMENT BUILDINGS NOT PROTECTED BY AUTOMATIC
 SPRINKLERS OR A COMPLETE AUTOMATIC SMOKE DETECTION
 SYSTEM SHALL HAVE SINGLE STATION OR MULTI-STATION SMOKE
 ALARMS (HARD-WIRED OR BATTERY POWERED) INSTALLED INSIDE
 EACH BEDROOM AND DIRECTLY OUTSIDE BEDROOM DOORS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-30 Cont ID  
Sent By dharvey Date 2013-04-30 Time 15:09 Rev Time 0.00
Received By dharvey Date 2013-04-30 Time 15:08 Sent To  
Notes
2013-04-09 07:53:01INCOMING SENT TO B-14 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-04-15 Cont ID  
Sent By hmoser Date 2013-04-15 Time 08:48 Rev Time 0.00
Received By hmoser Date 2013-04-15 Time 08:37 Sent To  
Notes
2013-04-15 08:48:15AIR CONDITIONING CONTRACTOR SHALL SUBMIT APPLICATION
 AND PLANS FOR PERMIT ON NEW OFFICE/DEN AND
 VENTILATION FOR BATHROOM.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-04-09 Cont ID  
Sent By lwagner Date 2013-04-09 Time 15:43 Rev Time 0.00
Received By lwagner Date 2013-04-09 Time 14:55 Sent To  
Notes
***NONE***