Plan Review Details - Permit 13040088
Plan Review Stops For Permit 13040088
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-04-26 Cont ID  
Sent By lwagner Date 2013-04-26 Time 13:10 Rev Time 0.00
Received By lwagner Date 2013-04-26 Time 13:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2013-04-03 Cont ID  
Sent By lwagner Date 2013-04-03 Time 10:23 Rev Time 0.00
Received By lwagner Date 2013-04-03 Time 10:18 Sent To  
Notes
2013-04-03 10:23:36FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 NOT ENOUGH INFORMATION FOR REVIEW. PLEASE SUBMIT
 THEFOLLOWING:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC?2010 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC?2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC?2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC?2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC?2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805?6692
 EMAIL [email protected]
 FAX # 805?6676
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-03 Cont ID  
Sent By lwagner Date 2013-04-03 Time 10:23 Rev Time 0.00
Received By lwagner Date 2013-04-03 Time 07:33 Sent To  
Notes
2013-04-03 07:33:45INCOMING SENT TO <$5K PLUMBING BOX. JW